Information
-
Room Number:
-
Inspected by:
-
Conducted on
Slip, Trip and Fall
-
Walking surfaces are free of obstructions?<br>Walking surfaces to & from Exit are free of obstructions? <br>
-
Floors are clean, dry & in good condition?<br>
-
There are no floor holes greater than 1"?<br>
-
All floor holes, open pits, vats & ditches are guarded with a guardrail and/or have a toe board or floor cover?<br>
-
Wall openings with a drop of more than 4 ft. are guarded with a guardrail and/or have a toe board where necessary?<br>
-
Storage areas are free from accumulation of materials that may cause tripping, fire or explosion hazards?<br>
-
There is no overhead storage of materials on top of cabinets, equipment or piping?<br>
-
Storage in tiers is stacked, blocked & interlocked & limited in height for stable & secure storage?<br>
-
ADDITIONAL COMMENTS:
Exits
-
All exit doors are in good working order?<br>
-
Any door or passage that is NOT an exit and is likely to be mistaken as an exit is marked "NOT AN EXIT"?<br>
-
All emergency exits are labeled, (above the door), with readily visible signage?<br>
-
If the sign is lighted, is it functioning properly?<br>
-
ADDITIONAL COMMENTS:
Emergency Equipment
-
Fire extinguishers are inspected monthly? (Check date on tag)<br>
-
Fire extinguishers are hung on a wall or located in appropriately labeled cabinets?<br>
-
Safety equipment (fire extinguishers, eyewash, shower pull stations) are not blocked?<br>
-
ADDITIONAL COMMENTS:
PPE
-
Current PPE hazard assessments posted in the area & available for use?<br>
-
ADDITIONAL COMMENTS:
Electrical/Energy Control
-
Electrical equipment is marked with the manufactures name & applicable rating?<br>
-
Each disconnect is marked to indicate its purpose?<br>
-
Adequate working clearance, (3 ft. in front X 30" wide), & illumination are provided for all working spaces around electrical equipment?<br>
-
Pull boxes, junction boxes & fittings are appropriately covered?<br>
-
Light fixtures less than 7 ft. high do not have exposed parts?<br>
-
Conduits containing live wires have covers, knockout plates, elbows, etc. in place?<br>
-
Electrical circuit breakers are clearly labeled to their use? (inside of door - legible).<br>
-
All unused circuits are covered with a blank & marked "SPARE"?<br>
-
Electrical cords are not secured with electrical cable ties?<br>
-
Extension cords are not being used?<br>
-
ADDITIONAL COMMENTS:
Additional Safety & Housekeeping
-
Are ladders well maintained? - <br><br>
-
Are ladders in their designated location?
-
LADDER INSPECTION & SIGN OUT SHEETS-<br>Please remove and return used sheet(s) to the Safety Coordinator & replace with a NEW sheet(s).
-
Palletized materials are stored securely in racks? (Pallets in good condition).<br>
-
ADDITIONAL COMMENTS:
Chemical / Gas Cylinder Storage
-
All single, in use, gas cylinders are secured & upright?<br>(No nesting of in-use cylinders.)<br>
-
All non-vented flammable liquid cabinets have the bung in place?<br>
-
MSDS books are current & available?<br>
-
All chemicals are labeled with proper HMIS labels?<br>
-
All pipes are labeled as to contents & direction of flow of materials?<br>
-
Toxic, Flammable, Oxidizing & Corrosive gasses are stored in approved cabinets?<br>
-
Storage areas are well ventilated, dry & made of fire resistant construction?<br>
-
Containers are protected from bottom corrosion?<br>
-
Emergency showers & eyewashes are present where acidic or caustic gases are used?<br>
-
No more than 25 gallons of flammable liquids are stored outside of an approved storage cabinet?<br>
-
ADDITIONAL COMMENTS:
FOLLOW UP ITEMS - ADDITIONAL NOTES:
-
ADDITIONAL COMMENTS: