  • CHI Franciscan Facilities EOC Rounds Checklist v.3

  • Site / Department

  • Conducted on

  • Prepared by

  • Personnel

Life Safety

  • Smoke/Fire doors close and latch properly

  • Check gaps and undercuts in Smoke/Fire doors. No more than 1/8" gap and 3/4" undercut

  • Smoke/Fire doors are unobstructed

  • Fire extinguishers are unobstructed and monthly checks are up to date; Mounted < 5'

  • Exits are not obstructed or blocked

  • Exit paths and 8' corridors are maintained and unobstructed

  • Sprinkler heads are free of dust or debris and 18" clearance is maintained

  • Exit signs are lit and direction arrow is accurate

  • Pull stations are unobstructed

  • Trash & linen chutes latch properly

  • Battery back up lighting in "anesthetizing" locations (OR, CathLab, etc.)

  • Staff can articulate the meaning of RACE & PASS: question a sampling of staff

  • ILSM/IRCA active/in place in area, if so is it being followed?

General EOC

  • Medical gas panels are properly labeled and unobstructed

  • Ceiling tiles clean and without evidence of water damage

  • Negative & positive pressure relationships are maintained appropriately

  • Electrical panels are locked in public areas and free of obstructions

  • Work areas are free of extension cords and adaptors<br> - Electrical power strips not daisy chained<br> - Only approved re-locatable power taps are in use in patient areas

  • No space heaters in patient care areas

  • Alcohol gel dispensers installed appropriately; not above or within 6" of ignition source

  • Appropriate Trash containers in correct locations: <32 gal

  • Area in good repair: wall, flooring, window covering, counter tops, light & electrical outlets, doors etc..

  • Humidity sensors and pressure monitors are working properly

  • Fans are clean & covered; Stored properly

Hazardous Materials

General Safety

  • Hazardous Materials are stored and labeled properly

  • O2 storage area properly labeled; Separate rack for full tanks and partial/empty tanks; <12 e-cylinder stored in non-rated room

Satellite Accumulation Area

  • Containers labeled "Hazardous Waste"

  • Containers have "Accumulation start date"

  • Start date <90days (No storage >90 Days)

  • Containers in good condition/not leaking

  • Containers kept closed

  • Containers stored to prevent rupture/leakage

  • Waste compatible with container

  • Incompatible wastes separated

  • Adequate aisle space between containers (30 inches)

  • Accumulation area at or near point of generation

  • <55gals DW or 1 quart Acutely Haz Waste

Misc. and Survey End

  • Misc. Findings/Notes

  • Corrective Action Plans:

  • Surveyor Signature:

  • Department Representative Signature:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.