Title Page

  • Project Title

  • Location
  • Make and Model No. of Elevator

  • Checked by

  • Conducted on

Elevator Commissioning Checklist

General

  • Elevator Type

  • Capacity (Person/Load)

  • Rated Speed (m/s)

  • Total Number of Entrances

  • Location of Designated Point of Entry

  • Specify

  • Floors served

  • Location of Machine Room

  • Elevator Car Dimension (width x depth x height)

  • Rated Supply Voltage (kW)

  • Type of Protection Against Uncontrolled Car Movement

  • Specify

Overspeed Governor

  • Overspeed Governor (shall be of the centrifugal type operating at a speed at least equal to 115 % of the rated speed, where the means of adjusting the overspeed governor shall be sealed)

  • Safety gear for the elevator car (shall be tripped by its own overspeed governor, where tripping of safety gears by devices which operate electrically, hydraulically or pneumatically is not allowed)

  • Operation of the overspeed governor (motor control and brake control circuits shall be opened before or at the same time as the governor trips)

Elevator Well & Pit

  • Stoppers (shall be provided on ends of guide rails)

  • Guide rails and fixing

  • Guide shoes

  • Suspension rope termination including compensating chain/rope

  • Traveling cables (shall be properly fixed with no twist or kink while traveling)

  • Buffer

  • Function of interlock among emergency doors and electric safety device

  • Function of submersible pump in elevator pit

  • Cleanliness and dryness of elevator pit

Elevator Machine Room

  • Motor Type complied with approved document

  • Provision for protection of Traction Sheaves, Pulleys and Sprockets

  • Seismic Sensors (shall be capable of detecting the primary wave and secondary wave of an earthquake and provide the protection against earthquake as specified in clause C14.10 of the GS) with audio & visual alarm on supervisory panel

  • Provisions for Post-voltage-dip operation

  • Digital multi-function metering devices installed

Machine Room-less Elevator

  • Lockable elevator equipment cabinet with hinged doors outside elevator well for housing controls, devices, panels and facilities that is accessible by authorized persons only and can be locked without a key from outside and bears a warning notice

  • A window of the control panel for observing overspeed governor and motor brake.

  • The platforms and works areas inside the elevator well shall be adequate and able to support the weight of at least two persons and additional tools and equipment for carrying out the maintenance and repair.

  • A suitable lockable container for storage of facilities, together with clear instructions on the method for releasing the brake and moving the elevator car in an emergency

Elevator Car

  • Means provided to minimize the risk of dragging children’s hands into gaps between car door panels and uprights.

  • Height of detection devices for re-opening of elevator door follows requirements

  • Automatic switching off of Ventilation Fan, Air-conditioning and Lighting inside an elevator car within an adjustable period of 2 minutes to 15 minutes after the last registered call is answered

  • CCTV camera

  • Monitor for information display system

  • Stainless steel drain water storage tank for goods elevator installed in markets and abattoirs

  • Emergency exit

  • Stainless steel load plate (no. of persons & kg)

  • Stainless steel “No smoking” and "In case of fire, do not use the elevator" notice

  • Overload device (shall be tested where floating car platform type device is not acceptable)

  • Full load device (floating car platform type device not acceptable)

Control Station

  • Call button with acceptance signal

  • “Door open” & “Door close” push buttons

  • Audible & visible signals for overload

  • Alarm push button with protection from being operated accidentally

  • An emergency alarm push button together with a buzzer, an indication light for acknowledgment and an intercom provided in the elevator car and connected to the building management office or the caretaker’s office which shall be equipped with a buzzer, an indication light and an intercom connected to the elevator car(s)

  • All lift control buttons with a minimum dimension specified in particular specification

  • Tactile markings of high contrasting color as specified in particular specification

  • Voice annunciator for indicating the stopping floor

  • Illuminated visual indicator for indicating the direction of elevator car travel and the position of the elevator car

  • Emergency key switch for bed/passenger elevator

  • Light switch, alarm reset switch, fan switch and cleaner’s stop-switch (shall be in the form of key switches or housed in a recessed metal box with hinged or sliding lid which shall be key-locked)

  • Non-stop button & key-operated attendant control switch for elevators with attendant control

Elevator Ride Quality

  • No presence of sound sources extraneous to the normal operation of the elevators or the building plant and equipment (e.g.<br>building environmental noise, audible construction, refurbishment or cleaning work etc.)

  • All building plant and equipment, including the adjacent elevator(s), in normal service

  • Documentary evidence or calculation proof provided to demonstrate that the feet of the instrumentation exert pressure on the floor of not less than 60 kPa

  • Elevator ride quality measurements boundaries

  • 1) at least 0.5 s before commencement of door close operation at the departure terminal floor;
    2) full travel of the lift from terminal to terminal; and
    3) at least 0.5 s after completion of door open operation or cessation of lift motion at the arrival terminal floor, whichever occurs last

  • At least one complete UP run and DOWN run measured

  • General information of measurements

  • Includes:
    - date and time of the measurement;
    - instrument identification number and the date of last calibration;
    - name(s) and affiliation of the persons present during measurement;
    - status of any equipment as defined;
    - building type;
    - lift number;
    - departure and arrival terminal floor designations;
    - direction of travel; and
    - distance of travel

Completion

  • Additional Comments

  • Checked by

  • Witnessed by

  • Contractor Name & Signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.