Cold sentinel tap ground floor (wet TMV take from pipework) accessible toilet temperature in centigrade (run for 2 minutes)

The temperature is above 20oC report this to maintenance!

Hot sentinel tap Ground floor cleaners store temperature in centigrade (run for 1 minute)

The temperature is below 50oC report this to maintenance!

Cold sentinel tap ground floor cleaners store temperature in centigrade (run for 2 minutes)

The temperature is above 20oC report this to maintenance!

Hot sentinel tap in Staff Room Sink temperature in centigrade (run for 1 minute)

The temperature is below 50oC report this to maintenance!

Hot sentinel tap in dryside cleaning cupboard temperature in centigrade (run for 1 minute)

The temperature is below 50oC report this to maintenance!

Hot sentinel tap in Cafe wash hand basin temperature in centigrade (run for 1 minute)

The temperature is below 50oC report this to maintenance!

Calorifier in pool plant room temperature in centigrade
Outlet temperature

The temperature is below 60oC report this to maintenance!

Inlet temperature

The temperature is below 50oC report this to maintenance!

Cold water tank temperatures

Is it February or July?

Temperature of gym cold water tank

The temperature is above 20oC report this to maintenance!

Comments

Add signature
Please note that this checklist is a hypothetical example and provides basic information only. It is not intended to take the place of, among other things, workplace, health and safety advice; medical advice, diagnosis, or treatment; or other applicable laws. You should also seek your own professional advice to determine if the use of such checklist is permissible in your workplace or jurisdiction.