Title Page
-
Prepared by
-
Conducted on
-
Location
CAUSE
-
Level 16 - Call Point Activation
EFFECT ON SOUNDERS / INDICATIONS
Sounders / Indications
-
Alarm Sounders Level 16 North Tower
-
Visual Indicators Level 16 North Tower
-
"FIRE" Indication On all Fire Alarm Panels
EFFECT ON PLANT
Plant
-
Central Mechanical Plant Shuts Down
-
Gas Heating Plant Room Shuts OFF Valve
EFFECT ON DOORS
Doors
-
Level 16 Corridor Held open fire doors release.
-
GF Power Operated Doors Main Entrance Release/Open
-
Security Doors release
EFFECT ON MSFD
Motorized Smoke Fire Dampers
-
Smoke Dampers Activate and shut (Level 16)
EFFECT ON AOV
Automatic Open Vents
-
Level 16 AOV's Activativates and Opens
-
Head of Stair Extract Vent Opens
EFFECT ON LIFTS
Lifts
-
Lift 1 R/H TRIPLX SOUTH TOWER (10834822)
-
Lift 2 MIDDLE TRIPLEX SOUTH (10834823)
-
Lift 3 L/H TRIPLX SOUTH TOWER (10834824)
-
Lift 4 SERVICE LIFT SOUTH TOWER (10834825)
-
Lift 5 L/H DUPLEX NORTH TOWER (10834826)
-
Lift 6 R/H DUPLEX NORTH TOWER (10834827)
-
Lift 7 NORTH TOWER (10834828)
-
Lift 8 SERV LIFT NORTH TOWER (10834829)
-
Lift 10 MALVERN HOUSE (10834831)
-
Lift 11 SOUTH TOWER (10834832)
-
Lift 13 PLATFORM (10834834)
-
Lift 15 NORTH TOWER (10881651)
OBSERVATIONS
-
Observations.