Information
-
Audit Title
-
Document No.
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
-
Select date
-
Jurisdiction
-
Permit Number
-
Contact Information
-
Contact Name
-
Phone
-
Email
-
Occupancy Type
- Assembly
- Business
- Educational
- Factory
- High-hazard
- Institutional
- Mercantile
- Residential
- Moderate Hazard
- Miscellaneous
-
Knox Box located
-
Knox Box located
-
Knox Box located
Permits
-
Permits Posted IFC 105.3.5
-
Operational Permit Required IFC 105.6
Fire Department Access
-
Fire Lanes unobstructed width of 20 ft and 13-6 ft high. IFC 503.2.1
-
Approved signs or markings IFC 503.3
-
Fire lanes shall not be obstructed including parked cars. IFC 503.4
-
Post and maintain street address so it is visible from the street with minimum 4" letters residential or 6" for commercial. IFC 505.1
-
Approved Key Box is required when immediate access is necessary. Provide Keys for entry and interior doors, elevator, and fire systems. IFC 506.1
-
Fire lanes, hydrants, and equipment must remain clear of obstructions that may inhibit use. IFC 507.5.4
-
A 3-foot clear space shall be maintained around hydrants. IFC 507.5.5
-
Other
Fire Protection Equipment and Systems
-
Storage must be 18" below sprinkler heads, and 24" from the ceiling in unsprinklered buildings. IFC 315.2.1
-
Fire protection equipment must be maintained and/or repaired. IFC 901.6
-
Sprinkler heads found to be corroded, dirty, greasy, or covered with paint must be cleaned or replaced. IFC 901.6
-
Extinguishing systems must be serviced at regular intervals; sprinklers & fire extinguishers annually, hood and duct systems 3, 6, or 12 months. IFC 906.6.1
-
Provide Class K extinguisher within 30 feet of cooking areas. IFC 904.11.5
-
Commercial occupancies must have 2A:10BC and be sufficiently charged. IFC 906.3
-
Extinguishers are to be located so maximum travel distance is 75 feet for ordinary combustibles or 30 feet for flammable liquids or similar materials. IFC 906.3.1
-
Extinguishers shall be mounted on brackets or in cabinets, or set on shelves no higher than 54" or lower than 48" above the floor. A sign indicating location is necessary when it is not visible. IFC 906.9
-
Fire Alarm systems shall be tested annually. IFC 907.9
-
Other
Fire Doors
-
Reinstall fire door(s) removed. IFC 703.1
-
Do not block or restrain fire door(s) which must be maintained self closing and remain in closed position except in actual use. IFC 703.2
-
Repair fire door(s) so they open freely, close completely, and latch when released
-
Other
Rubbish, Debris, Combustable Materials
-
Remove and properly dispose of tall grass, brush, and/or debris. IFC 304.1.2
-
Remove and properly dispose of debris. IFC 304.2
-
Combustible waste must be placed in covered metal containers. IFC 304.3.1
-
Exterior dumpsters greater than 1 CY shall not be within 5 feet of combustible construction. IFC 304.3.4
-
Remove accumulations of grease from range hood, range, and connecting flue. Clean periodically. IFC 904.11.6.3
-
Other
Combustable Storage
-
Stock and/or storage must be at least 24" from ceiling or 18" below sprinkler heads. IFC 315.2.1
-
Remove all flammable or combustible materials from unfinished basement. IFC 315.2.4
-
Storage in attic is not allowed unless protected by sprinkler system or 1 hour construction. IFC 315.2.4
-
Combustible storage is not allowed in Boiler, Mechanical, or Electrical Panel rooms. IFC 315.2.3
-
Heating devices such as furnaces, wall heaters, water heaters, and the Like must have adequate clearance from combustible materials. IFC 603.5.1
-
Other
Miscellaneous
-
Requirements that are essential for public safety but not specifically mentioned in the IFC shall be determined by the AHJ. IFC 102.8
-
Any installation that requires inspection prior to use and is covered or concealed prior to inspection shall be exposed for inspection. IFC 106.3
-
OPENINGS WALLS / CEILINGS: Repair/seal unprotected opening with fire resistive materials. IFC 703.1
-
COMPRESSED GAS: Secure/chain cylinders upright in approved manner. IFC 3003.5.3
-
LP GAS: discontinue unapproved use of LP gas in the building
-
Other
Exits
-
No storage under stairways unless protected by 1 hour construction
-
Exit doors shall swing in direction of travel if it services a hazardous area or occupant load of 50 or more. IFC 1008.1.2
-
Exit doors shall operate from the inside without the use of a key or any special knowledge or effort. IFC 1008.1.9
-
Post sign above main exit in 1" letters: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. IFC 1008.1.9 3
-
Minimum stairway width shall not be less than 44" or 36" if occupant load is 49 or less. IFC 1009.1
-
Exit signs are required at exit doorways and where necessary to clearly indicate the direction of egress. IFC 1011.1
-
Where lighted exit signs are installed they will have 2 working bulbs. IFC 1011,.2
-
Exit ways and doorways must kept free of obstructions and obstacles, including temporary storage. IFC 1030.3
-
Other
Assembly Occupancies
-
Conspicuously post a durable sign indicating the maximum room occupancy. IFC 1004.3
-
Other
Flammable Liquids
-
All spray operations exceeding 9 square feet must be done within an approved spray booth, room or area.
-
Flammable liquids in combined amount exceeding 10 gallons must've stored in a flammable liquids cabinet. Amount stored in such cabinets cannot exceed 120 gallons. Maximum of 3 cabinets in a room. Quantities in excess of this must be stored in an approved flammable liquid storage room. IFC 3404.4.4
-
Flammable liquid containers under 30 gallons cannot be stacked more than 2 high (or 3 feet; whichever is greater) and containers over 30 gallons cannot be stacked. IFC 3404.3.5.2
-
Warning signs are required on all flammable liquid containers, entrances to storage rooms, storage cabinets and at service stations where flammable liquids are stored and dispensed. IFC 3403.5
-
Other
Electrical
-
Unused electrical panels must be covered (no tape). IFC 605.1
-
Wiring or circuits that are no longer in use must be removed. IFC 605.1
-
Clearance in front of panels at least 30 inches. IFC 605.3
-
Doors into electrical control panel rooms shall be marked with sign stating ELECTRICAL ROOM. IFC 605.3.1
-
Multi Plug Adaptors are not allowed except for those with a fused or circuit breaker protected " pore strip". Power strips can not be connected end to end. IFC 605.4
-
Electrical cords cannot run through doorways, windows, or similar openings, located in foot traffic or were damage may occur. IFC 605.4.3
-
Extension Cords cannot be used for permanent wiring of lights or equipment. Only one device may be used per cord when using extension cords. IFC 605.5
-
Damaged electrical cords must be replaced or repaired. In line splices are not allowed. IFC 606.5.3
-
Cover plates must be provided for light switches, outlets, and/or any junction box with exposed wiring. IFC 606.6
-
Other
Signatures
-
Violations found
-
A reinspection will be required on
-
A reinspection is not required but you must attend to the items noted above
-
Inspector
-
Received by