CHI Franciscan Facilities EOC Rounds Checklist v.3
-
Site / Department
-
Conducted on
-
Prepared by
-
Personnel
Life Safety
-
Smoke/Fire doors close and latch properly
-
Check gaps and undercuts in Smoke/Fire doors. No more than 1/8" gap and 3/4" undercut
-
Smoke/Fire doors are unobstructed
-
Fire extinguishers are unobstructed and monthly checks are up to date; Mounted < 5'
-
Exits are not obstructed or blocked
-
Exit paths and 8' corridors are maintained and unobstructed
-
Sprinkler heads are free of dust or debris and 18" clearance is maintained
-
Exit signs are lit and direction arrow is accurate
-
Pull stations are unobstructed
-
Trash & linen chutes latch properly
-
Battery back up lighting in "anesthetizing" locations (OR, CathLab, etc.)
-
Staff can articulate the meaning of RACE & PASS: question a sampling of staff
-
ILSM/IRCA active/in place in area, if so is it being followed?
General EOC
-
Medical gas panels are properly labeled and unobstructed
-
Ceiling tiles clean and without evidence of water damage
-
Negative & positive pressure relationships are maintained appropriately
-
Electrical panels are locked in public areas and free of obstructions
-
Work areas are free of extension cords and adaptors<br> - Electrical power strips not daisy chained<br> - Only approved re-locatable power taps are in use in patient areas
-
No space heaters in patient care areas
-
Alcohol gel dispensers installed appropriately; not above or within 6" of ignition source
-
Appropriate Trash containers in correct locations: <32 gal
-
Area in good repair: wall, flooring, window covering, counter tops, light & electrical outlets, doors etc..
-
Humidity sensors and pressure monitors are working properly
-
Fans are clean & covered; Stored properly
Hazardous Materials
General Safety
-
Hazardous Materials are stored and labeled properly
-
O2 storage area properly labeled; Separate rack for full tanks and partial/empty tanks; <12 e-cylinder stored in non-rated room
Satellite Accumulation Area
-
Containers labeled "Hazardous Waste"
-
Containers have "Accumulation start date"
-
Start date <90days (No storage >90 Days)
-
Containers in good condition/not leaking
-
Containers kept closed
-
Containers stored to prevent rupture/leakage
-
Waste compatible with container
-
Incompatible wastes separated
-
Adequate aisle space between containers (30 inches)
-
Accumulation area at or near point of generation
-
<55gals DW or 1 quart Acutely Haz Waste
Misc. and Survey End
-
Misc. Findings/Notes
-
Corrective Action Plans:
-
Surveyor Signature:
-
Department Representative Signature: