Title Page
-
Conducted on
-
Prepared by
-
Location
-
General condition
- Good
- Average
- Poor
- End of useful life
-
Compliance with minimum standards<br>(Questions 2 to 23,32 and 33)
-
Maintenance quality<br>(Questions 5,12,26 to 32 and 34 to 40)
-
Is the plant running
-
Is the unit and it's associated plant secure from unauthorised access
-
Is the unit safely accessable for inspections and maintenance
-
Is the air intake positioned to avoid short circuiting with extract or foul air from other sources such as had scavenging outlets
-
Are all inspection lights working
-
Are motorised dampers fitted to the intake and discharge
-
For belt driven fans, is the drive visible without removing covers
-
For plug and EC fans is the fan visible without removing covers
-
Is the cooling coil located in the discharge side of the fan
-
Is the energy recovery system required (state type)
-
Are condensate drainage systems fitted to ask energy recovery systems, cooking could and humidifiers in accordance with chapter 13 of HTM 03-01 part B
-
Are drainage traps clean and filled with water? (See table 3 in HTM 03-01 part B)
-
Is the drain trap air break at least 15mm?
-
If a humidifier is fitted state the type
-
Is the humidifier capable of operation?
-
Is there space to safely change the filters?
-
Are there test holes in all the principle ducts?
-
Are the test holes capped?
-
What is the general condition of the exterior of the AHU?
-
Are the principal ducts lagged?
-
Is the system clearly labelled?
-
Record pre filter differential pressure
-
Record main filter differential pressure
Switch plant of and fit padlock to isolator
-
Did the motorised dampers close on plant shut down?
-
Is the vermin/pest screen clean?
-
Is the intake section including the fog coil clean
-
Are the pre filters correctly fitted with no bypass
-
Are drive belts correctly aligned and tensioned
-
Is the cooling coil matrix clean?
-
Are all drip trays fully accessable or capable of being removed for cleaning and have a fall to drain?
-
Are the drainage trays stainless
-
Are the drainage trays clean?
-
Is the internal base of the AHU free from any sign of ponding?
-
Is the matrix clean for each heater battery
-
Have the main filters been correctly fitted with no air bypass?
-
Is the AHU and it's associated main ductwork clean internally?
Energise plant
-
Did the unit start satisfactorily
Test automatic fan motor change over if fitted
-
Did automatic change over operate satisfactorily?
-
Additional comments