Title Page

  • Conducted on

  • Prepared by

  • Location
  • General condition

  • Compliance with minimum standards<br>(Questions 2 to 23,32 and 33)

  • Maintenance quality<br>(Questions 5,12,26 to 32 and 34 to 40)

  • Is the plant running

  • Is the unit and it's associated plant secure from unauthorised access

  • Is the unit safely accessable for inspections and maintenance

  • Is the air intake positioned to avoid short circuiting with extract or foul air from other sources such as had scavenging outlets

  • Are all inspection lights working

  • Are motorised dampers fitted to the intake and discharge

  • For belt driven fans, is the drive visible without removing covers

  • For plug and EC fans is the fan visible without removing covers

  • Is the cooling coil located in the discharge side of the fan

  • Is the energy recovery system required (state type)

  • Are condensate drainage systems fitted to ask energy recovery systems, cooking could and humidifiers in accordance with chapter 13 of HTM 03-01 part B

  • Are drainage traps clean and filled with water? (See table 3 in HTM 03-01 part B)

  • Is the drain trap air break at least 15mm?

  • If a humidifier is fitted state the type

  • Is the humidifier capable of operation?

  • Is there space to safely change the filters?

  • Are there test holes in all the principle ducts?

  • Are the test holes capped?

  • What is the general condition of the exterior of the AHU?

  • Are the principal ducts lagged?

  • Is the system clearly labelled?

  • Record pre filter differential pressure

  • Record main filter differential pressure

Switch plant of and fit padlock to isolator

  • Did the motorised dampers close on plant shut down?

  • Is the vermin/pest screen clean?

  • Is the intake section including the fog coil clean

  • Are the pre filters correctly fitted with no bypass

  • Are drive belts correctly aligned and tensioned

  • Is the cooling coil matrix clean?

  • Are all drip trays fully accessable or capable of being removed for cleaning and have a fall to drain?

  • Are the drainage trays stainless

  • Are the drainage trays clean?

  • Is the internal base of the AHU free from any sign of ponding?

  • Is the matrix clean for each heater battery

  • Have the main filters been correctly fitted with no air bypass?

  • Is the AHU and it's associated main ductwork clean internally?

Energise plant

  • Did the unit start satisfactorily

Test automatic fan motor change over if fitted

  • Did automatic change over operate satisfactorily?

  • Additional comments

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.