211200 Standpipe
-
211313 Wet Pipe System
-
213000 Fire Pump
-
Document No.
Execution of Work
Hangers
-
Are hangers straight and plumb?
-
Are hangers installed to manufacturer's guidelines?
-
Are hanger and supports proper spaced and independently supported?
-
Are hanger damaged or been removed by other trades?
-
Are hangers installed to NFPA 13 standards?
-
Are hangers of the CORPS listed approved material
Pipe, Fittings and Valves
-
Is proper schedule of pipe being used? (2-1/2" and larger diameter pipe Schedule 10 and 2" and smaller diameter pipe Schedule 40)
-
Is pipe free of physical damage?
-
Is pipe and fittings installed free of foreign debris or corrosion?
-
Are joints and fittings properly installed
-
Verify that indicating valve is working and in the correct position for system condition?
-
All floor control valves are installed properly
-
All valves and devices are accessible
-
Drain line installed
-
Are all outlet capped and plugged at the end of shift?
-
No piping, wiring or duct is touching sprinkler pipe
-
No more than 4 threads visible on threaded joints?
-
All bolts shall extend no less than three full threads
-
Are all bolts torqued to manufacturer's guidelines?
-
Has all pipe been pressure/water tested?
-
All material installed meet CORPS approval?
Sprinkler Heads and Flexible Connections
-
Are the proper temperature rating sprinkler heads installed?
-
Are brackets attached to ceiling grid as per manufacturer's guidelines
-
Are sprinkler head guards installed properly
-
Are sprinkler heads obstructed?
-
Are sprinkler heads free of paint, corrosion, or other non-approved contaminants?
-
Are sprinkler head located at least 1 foot away from diffuser?
-
All material installed meets CORPS approval ?
Design Installation
-
Are hangers within 12" of the end of the line
-
No sprinkler heads are further than 7'-6" or closer than 6" from walls
-
Sprinkler heads are installed under ductwork 4'-0" or greater
-
Mechanical rooms with ceilings lower than 8' above FF have sprinkler heads with guards?
-
Do sprinkler spacing exceed 130 sq. ft. in ordinary hazard areas.
-
Do all low points in sprinkler system exceeding 5 gallons must have a drain?
Underground
-
Is bedding at the proper depth and material?
-
Are all bolts torqued to manufacturer's specification?
-
Are all rods and bolts are tar coated?
-
Is tracker wire installed
-
Is marking tape 1' foot above pipe?
-
Is underground installed as per drawings
-
All installed materials meet USACE approved submittals
Miscellaneous
-
Work area is clean and free debris (cut off rods, plastic plugs and caps)
-
Is fire stopping installed at all wall and/or floor pentrations
-
Is sprinkler system(s) installed as per drawings?