Piping

  • Nitrogen purging during brazing?

  • Using 15% brazing rod?

  • Heat Pump no flow selector

  • System Selector Refrigerant Piping Layout - being followed with actual lengths entered on page?

  • Do refrigerant pipe sizes match selector tool layout?

  • System Selector.gif
  • Pipe hangers clevis style with saddle? (As per picture below)

  • Saddle Hanger.gif

Heat Recovery - Flow Selectors

  • Flow Selector - In an area where the operating sound of the solenoids will not be objectionable?

  • Mounted in the horizontal position? (See picture below)

  • Flow Selector.jpg
  • Flow Selector - Installed with proper clearances and service access Per drawing with 3' of clearance for electric access.

  • Add media

  • Enter the distance that the flow selector is mounted from the indoor unit __________________ft. Must be ≤ 49 Ft. refrigerant piping length

  • Do the field installed refrigerant line sizes and lengths, to the flow selector match the piping layout?

  • Nitrogen Purge during brazing, and heat protection used when brazing at Flow Selector?

Indoor Refrigerant Piping: Branching Joints

  • Branch joint are correct size and match System Selector Tool?

  • Header Type Branch Joint : Installed horizontal within ± 10° per instructions? (As shown in photo below)

  • Headers.gif
  • Y Type Branch Joint : Installed horizontal within ± 15° per instructions? (See picture below)

  • Horizontal Y.gif
  • Installed vertical per instructions? (See picture below)

  • Y Branches.gif
  • Are branch joints properly supported?

  • Maintain a minimum distance of 18" between branching joints, elbows and equipment? (Per picture below)

  • 18in rule.gif
  • Sockets, joints and insulation were installed per instructions?

  • No traps per rules and shown in picture below ?

  • Trap Rule.gif
  • Expansion joints installed per installation instructions? (See picture below)

  • Expansion Loop.gif

Pipe Insulation

  • Is pipe insulation 1" close cell UV Rated 245 Degrees F?

  • Are all pipes insulated separately?

  • No gaps or cuts in insulation?

  • Are Insulation joints glued and not crushed?

  • Add signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.