Title Page
-
Client / Site : Cogent Breeding Ltd
-
Reference Number
-
Conducted on
-
Inspected by
-
Location
Monthly Inspection
Fire Extinguisher Inspection
Fire Extinguisher
Fire Extinguisher 1
Fire Extinguisher Information
-
Location : CANTEEN
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 2
Fire Extinguisher Information
-
Location : ENTRANCE
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 3
Fire Extinguisher Information
-
Location : ENTRANCE
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 4
Fire Extinguisher Information
-
Location: LABORATORY ENTRANCE
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 5
Fire Extinguisher Information
-
Location: LABORATORY ENTRANCE
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 6
Fire Extinguisher Information
-
Location: ALTERNATIVE SPECIES LAB
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 7
Fire Extinguisher Information
-
Location: CONVENTIONAL LAB- STOCKMEN ENTRANCE
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 8
Fire Extinguisher Information
-
Location: CONVENTIONAL LAB - ENTRANCE
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 9
Fire Extinguisher Information
-
Location: SORTING LABORATORY
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 10
Fire Extinguisher Information
-
Location: SORTING LABORATORY- STORAGE
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 11
Fire Extinguisher Information
-
Location: SORTING LAB - EMPTY TANKS ROOM
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 12
Fire Extinguisher Information
-
Location: SORTING LABORATORY- FREEZING AREA
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 13
Fire Extinguisher Information
-
Location: OFFICES CORRIDOR
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 14
Fire Extinguisher Information
-
Location: OFFICES CORRIDOR
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 15
Fire Extinguisher Information
-
Location: OFFICES LOFT - ELECTRIC BOARD
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 16
Fire Extinguisher Information
-
Location: SERVER ROOM
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 17
Fire Extinguisher Information
-
Location: COMPRESSOR ROOM
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 18
Fire Extinguisher Information
-
Location: ELECTRIC BOARDS ROOM
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Fire Extinguisher 19
Fire Extinguisher Information
-
Location: LOFT
-
Expiry Date
-
Type of Fire Extinguisher
Fire Extinguisher Inspection
-
1. Has a valid maintenance tag
-
2. Mounted in an easily accessible place, no debris or material stacked in front of it.
-
3. Safety pin is in place and intact. Nothing else should be used in place of the pin.
-
REFERENCE: Safety pin is in place and intact
[This is an example of how you can use iAuditor to include best practice reference images in your templates to assist with inspections] -
4. Label is clear and extinguisher type and instructions can be read easily.
-
5. Handle is intact and not bent or broken.
-
6. Pressure gauge is in the green and is not damaged or showing “recharge”
-
7. Discharge hoses/nozzle is in good shape and not clogged, cracked, or broken
-
8. Extinguisher was turned upside down at least three times (shaken) to make sure it is full.
-
9. Location of extinguisher is easily identifiable by signs
-
10. Dust and wipe down the extinguisher
-
11. Annual maintenance tag is signed and dated
-
Take a photo of the annual maintenance tag
-
Overall condition of fire extinguisher
Completion
-
Write down observations
-
State recommendations about the inspections here
-
Name and Signature of Inspector