Title Page
-
Client
-
Address
-
Type of Premises
-
Conducted on
-
Prepared by
-
Fire Risk Assessment Type
-
Responsible Person
-
Fire Risk Assessment number
-
Front Elevation Photograph
Limitations of this inspection
-
This fire risk assessment (FRA) has been undertaken based on the Fire Risk Assessment Company’s <br>understanding of the building’s current design, use, fire strategy and evacuation procedures. It provides an <br>assessment of the risk to life from fire and does not address building or property protection, or business <br>continuity. This report is not an assurance against risk and is based on the best judgement of the Fire Risk <br>Assessment Company. <br>This FRA may rely on information supplied by others and no liability is accepted for the accuracy of such <br>information. Where information has been provided (e.g. regarding corporate policies and procedures or <br>systems maintenance) this will be considered as confirming compliance unless evidence to the contrary is <br>found during the assessment. <br>Information contained in this report should not be relied upon and used by third parties without the express <br>permission of the Fire Risk Assessment Company. <br>This FRA should be subject to review not later than the Recommended Reassessment Date stated in the <br>report or when: <br>a) material alterations to the premises take place; <br>b) a significant change occurs in the matters taken into account when the FRA was carried out; <br>c) a significant change to fire precautions occurs; or <br>d) there is any other reason to suspect that the original FRA might no longer be valid (this might include the <br>occurrence of a fire). <br>This FRA may identify areas to which access was not available during the inspection. In certain instances, the <br>Fire Risk Assessment Company may have made specific recommendations for further inspection in the report, <br>however, as general guidance it is recommended that any areas not accessed are inspected as soon as <br>possible. <br>Assessment of external wall construction and building structure is required for multi-occupied residential <br>buildings, but is a specialist area usually beyond the remit of fire risk assessors. In addition, the level of <br>intrusive access required for complete assessment is impossible to achieve during a non-intrusive FRA. The <br>Fire Risk Assessment Company will therefore usually rely on the provision (by the Client Organisation) of <br>accurate information and assessments by experts when considering the adequacy of these elements. In some <br>cases, it may be appropriate for external walls to be assessed during the FRA but this is limited to low-rise <br>buildings of traditional construction, utilising non-combustible materials, where there is minimal risk of <br>external fire spread. Where the FRA includes an assessment of the external walls, this is based on a nonintrusive visual inspection from ground level and should not be considered as comprehensive. <br>Where it is necessary to establish the height of the top storey to determine the applicability of certain <br>regulations this information is expected to have been supplied by the responsible person. Where this is not <br>made available an estimate will be made using a typical floor to floor height value of 3.0m. It should be noted <br>that this might not be accurate in non-typical buildings and may lead to the incorrect application of legislative <br>requirements. <br>Where this FRA makes comments about fire safety systems these are assumed to have been designed and <br>installed in accordance with the relevant guidance. Inspections of such systems during the FRA are limited to <br>a visual check with no testing being carried out. <br>Where new works, alterations or extensions are noted on-site it is assumed that all appropriate consents and <br>approvals have been obtained. <br>Recommendations made in this report may propose works to be completed which are subject to consents or <br>approvals under other legislation. The Client Organisation should ensure that all appropriate consents and <br>approvals are obtained prior to commencement of any such works. It is assumed that recommendations <br>made in this report will be progressed and carried out by persons who are qualified and competent to do so. <br>Where recommendations made in this report include quantities, these are estimated, indicative values which <br>should not be relied upon without confirmation/remeasurement. <br>Where this report refers to technical guidance such as British Standards it should be taken to be the most <br>recently updated version irrespective of the version cited. If in doubt about any matters relating to the <br>guidance cited reference should be made back to the Fire Risk Assessment Company for clarification
Recommendation Priorities
-
All recommendations made for remedial action as result of the fire risk assessment are assigned a priority in this report. The priorities used have an associated timescale for completion of the recommendations. These are as follows: Recommendation Priorities: Recommended Timescales Ultra-high risk - 1 day High risk - 3-6 months Medium risk - 6-12 months Low risk - 12-24 months Management 1 - 1 month Management 2 - 12 months
The Premises
-
Building description
-
Number of floors
-
Areas accessed
-
Areas not accessed
-
Building Construction
-
Floor/ storey area
-
Management extent/ type
-
Responsible person for Fire Safety matters
-
Person consulted during the Fire Risk Assessment
-
Number of residents/ persons in the premises
-
Type of occupants
-
Any other information relating to the premises
-
Photographs of the site
Fire Safety Legislation
-
Fire Safety Legislation applied for this premises
External Wall Assessment (Visual inspection only)
-
(a) Wall Construction
-
(b) Wall attachments and features
-
(c) Window and door details
-
(d) Window spandrels and infill panel details
-
(e) Risks and mitigation
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
External photographs
Prevent/ Reduce Fire Hazards
1. Electrical Fire Hazards - Elimination & Reduction
-
1.1 Was the electrical intake/ meter equipment/ cupboard accessed?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
1.3 Portable Appliance Testing (PAT) being carried out annually (if required)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
1.3 Does the common/ portable electrical equipment appear in good condition?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
1.4 Are the common electrical wiring cables secured according to BS7871:2018 - to ensure they do not collapse in a fire situation?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
1.5 Is all electrical equipment clear of combustibles?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
2. Heating Systems
-
2.1 Type of common fixed heating systems
-
2.2 Are there any portable heating system present?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
2.3 If there are gas heating systems present - are they enclosed in fire-rated construction/ routed within the building satisfactorily?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
3. Smoking Policies
-
3.1 Is there a 'No Smoking' policy and what arrangements are in place to implement it?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
3.2 Is there any evidence of smoking within the premises?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
4. Arson Prevention
-
4.1 What are the arrangements for waste materials/ refuse storage?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
4.2 Are the external escape routes clear/ any fire loading close to the building?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
4.3 Is the building secure?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
4.4 Are there any other issues relating to arson?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
5. Housekeeping
-
5.1 Is the common area clean and tidy?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
5.2 Are the common areas free of combustible/ trip hazards?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
5.3 Are there any hazardous material present/ stored on the premises?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
5.4 Are there any other housekeeping issues?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
6. Cooking Facilities
-
6.1 Type and extent of the cooking facilities.
-
6.2 Are there measures to prevent fires due to the cooking facilities?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
7. Contractors
-
7.1 Is there a policy in place regarding contractors and in-house staff in relation to fire safety, controls and restrictions (eg hot works undertaken)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
8. Any other issues regarding Fire Hazards (e.g. dangerous substances)?
-
8.1 Any other issues relating to Fire Hazards within the premsies?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
Fire Safety
9. Fire Alarm Systems
-
9.1 Does the building have a fire detection system present?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
9.2 Does the fire alarm system appear to be in good working condition?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
9.3 If within the complex bulding - does the fire alarm have a zone plan displayed?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
9.4 Is the fire alarm suitable for this type of building/ type/ risk?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
9.5 Is the fire alarm system monitored remotely?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
9.6 Are the sampled flats/ bedrooms provided with individual Grade LD3 smoke alarms?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
9.7 Are they any other issues relating to the fire alarm systems?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
10. Means of Escape
-
10.1 Is the evacuation strategy appropriate for this building?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.2 Is the means of escape satisfactory?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.3 Are the means of escape protected?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.4 Are there a suitable number of exits?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.5 Are all exits of a suitable width?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.6 Are all final exit doors easily openable (without use of a key)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.7 Are all steps/ stairs in good condition?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.8 Are all external paths/ routes in good repair?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.9 Are travels distances satisfactory?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.10 Are the means of escape provided with permanent/ manual openings for smoke control?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.11 Will disabled persons be able to escape from the building?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
10.12 Are there any other issues relating to the means of escape?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
11. Emergency Lighting
-
11.1 Is emergency lighting provided?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
11.2 Does the emergency lighting appear in good condition (visual check only)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
11.3 Does the emergency lighting cover the internal and external areas of the building sufficiently?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
11.4 Are there any other issues relating to the emergency lighting system?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
12. Flat/ Bedroom Entrance Fire Doors
-
12.1 Are all flat/ bedroom entrance doors fire-rated?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.2 Are all flat/ bedroom entrance doors in good condition (including letterboxes/ defects)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.3 Are all flat/ bedroom entrance doors sampled provided with self-closing devices?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.3.1 Are flat/ bedroom doors checked regularly to ensure self-closing devices are fitted and working correctly?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.4 Are all flat/ bedroom entrance doors provided with intumescent strips and cold smoke seals?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.4.1 Are flat/ bedroom entrance doors checked regularly to ensure intumescent strips and cold smoke seals are in place and are in good condition?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.5 Is the glazing to flat/ bedroom entrance doors fire-rated?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.6 Are the side panels and fan lights/ panels to flat/ bedroom entrance doors fire-rated?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.7 Are there any other issues relating to the flat/ bedroom entrance doors?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
12.8 Are there any other issues relating to the flat/ bedroom entrance doors?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
13. Common Area Fire Doors
-
13.1 Are all common area doors appropriately fire-rated?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
13.2 Are all common area fire doors in good condition?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
13.3 Are all common area fire doors sampled provided with self-closing devices?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
13.4 Are all common area fire doors provided with intumescent strips and cold smoke seals?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
13.5 Is the glazing to the common area doors fire-rated?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
13.6 Are the side panels and fan lights/ panels to the common area doors fire-rated?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
13.7 Are common area fire doors checked regularly to ensure they are in good condition?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
13.8 Are there any other issues relating to the common area fire doors?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
13.9 Are there any other issues relating to the common area fire doors?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
14. Compartmentation
-
14.1 Does the compartmentation appear satisfactory (limited visual inspection only)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.2 Are there any hidden voids present (if so are they fire-stopped/ enclosed)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.3 Are all services cupboards/ risers/ ducts enclosed in fire-resisting construction?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.4 Are electric meter boxes within the common parts suitably fire rated with no penetrations within?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.5 Are pipes/ services provided with suitable fire-stopping through the compartmentation walls?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.6 Are the roof space voids provided with suitable compartmentation?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.7 Is the electrical intake equipment adequately enclosed in fire-resisting construction?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.8 If there are common ventilation systems present - are there fire safety systems in place to prevent fire/ smoke spread?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.9 Are wall and ceiling linings appropriate to limit fire spread?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.10 Are soft furnishings in common areas appropriate to limit fire spread/growth?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.11 Are curtains or drapes within common areas appropriate to limit fire spread/growth?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.12 Are there any other issues relating to the compartmentation?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
14.13 Are there any other issues relating to the compartmentation?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
15. Fire Safety Signage/ Notices
-
15.1 Are Fire Action Notices clearly displayed in the correct location with the correct and consistent information completed on them (Stay-Put / Simultaneous Evacuation)
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
15.2 Is the fire door signage correct?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
15.3 Is the Fire Exit/ directional signage correct and adequate?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
15.4 Is 'No Smoking' signage provided?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
15.5 Are there any other issues relating to Fire Safety signage?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
16. Fire Safety Systems and Equipment
-
16.1 Are portable fire extinguishers provided?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
16.2 Has lightning protection been provided?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
16.3 Has the building been provided with a Fire Service Drop Key system to gain access?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
16.4 Has the building been provided with a Fire Mains system (Dry/ Wet riser)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
16.5 Has the building been provided with a sprinkler system?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
16.6 Has the building been provided with equipment for the evacuation of disabled persons?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
16.7 Have fire doors been fitted with automatic hold open or free-swing devices? (Electromagnetic, Dorgards etc.)
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
16.8 Has the building been provided with a lift for Fire Safety purposes?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
16.9 Are there any other issues regarding Fire Safety systems/ equipment?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
17. Management
-
17.1 Has a competent person(s) been appointed within the organisation to assist in undertaking preventative and protective fire safety measures?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.2 Is there a policy for the fire safety arrangements & proceedures?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.3 Are there suitable Fire Assembly Points identified?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.4 Have staff been provided with Fire Safety training?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.5 Have staff been nominated and trained in the use of fire extingushers?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.6 Have staff been nominated and trained in assisting with evacuations from the building?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.7 Are there suitable arrangements for the evacuation of disabled persons (Consider information for residents, PEEPs PCFRAs etc.)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.8 Do the Fire Service attend for familiarisation visits?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.9 Are fire safety checks carried out regularly by staff?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.10 Are fire drills carried out regularly?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
17.11 Are there any other issues relating to Fire Safety Management?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
18. Testing, Maintenance and Records
-
18.1 Is there a Fire Safety log book provided (paper or on-line)?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.2 Has the common electrical system been serviced in the past five years?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.3 Are the fixed gas systems serviced annually?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.4 Is the fire detection/alarm system maintained and tested by a specialist contractor as per BS 5839-1 or BS 5839-6
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.5 Is the emergency lighting is inspected, tested and maintained as per BS EN 50172:2004/BS 5266-8:2004 and BS5266-1:2016?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.6 Is fire extinguisher servicing is carried out annually?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.7 Is the lightning protection system serviced annually?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.8 Is the Fire Service drop key access system serviced annually?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.9 Is the fire mains system serviced annually?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.10 Is the sprinkler system serviced in accordance with relevant guidance?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.11 Are the disabled evacuation equipment serviced in accordance with relevant guidance?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.12 Are the fire door 'hold-open' devices serviced in accordance with relevant guidance?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.13 Is the fire-fighting lift serviced in accordance with relevant guidance?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.14 Are records kept of the regular Fire Safety checks?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.15 Are records kept of the fire drills undertaken?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
-
18.16 Are records kept of staff Fire Safety training?
- Ultra-high Risk
- High Risk
- Medium Risk
- Low risk
- Maintain Standard
- Not Applicable
- Management 1
- Management 2
Final Fire Risk Rating
- Final Risk Rating
-
Fire Risk Matrix It must be noted here that health and safety action and risk assessment can never entirely eliminate risk, nor is it intended to, but it is used to reduce risk so far as is reasonably practical to an acceptable level. As an aid to calculating acceptable levels of risk, a 5 x 5 matrix can be a useful tool as shown below. It is important to note here, that from this the Responsible Person can “draw a line” so to speak, at what they consider acceptable risk. Likelihood 1 – Improbable (not applicable in residential premises as a fire is always possible) 2 – Possible 3 – Probable 4 – Certain – low speed spread 5 – Certain – high speed spread Severity 1 – Minor Injury 2 – Injury 3 – Serious Injury 4 – Single Fatality 5 – Multiple Fatality Fire Risk (likelihood) is rated with the existing conditions and control measures being in place and strictly adhered to. Injury Severity (consequence) is as if a fire occurs despite the control measures being in place. The resulting assessment is by thoughtful consideration of the above along with the conditions found on site and is represented by the points summary below.
-
Taking all of the above into account and in relation to the assessment table below, what is the likelihood of a fire starting?
-
Taking all of the above into account and in relation to the table below, what is the likely severity on life safety?
-
What is the total score of the two above numbers multiplied together?
-
What is the current risk rating?
-
What are the main reasons for this score?
Review
-
This is a “Living Document”. It must be reviewed and changed after corrective works are completed, new equipment, electrical goods / machinery, etc. processes are introduced to the premises, after any change in fire legislation, or because of an incident that could be learnt from at another building, from an occurrence that may increase the threat of arson, or in any case at least within one year of its assessment / last review date. Note changes / actions taken etc. by hand in the boxes above or on a separate sheet attached as required. Date and initial all such entries.
-
Fire Risk Assessor Signature
-
Date of Report
-
Latest date for re-assessment