Honeywell EBI status check
-
Document No.
-
Prepared by
-
Location
-
Select date
-
Who did this check-up: Please type name.
-
EBI Alarm Tests -- to be done ONCE PER SHIFT
Outside Air Temperature: (OAT)
-
What is the current OAT? (°C)
Air Handling Units Summary
-
SA SetPoint vs. SA Temp? -- (Within +/- 1°C)<br><br>Ignore AHU 19
-
RA RH -- All within Range 30 - 65 RH for Various AHU's?
-
Is everything out of "Manual"? (If in Manual, Please Note/Specify)
Operating Rooms
-
All O.R temps close to SetPoint? -- (Within +/- 1°C)
-
All RH within their Range of 30 - 60°C?
-
All Air Flows close to SetPoint? -- (Within +/- 40 L/S)
Chiller Plant
-
CWS Temp -- Is it within Range 5.5 - 12°C?
-
CWR Temp -- Is it within Range 10 - 14°C?
-
Which Chiller is Operating? (select all)
- 1
- 2
- 3
- 4
- Dry Cooler
Heating Plant
-
HWS Temp -- Is it within Range 67- 75°C?
-
Which Boiler is Operating? (select all)
- 1
- 2
- 3
- 4
- 5
- COGEN
Domestic Hot Water System
-
HWS Temp -- Is it within Range 66 - 73°C? (Ideal S.P = 71°)
L120 Data Room
-
Room Temp -- Is it within Range 17 - 23°C?
-
AC 1,2 and 3 - All green? All within Normal state?
Isolation Rooms
-
Exhaust Fan 10 - All functioning?
-
Exhaust Fan 26 - All functioning?
-
Exhaust Fan 24 - All functioning?
Fridge and Freezers (4 Sub-Categories)
1. Morgue
-
All temps within their Range? (3 of them)
2. Food Service
-
All temps within their Range? (3 of them)
3. Lab
-
All temps within their Range? (5 of them)
4. Pharmacy
-
All temps within their Range? (1 of them)
C-Buses
-
Are all boxes Green? (Versus being Red)
-
Click "Lonworks Riser" (Upper Right Hand Corner) -- All appear green?
Alarm Page (Please Filter to Automation)
-
-- Make sure to filter to Automation --<br>Does everything look OK?