Title Page
-
Client
-
Site
-
Tenancy/ Building Number
-
Date & Time of Audit
-
SIMPRO Job Number
-
Prepared by
-
Signature
Site Reticulation
-
Please either review a supplied Single Line Diagram- Does as found match as supplied? If none provided, complete a markup for the site on a clean piece of A3 Paper, Take a photo and upload as an attachment to this section. Ensure you include Submain size and qty (ie 4 x 1C 25mm + 6mm E), Breaker size, type and settings (if a settable MCCB).
-
Please complete a markup of any site reticulation ie pit and pipe, cable tray. Please make notes on sizing and spare capacity.
Main Switchboard and Consumer Main Inspection
-
Board Number
-
General Condition of Switchboard (include photo)
-
is there 600mm clear access once the switchboard doors are open?
-
Main Switch Size and Rating, Is it a circuit breaker or isolator?
-
Upstream Protection from the board- size, location etc
-
Labelling complete and correct?
-
Consumer Main Type (eg XLPE, Orange Circ)
-
Consumer Main Size
-
1PH/3PH?
-
Consumer Main Visual Condition, including terminations, segregation and heatshrink condition
-
Main Earth- Where is it located? is it tagged as the main earth and labelled at the MSB as the main earth? General Condition?
-
Main Earth Size?
-
Main Earth- Test and record main earth resistance using a trailing lead
-
Equipotential Bond- is there one? is one required ie is it copper pipe or poly pipe? General Condition?
-
Equipotential Bond- Size?
-
Equipotential Bond, is it Labelled both ends?
-
MEN- Is there an MEN present? is it labelled and of the correct size?
Distribution Board Inspection
-
DB Number
-
General Condition of Switchboard (include photo)
-
Switchboard: Labelling complete and compliant?
-
Switchboard: Access to switchboard unimpeded? is there 600mm clear access once the switchboard doors are open?
-
Switchboard: Cable Entries- Are they suitably Bushed/Insulated and sealed- Is the switchboard vermin proof?
-
Switchboard: Inspection Type: Thermal Scanning or visual inspection?
- Thermal Scanning
- Visual Inspection
-
Switchboard: busbar/internal wiring- is there no visual evidence of overloading- are connections tight?
-
Circuit protection: Are all breakers compatible to the board type?
-
Circuit protection: Are all breakers orientated in the same direction for on/off?
-
Circuit Protection: Are all circuits RCD protected?
-
Circuit Protection: Complete pushbutton test and record any failed results
-
Circuit Protection: Check line/load connections for correct polarity and tightness
- Pass
- Fail
- N/A
-
Circuit Protection: Are CB/RCBO sized correctly for outgoing cable sizes?
- Yes
- No
- N/A
Circuit Protection: Are CB/RCBO sized correctly for outgoing cable sizes?
-
Lighting (include quantity)
-
Power (include Quantity)
-
Other (include quantity)
-
Circuit Protection: Total Number of Circuits currently in service (1 phase circuits)
-
Circuit Protection: Total Number of Circuits Currently in service (3 phase circuits)
-
Emergency Lighting: Are there exit and emergency lights installed in the Building compliant to AS2293.2
-
Emergency Lighting: Is there an emergency lighting logbook present and completed within 6 months
-
Emergency Lighting: If Yes, is the emergency lighting installed as per the logbook details
-
Emergency Lighting: Does the switchboard have an emergency lighting test switch?
-
Emergency Lighting: If yes, does the test switch work correctly?
General Light and Power
General Light and Power
-
Ceiling Space: Has wiring been suspended off the ceiling grid? (where accessible) or secured to timber battens using moulded clips
-
Ceiling Space: any visual safety hazards? (where accessible)
-
Ceiling space: Cabling installed compliant to current standards ( visual inspection, where accessible only)
-
General Power: Are visible outlets in good condition/mounted securely, labelled?
-
General Power: Select one outlet, remove and check termination method and quality of termination- is it ok?
-
Cabling Type- Is there any indication of bare earth cabling, cloth insulated cabling?
-
Overall- Does the installation look Defect Free? General Comments and Photos to be added
Communications
-
Communications: IDF- Lead in cabling terminated?
-
Communications: IDF- Outgoing cabling compliant?
-
Communications: IDF- Cover Installed?
-
Communications IDF- Record Pair Number if detailed
-
Communications- Horizontal Cabling- Brand, Type (Cat5,6,6A)
-
Communications- General Condition OK?
-
Fibre Optic- Draw SLD of Site Reticulation
-
Fibre Optic- What Brand, Type (Single, multimode) and variant (ie OS2, OM4) is it indoor/outdoor?