Title Page
-
Document Number
-
Site conducted
-
Conducted on
-
Prepared by
Sign Off Sheet
- Block Handover
-
Work Area (DC Blocks / MV MV JB etc)
-
All the trenches / holes been backfilled
-
Pile position from Tracker 700mm
-
Are there any bent / damaged piles?
-
Combiner piles straight and aligned (Only piles damaged by JLE, if any)
-
Cable Lengths of String / Subarrays / Earths at pile are correct lengths
-
Subarray / String Cables in good condition and in position minimum 300mm on torque tube
-
Cables Labelled, Pos and Neg installed and present (Ensuring temporary labelling is correct as per schedules)
-
Conduit heights / positions at Combiner Box / Support piles are correct
-
General Condition of the area (Rubbish, excess materials / spoils etc) are acceptable
PCU
-
Survey peg locations, column positions. As PCU’s must be positioned in reference to the cable position what do the markings reference for us to confirm positioning
-
Cable lengths at PCU in good condition and are correct lengths
-
Conduits left at 300mm at MV end and LV Aux panel. 75mm Above FSL for conduits
-
DC feeder conduits cut 75mm above finished level
-
All earths present and in correct locations and at least 1m length - EL - OOELE - DWG - 471
-
Terminations only to be connected and torqued after the back fill and compaction completed. As specified in STSP-SMEC-EL-00ELE-DWG-423 - Applies to handover worth pointing out
-
Terminations only to be connected and torqued after the back fill and compaction completed. As specified in STSP-SMEC-EL-00ELE-DWG-423 - (Applies to handover)
-
Pads stripped back to correct size
MV Junction Box
-
Earth bonding tails present correct size and correct length
-
Pad level / condition/ size as per acceptable SOW
-
MV cables all present, labelled and sealed from moisture
-
Correct cable and conduit size