Title Page
-
Audit Title
-
Apprentice Name
-
Conducted on
-
Prepared by
-
Location
-
Assessed By
Practical Assessment
Install 3 phase outlet
-
Correct Polarity
- Competent
- Further training
- Not Applicable
-
Terminations
- Competent
- Further training
- Not Applicable
-
Add media
-
Comments
Install 2 way light Switch
-
Correct Polarity
- Competent
- Further training
- Not Applicable
-
Switches operate correctly
- Competent
- Further training
- Not Applicable
-
Terminations
- Competent
- Further training
- Not Applicable
-
Comments
-
Add media
Testing
-
Test for dead - Prove meter on a known supply - Test all conductors
- Competent
- Further training
- Not Applicable
-
Phase Rotation - Connect Phase rotation meter to each phase - Energex supply into the building is anti lock wise 321 or CBA - Most fans and motors are require clockwise rotation 123 or ABC - To change supply rotation change any 2 phases.
- Competent
- Further training
- Not Applicable
-
Insulation Resistance - Ensure earth and metering is disconnected from circuit when testing - Test voltage must be twice the nominal voltage - Test Single phase circuits at 500V, ensure circuit is disconnected from the RCD. Test at 250V if there are circuits that contain electronic equipment that cannot be disconnected. - Test 3 phase circuits at 1000V. - Test shall be no lower than 1M Ohm unless it is for a sheathed heating element which shall be no less than 0.01M Ohm
- Competent
- Further training
- Not Applicable
-
Earth Continuity - Use a trailing earth lead to each point from the Switchboard - The resistance of the Main Earthing conductor or any equipotential bonding conductor shall be no less than 0.5 Ohm. - For final sub-circuits the resistance values for the earthing conductor are given in table 8.2 in the AS 3000 as a function of the rating associated with the over current protective device.
- Yes
- No
- N/A
-
Earth Fault Loop Impedance - This test is to ensure that the impedance of the circuit is low enough for the circuit breaker to trip within the required time if a fault occurred - Table 8.1 in AS 3000 provides Maximum values of impedance based on 230V. - To calculate the max fault loop impedance multiply the circuit breaker rating by 7.5 for C Type circuit breaker then divide the nominal voltage of the circuit by this value. (Example for a 20A breaker 7.5x20=150. For a 240V circuit 240/150=1.6 Ohms)
- Yes
- No
- N/A
-
RCD Testing - There are 2 types of RCD (Type 1 - 10mA for Medical installations and Type 2 - 30mA for all other installations) - Ensure RCD’s offer RCD and circuit overload protection - Additional protection by RCD required for final sub circuits up to 32A
- Competent
- Further training
- Not Applicable
Other Items Covered
-
Item
-
Comments
-
Add media
Attendance
-
Add signature