Title Page
-
Commissioning Waterbrake
-
m.v. Vishy Vessel
-
Fish Fleet B.V.
-
BPT
-
Conducted on
Electrical Commissioning Checklist
Low Voltage (L.V.) Installation
Working Space and Facilities
-
Adequacy working space and safe access provided for switch room and /or electrical facilities.
-
Entrance /exit to switch room and/or electrical facilities are free of obstruction.
-
Suitable locking facilities provided for electrical facilities.
-
Suitable lighting provision provided for switch room and /or electrical facilities.
-
Suitable ventilation provision provided for switch room and /or electrical facilities.
-
Danger notices, warning notices, schematic diagrams, instructions and similar information are correctly and adequately provided.
-
Warning notices for earthing and main bonding connections provided in compliance.
-
All switchgears, distribution boards and electrical equipment properly labelled.
Connection from distribution board
-
An up-to-date notice of periodic inspection and testing provided at point of supply (i.e. a switchboard, a circuit breaker or a distribution board) of the installation.
-
Breakers leading to the waterbrake starter cabinet are provided with a legible and durable identification label.
-
No visible damage to impair safety.
-
An up-to-date schematic diagram displayed.
-
Earthing system effectively connected.
-
All protective devices are functioned properly and correctly set.
-
The breaking capacity of all circuit breakers /interconnection devices are able to withstand the prospective fault current.
-
Operation of circuit breakers and main switches checked.
-
Warning notice displayed at main bonding connections.
-
All accessible live parts screened with insulating plate or earthed metal.
Control cabinet waterbrake
-
No undersized conductor used between the distribution board and control cabinet.
-
Control, indication and alarm functions checked. (see CHPT4. "Commissioning of document waterbrake")
-
Fuses/MCB’s matching the lowest rated conductor in the circuit.
-
Cable conductors of correct phases connected.
-
A means of isolation provided for every circuit.
-
Protective relays have been correctly set and overcurrent protective devices suitably set for all circuits.
-
A warning notice ‘DANGER’ provided on the front panel of every distribution board.
-
Suitable cable terminations provided.
-
Single-pole devices for protection or switching connected in phase conductors only.
-
A notice of periodic testing provided at or near the main distribution board incorporating a residual current device.
-
Cabinet securely mounted on suitable supports.
-
A suitable switch provided to control each distribution board.
-
Phase barriers for 3-phase distribution board provided, where necessary.
-
The breaking capacity of MCB is compliant.
-
Suitable tools for withdrawal of fuses at a fuse board provided, where necessary.
-
Circuits connected to MCB or fuse in accordance with the schematic diagram.
Conductors, Cables and Wiring
-
No visible damage to impair safety.
-
All live conductors and their methods of insulation, in relation to design currents of circuits and to the operating currents of the protective devices, are properly selected and erected.
-
All cables, flexible cords, switches, plugs and socket outlets, accessories and equipment are found to be in good working conditions.
-
All conductors are correctly and securely connected and identified.
-
Armored cables properly terminated to metal casing or trunking by proper cable glands.
-
Cables passing through smoke lobby protected by enclosures of adequate fire rating.
-
Non-sheathed cables protected by conduit, trunking or ducting.
-
Cables and ductings adequately supported.
-
Cables at distribution board or busbar terminated with cable lugs
-
Main cables connected up with correct polarity.
-
Cables protected against mechanical damage and suitably supported.
-
All exposed metal parts including the armor effectively earthed.
Final Circuits
-
Low voltage circuits segregated from extra low voltage circuits.
-
Exposed insulated non-sheathed cables protected.
-
Circuit protective conductor is formed by the enclosure and a separate protective conductor between the earthing terminal of socket outlet and its associated metal box provided.
-
Circuit protective conductor is not formed by the enclosure and a separate protective conductor to the earthing terminal of socket outlet provided.
-
Minimum sizes of protective conductors are provided as per requirement for limitation of protective conductor impedance.
-
Means of isolation provided for every fixed appliance.
-
No fixed luminaire nor fixed heater having unguarded heating elements installed within reach of parts affected by heat
-
Appliances exposed to weather being IP55 rated.
-
Luminaires, switches, sockets and plugs, cable couplers installed outdoor, being IP55 rated.
-
General/site lighting readily accessible to the public supplied from a safety source.
-
General/site lighting not readily accessible to the public and not supplied from a safety source, protected by RCD having a rated residual operating current not exceeding 30mA.
-
Emergency stops on both local and remote controls are clearly marked, in good condition, visible, and accessible.
-
Buttons and indicator lights are clearly visible, in good undamaged condition.
-
400 V plug is correctly installed and undammaged.
-
230 V plug is correctly installed and undammaged.
-
Interconnections of control cabling (between winch and waterbrake) is correctly mounted to terminal blocks. And cable is in undammaged condition.
-
All connections to terminal blocks and screw terminals are tightly connected.
Completion
-
Additional Comments
-
Checked by
-
Witnessed by
-
Contractor Name & Signature