Information
-
Site / Area Name:
-
Address:
-
Date:
-
Conducted by:
-
Site / Ward Manager:
-
Date sent to Locality Director:
-
Date sent to Locality Manager:
-
Date sent to Site / Ward Manager
Cover Sheet
Site Information:
-
Directorate / Locality
-
Ward / Department:
-
Risk Code Factors for Type of Ward/Client/Patient Group:<br>PICU / AAU<br>Acute / Severe<br>Long Stay<br>Dementia / Elderly / Rehab<br>Outpatients
-
Manager: (Ward / Department:)
-
Conducted on:
-
Inspected by:
-
Personnel / Department Involved:
Ligature 1
Ligature / Anchor Point 1
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 2
Ligature / Anchor Point 2
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 3
Ligature / Anchor Point 3
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 4
Ligature / Anchor Point 4
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 5
Ligature / Anchor Point 5
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 6
Ligature / Anchor Point 6
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 7
Ligature / Anchor Point 7
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 8
Ligature / Anchor Point 8
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 9
Ligature / Anchor Point 9
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 10
Ligature / Anchor Point 10
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 11
Ligature / Anchor Point 11
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 12
Ligature / Anchor Point 12
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 13
Ligature / Anchor Point 13
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 14
Ligature / Anchor Point 14
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 15
Ligature / Anchor Point 15
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 16
Ligature / Anchor Point 16
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 17
Ligature / Anchor Point 17
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 18
Ligature / Anchor Point 18
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 19
Ligature / Anchor Point 19
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 20
Ligature / Anchor Point 20
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 21
Ligature / Anchor Point 21
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 22
Ligature / Anchor Point 22
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 23
Ligature / Anchor Point 23
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 24
Ligature / Anchor Point 24
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 25
Ligature / Anchor Point 25
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 26
Ligature / Anchor Point 26
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 27
Ligature / Anchor Point 27
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 28
Ligature / Anchor Point 28
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 29
Ligature / Anchor Point 29
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 30
Ligature / Anchor Point 30
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 31
Ligature / Anchor Point 31
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 32
Ligature / Anchor Point 32
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 33
Ligature / Anchor Point 33
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 34
Ligature / Anchor Point 34
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 35
Ligature / Anchor Point 35
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 36
Ligature / Anchor Point 36
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 37
Ligature / Anchor Point 37
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 38
Ligature / Anchor Point 38
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 39
Ligature / Anchor Point 39
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 40
Ligature / Anchor Point 40
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 41
Ligature / Anchor Point 41
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 42
Ligature / Anchor Point 42
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 43
Ligature / Anchor Point 43
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 44
Ligature / Anchor Point 44
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 45
Ligature / Anchor Point 45
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 46
Ligature / Anchor Point 46
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 47
Ligature / Anchor Point 47
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 48
Ligature / Anchor Point 48
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 49
Ligature / Anchor Point 49
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 50
Ligature / Anchor Point 50
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 51
Ligature / Anchor Point 51
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 52
Ligature / Anchor Point 52
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 53
Ligature / Anchor Point 53
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 54
Ligature / Anchor Point 54
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 55
Ligature / Anchor Point 55
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 56
Ligature / Anchor Point 56
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 57
Ligature / Anchor Point 57
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 58
Ligature / Anchor Point 58
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 59
Ligature / Anchor Point 59
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 60
Ligature / Anchor Point 60
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 61
Ligature / Anchor Point 61
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 62
Ligature / Anchor Point 62
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 63
Ligature / Anchor Point 63
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 64
Ligature / Anchor Point 64
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 65
Ligature / Anchor Point 65
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 66
Ligature / Anchor Point 66
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 67
Ligature / Anchor Point 67
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 68
Ligature / Anchor Point 68
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 69
Ligature / Anchor Point 69
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 70
Ligature / Anchor Point 70
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 71
Ligature / Anchor Point 71
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 72
Ligature / Anchor Point 72
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 73
Ligature / Anchor Point 73
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 74
Ligature / Anchor Point 74
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 75
Ligature / Anchor Point 75
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 76
Ligature / Anchor Point 76
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 77
Ligature / Anchor Point 77
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 78
Ligature / Anchor Point 78
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 79
Ligature / Anchor Point 79
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 80
Ligature / Anchor Point 80
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 81
Ligature / Anchor Point 81
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 82
Ligature / Anchor Point 82
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 83
Ligature / Anchor Point 83
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 84
Ligature / Anchor Point 84
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 85
Ligature / Anchor Point 85
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 86
Ligature / Anchor Point 86
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 87
Ligature / Anchor Point 87
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 88
Ligature / Anchor Point 88
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 89
Ligature / Anchor Point 89
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 90
Ligature / Anchor Point 90
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 91
Ligature / Anchor Point 91
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 92
Ligature / Anchor Point 92
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 93
Ligature / Anchor Point 93
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 94
Ligature / Anchor Point 94
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 95
Ligature / Anchor Point 95
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 96
Ligature / Anchor Point 96
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 97
Ligature / Anchor Point 97
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 98
Ligature / Anchor Point 98
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 99
Ligature / Anchor Point 99
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Ligature 100
Ligature / Anchor Point 100
-
Room No / Identifier / Name:
-
Room / MICAD Reference:
-
Select Room / Area Type:<br>5 = Bathroom / Toilet<br>4 = Bedroom<br>3 = External Areas<br>2 = Day / Dining Room / Lounge<br>1 = Corridor / Communal Area
-
Ligature Anchor Point Description:
-
Select Ligature Height Code:<br>5 = 800mm - 2.2m<br>4 = 500mm - 800mm<br>3 = 2.2 = 3.5<br>2 = 300mm - 500mm = 2<br>1 = < less 300mm or more > 3.5m
-
Ward Type Values (+ / - )<br>PICU / AAU +5<br>Acute / Severe +4<br>Long Stay +3<br>Dementia / Elderly / Rehab + 0<br>Outpatients - Divide by 2
-
Enter Risk Grading:<br>(Room / Area Type x Height Code, + / - = Ward Type Value)<br>14 - 30 = HIGH<br>6 - 13 = MEDIUM<br>1 - 5 = LOW<br><br>
-
Ligature Anchor Point Photo:
-
Any Mitigating Factors e.g. Communal Area, Line of Sight, Non-Secure Unit?
-
Can the Ligature Anchor Point be removed, replaced or modified YES/NO?
-
If No, can it be managed clinically? If so, how?
-
Is further action required Yes / No? If Yes, please describe:
-
Next Review Date: (Agreed date with manager) Within 1 Week, Within 1 Month, Within 6 Months
Please use the record sheet at the end of this document to record local actions
Local Action Plan
LOCAL LIGATURE ACTION PLAN
-
Please use the space provided to record any local actions. If you are recording individual actions; please precede each entry with the Ligature number shown in this report along with the location and description.