Information
-
Audit Title
-
Document No.
General Profile
Site Details
-
Client Name
-
Branch/ Site Name
-
Address
-
Responsible Person
-
Responsible Person Job Title
-
Contact details
-
Assessors Name
-
Assessment Date
-
Premises Photo
-
Site Description
Main Building Profile Information
-
Primary use of Building
- Office
- Retail
- Factories
- Residential
- Residential Care
- Teaching Establishment
- Place of Public Assembly
- Hospitals
- Transport
- Licensed Premises
- Sleeping Accomodation
-
Recommended review period
- 6 Months
- 12 Months
- 24 Months
- 36 Months
- 48 Months
- 60 Months
- 72 Months
- N/A
-
Floor Area of Building (SqM)
-
Floor Area Assessed (SqM)
-
Number of Floors (Enter No.)
-
Number of Floors Occupied (Enter No.)
-
Is the occupier the sole user of the building?
-
Details of multi occupied building.
-
Total Number of Staff On-site (Enter No.)
-
Occupants with Disabilities (Enter No.)
-
Sleeping Occupants (Enter No.)
-
Floors Accessed by Public (Enter No.)
-
Total Occupancy (Enter No.)
Fire Safety Related Profile Information
Fire Safety Related Profile information
-
Are the premises currently free of any outstanding enforcement notices?
-
Is the emergency plan for the premises adequate?
-
Alarm Type
- Unknown
- L
- L1 All areas
- L2 Escape routes, adjoining rooms and specific hazard areas
- L3 Escape routes and adjoining rooms
- L4 Escape routes only
- L5 To suit specific risk assessment
- LD
- LD1
- LD2
- LD3
- P
- P1
- P2
- PD
- PD1
- PD2
- M
- M\E
- M\P
- L\M\E
- P\M\E
- No AFA
- None
-
Are the premises free of fire incidents in the last 24 months?
Incident
-
Floor
-
Room/ Area
-
Details of incident.
-
Person Injured as a Result of Fire
Inaccessible Areas
-
Inaccessible Areas
Area
-
Floor
-
Room/ Area
-
Reasons for No Access
Mitigation Information
-
Indicate the Location of:
-
Mains Electrical intake
-
Room
-
Main Gas Intake
-
Room
-
Fire Alarm Indicator Panel
-
Room
-
Sprinkler Stop Valve
-
Room
-
Fire Fighting Switches
-
Room
-
Fire Fighting Shafts and Risers
-
Emergency Access for fire Service Vehicles
-
Location of Fire Hydrants
-
Location of Fire Assembly Point
Log Book
Cyclical Tasks
-
Electrical Wiring Tests
-
Date
-
Fire Detection and Alarms
-
Date
-
Emergency Lighting
-
Date
-
PAT Testing
-
Date
-
Fire engineered Systems
-
Date
-
Heating and Airconditioning Systems
-
Date
-
Fire Drill
-
Date
-
Fire Training
-
Date
-
Sprinkler/ Suppression System
-
Date
-
Escape Routes
-
Date
-
Fire Fighting Equipment
-
Date
-
Add Building Specific Item
Building Specific
-
Inspection Type
- Electrical Wiring Tests
- Fire Detection and Alarms
- Emergency Lighting
- PAT Tests
- Fire Engineered Systems
- Heating Systems
- Fire Drill
- Fire Training
- Sprinkler/ Suppression System
- Escape Routes
- Fire Fighting Equipment
- Other
-
Cyclical Task
-
Location
-
Has the Cyclical Task been completed
Management
Management Responsibilities
-
Good management of fire safety on your premises is essential to ensure that any fire safety matters that arise are always effectively addressed.
-
1.1 Are management and staff fully aware of the fire safety features of the premises in compliance with relevant guidance, or is their knowledge at a satisfactory level?
Concern
-
Select Concern
- 2. Employees not aware of risks
- 3. Poor evacuation arrangements
- 4. Insufficient fire marshals
- 5. Contractors non compliant
- 6. Processes managed poorly
- 7. Employees not aware of haz subs
- 8. Environmental impact of fire
- 9. Access management - hazards
- 10. No fire marshals nominated
- 11. Young persons - parents etc.
- 12. No emergency plans
- 13. No multi Occ. coordination
- 14. FR Notice differs from emerg. plan
- 15. Staff unaware of EP
- 16. No fire policy
- 17. Emerg. Plan different to Policy
- 18. Escape routes not checked
- 19. Fire fighting policy unclear
- 20. Escape route policy ignored
- 21. Emerg. Plan help of FB SWFS
- 22. Emerg. Plan help of FB Other
- 23. Evac roll call inadequate
- 24. Competent persons to assist
- 25. No FS Mgmnt practices
- 26. Monitor FS
- 27. Temp workers - inform
- 99. Other
-
Cause for Concern
-
Recommendation
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
1.2 Have staff received fire awareness training in compliance with relevant guidance, or otherwise adequate training?
-
Concern
Concern
-
Select Concern
- 1. No fire induction training
- 2. No ongoing training provided
- 3. No training detail in records
- 4. No existing nominations/ training
- 5. Fire marshals not trained
- 6. Outside contractors not trained
- 7. No fire drill in 6 months
- 8. No training records available
- 9. No haz subs training policy
- 10. Trng not inline with Emerg. Plan
- 12. Not all records in log book
- 11. Inappropriate training
- 13. Evac. debrief req.
- 14. Trng. req. more often
- 15. Trng. req. Small Premises
- 99. Other
-
Cause for Concern
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
1.3 Are housekeeping standards compliant with relevant guidance, or otherwise satisfactory?
Concern
-
Select Concern
- 1. Flams not disposed of safely
- 2. Combustibles on MoE
- 3. Floor coverings are trip hazards
- 4. Fire exit obstructed outside
- 5. MoE route obstructed
- 7. Fire route not kept clear
- 8. Room use inappropriate
- 9. Fire route not delineated
- 10. Room contents impede MoE
- 11. Waste skips too close
- 12. Storage within staircase
- 13. Exits obstructed - housekeeping
- 14. Storage in vicinity of electrics
- 15. Elec/ Plant-manage
- 16. Combustibles general
- 17. No recycling in routes
- 99. Other
-
Cause for Concern
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Hazards
Ignition Risks
-
Identification of hazards and their removal or effective control is an integral part of a fire risk assessment. This section relates to ignition sources and the presence of flammable and combustible materials which are not suitably managed.
-
2.1 List all ignition sources, flammables, combustibles and dangerous substances that are not managed.
-
Concern
Concern
-
Select Concern
- I.1 Smokers Materials
- I.2 Fixed electrical equipment
- I.3 Portable electrical equipment
- I.4 Mains electrical supply
- I.5 Electrical extension leads
- I.6 Electrical adaptors
- I.7 Electrical heating system
- I.8 Electric portable heating system
- I.9 Gas heating system
- I.10 Portable gas heating appliances
- I.11 Cooking appliances
- I.12 Hot work processes
- I.13 Potential for deliberate ignition
- I.14 Open flam/equipment processes
- I.15 Display lighting equipment
- I.16 Lighting
- I.17 Other
- C.1 Flammable liquids in use
- C.2 Flammable liquids in storage
- C.3 Flammable gases in use
- C.5 Combustible Solids
- C.6 Untreated handing textiles
- C.7 Clothing displays
- C.8 Decorations
- C.9 Explosive atmospheres
- C.10 DSEAR Assessment
- C.11 Other
-
Cause for Concern
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Construction
Construction
-
The materials from which your premises are constructed and the quality of building work and state of repair could contribute to the speed with which any fire may spread, potentially affecting escape routes.
-
3.1 Are the fire resisting separating floors and or walls of the building compliant with relevant guidance or otherwise in a satisfactory condition?
Concern
-
Select Concern
- 1. Separating floors not FR30
- 2. Separating floors not FR60
- 3. Holes in FR30 ceiling
- 4. Holes in FR60 ceiling
- 5. Roof void storage Std for FR
- 6. Roof void storage tiles damaged
- 7. FR30 Ceiling penetrated
- 8. FR60 ceiling penetrated
- 9. Are materials used FR30
- 10. Are materials used FR60
- 11. Do floors meet required FR
- 12. Core panels breached
- 13. Core panels damaged
- 14. Core panel joints damaged
- 15. Ceiling tiles - fire spread
- 16. Fire spread to other buildings
- 17. Ceiling tiles - fire spread
- 18. Walls not FR30
- 19. Walls not FR60
- 20. holes in FR walls 0 fire spread
- 21. Holes in FR60 walls - fire spread
- 22. FR30 wall penetrated
- 23. FR60 wall penetrated
- 24. Glazing not FR30
- 25. Glazing not FR60
- 26. Glazing not pyro
- 27. Gap at head
- 28. Soil pipes thru floors
- 29. infil not req std
- 30. AFD for walls in flats
- 31. FR access hatch
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
3.2 Are shafts for lifts enclosed with fire resisting construction in compliance with relevant guidance or otherwise satisfactory?
-
Concern
Concern
-
Select Concern
- 1. Not enclosed with FR30
- 2. Not enclosed with FR60
- 3. FR30 wall penetrated
- 4. FR60 wall penetrated
- 5. Access hatch not FR
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
3.3 Are shafts for services enclosed within fire resisting construction, in compliance with relevant guidance, or otherwise satisfactory enclosed?
Concern
-
Select Concern
- 1. Not enclosed with FR30
- 2. Not enclosed with FR60
- 3. FR30 wall penetrated
- 4. FR60 wall penetrated
- 5. Air Con not adequate prot.
- 6. Vent sys not adequate prot.
- 7. Duct sys not adequate prot.
- 8. Bathroom ducts shut down on alarm
- 9. Access hatch FR?
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
3.4 Is the surface spread of flame classification of materials used to line walls and other surfaces compliant with relevant guidance or acceptable?
-
Concern
Concern
-
Select Concern
- 1. Class 3 SSoF (4m2 Rm)
- 2. Class 3 SSoF (30m2 Rm)
- 3. Class 1 SSoF req for room
- 4. Class 0 SSoF req circ area
- 5. Excessive SSoF display material
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
3.5 Are areas of ancillary accommodation separated from the remaining of the building with fire resisting construction in compliance with relevant guidance, or in a satisfactory manner?
Concern
-
Select Concern
- 1. Kitchen not FR30
- 2. Stores not MoE not FR30
- 3. Hazard area not FR30 enclosed
- 4. Int.car park not FR30 enclosed
- 5. Hazard area not FR60 enclosed
- 6. Int.car park not FR60 enclosed
- 7. Plant/services room not FR30
- 8. Plant/services room not FR60
- 9. Boiler room not FR30
- 10. Boiler room not FR60
- 11. Ancilry. accom on MoE not FR30
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
3.6 Are cavity barriers provided in voids in compliance with relevant guidance, or is the provision in voids satisfactory?
Concern
-
Select Concern
- 1. Inadequate void separated
- 2. Damaged Cav Barr in void
- 3. FR30 CB penetrated
- 4. Cavity barrier required
- 5. Non intrusive no cav barr check
- 6. FR60 CB penetrated
- 7. No asbestos reg/cav barr check
- 8. No asbestos reg/critical area check
- 9. CB no access thru ceiling
- 10. No CB over stairs etc
- 11. AFD in lieu CBs
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Means of Escape
Means of Escape
-
It is essential that escape routes, and the means provided to ensure they are used safely, are managed and maintained to ensure that they remain usable and available at all times when the premises are occupied.
-
4.1 Are the escape routes of such a number and so sited that the travel distance from any point to the nearest storey exit is compliant with relevant guidance or within acceptable limits?
-
Concern
Concern
-
Select Concern
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
4.2 Is the number of escape routes from a room or storey compliant with relevant guidance or sufficient?
-
Concern
Concern
-
Select Concern
- 1. +60 pers on single esc route
- 2. Over max occupancy for storey
- 3. Insufficient room/storey exits
- 4. Insufficient exit width
- 5. Escape corridors narrow in width
- 6. Escape corridors obstructed
- 7. Excess persons using room
- 8. Not to modern stds
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
4.3 Is escape from inner rooms compliant with relevant guidance or otherwise satisfactory?
-
Concern
Concern
-
Select Concern
- 1. Access room is high fire hazard
- 2. No VP or AFD
- 3. Inner room partitions too high
- 4. VP inadequate
- 5. Inner Inner room sitn
- 6. Inner inner no AFD
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
4.4 Are corridors compliant with relevant guidance, or provided with adequate fire resistance and/or other facilities to allow persons to reach a storey exit safely?
Concern
-
Select Concern
- 1. FR30 corridors in sleep/ res acc
- 2. Partitions not to ceiling
- 3. Subdivide dead end corridors
- 4. Subdivide corridors > 12mtrs/exits
- 5. Dead end not a prot corr.
- 6. Service corridor not FR30
- 7. Service corridor not FR60
- 8. FD30 corridors for diff occ
- 9. FR30 walls penetrated
- 10. FR60 walls penetrated
- 11. Combustibles in corridor
- 12. Corridor not FD60 res/sleep acc.
- 13. Storage in corr no AFD
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
4.5 Are accommodation stairways and or lifts sited in line with relevant guidance or satisfactory sited so that their position does no prejudice escape from upper floors?
-
Concern
Concern
-
Select Concern
- 1. Accom stairs prej escape
- 2. Escalator pred escape (30)
- 3. Lift prej escape (30)
- 4. Acc stair prej (60) escape
- 5. Esc prej upper flr escape (60)
- 6. Lift prej upper flr escape (60)
- 7. Stair prej escape req downstand
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
4.6 Is the capacity of protected stairways compliant with relevant guidance, sufficient and do they offer suitable protection to ensure the safe escape of occupants?
-
Concern
Concern
-
Select Concern
- 1. MoE stairways not FR30
- 2. MoE stairways not to final exit
- 3. Flats-no FR doors/vents
- 4. Unprot cpd/store on stair
- 5. Store/cpd on single stair
- 6. Reception area >10m2 on stairway
- 7. Reception area in single stairways
- 8. Risk WC opens onto stair
- 9. Horiz.movement thru stair enc
- 10. Insufficient prot stairs
- 11. Stairways not wide enough
- 12. Sngl stair no basemnt separation
- 13. Stairs no basemnt separation
- 14. Sngl stair not adequate protectd
- 15. Car park stair no adequate prot
- 16. Stair not adequately protected
- 17. Stair tread nosing lose
- 18. Stair coverings are defective
- 19. Defective handrail
- 20. Stairlift reduces escape width
- 21. Unprot electrics in prot stairs
- 22. No lobby approach > 20m high bldg
- 23. Combustibles in protectd stairs
- 24. This is a single stair condition
- 25. Dry riser not tested
- 26. Gap at side flr
- 27. Dirty/slippery stair
- 28. Loose mats etc
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
4.7 Are external stairways and routes compliant with relevant guidance or otherwise satisfactory for use in case of emergency?
Concern
-
Select Concern
- 1. Stairway may be unsafe
- 2. Unprotectd openings 1.8m of stair
- 3. Access rooms to stair not FR
- 4. SC req external escape door
- 5. Stairs not weather protected
- 6. Vents within 1.8m of stairs
- 7. No handrail provided
- 8. Defective handrail
- 9. External MoE route hazardous
- 10. No route access to RV point
- 11. Openings 1.8m ext exit route
- 12. Maintain external exit route
- 13. External route via unmade ground
- 14. Keep underground levels down
- 15. Obstructs on route
- 16. Poorly defined route
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
4.8 Are arrangements made for the means of escape of disabled persons complaint with relevant guidance or otherwise acceptable?
-
Concern
Concern
-
Select Concern
- 1. Disabled not considered in FRA
- 2. Poor disabled MoE strategy
- 3. No disabled emergency plan
- 4. No nomination system to assist disabled
- 5. 1st stage alert req for disabled
- 6. No training for disabled strategy
- 7. Trng of staff who help disabled
- 8. No disabled evacuation plan
- 9. Safe refuges not provided
- 10. refuge access obstructed
- 11. W/chairs impede MoE stairs
- 12. Inadequate refuge areas
- 13. Inadequate disabled evac lift
- 14. No comms in refuge
- 15. Fire alarm audible for deaf
- 16. Inadequate general lighting
- 17. Fire safety signs to small
- 18. Stairway not disabled friendly
- 19. Handrail not disabled friendly
- 20. No colour contrast on steps
- 21. Inadequate ramps
- 22. Lift not suitable for use in fire
- 23. Public access and special needs
- 24. External route-disabled
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
4.9 Are engineered systems fully compliant with relevant standards, or otherwise suitable for their purpose and adequately maintained?
Concern
-
Select Concern
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Doors and Partitions
Doors and Partitions
-
Effective fire resisting doors and partitions are vital to ensure that occupants can evacuate to a place of safety. The relationship between security and ease of use of doors on escape routes requires careful planning to ensure both objectives are satisfied. Any device which impedes occupants from escaping will not be acceptable.
-
5.1 Are fire resisting doorsets compliant with relevant guidance or otherwise installed and maintained to an acceptable standard?
Concern
-
Select Concern
- 1. FR doors in poor state
- 2. Cold seals defective
- 3. Defective intumescent seals
- 4. No/missing cold seals
- 5. No/missing intumescent seals
- 6. Ineffective self closer
- 7. Insufficient hinges
- 8. Door not closing properly
- 9. Doors not kept locked shut
- 10. Doors not FR30
- 11. Fire door is not to FD20SC
- 12. Fire door is not to FD30S
- 13. Fire door is not to FD30SC
- 14. Fire door is not to FD60
- 15. Fire door is not to FD60SC
- 16. Hold open device not provided
- 17. No self-closing device
- 18. Transform not FR
- 19. Inappropriate grill in fire door
- 20. Fire door wedged open
- 21. Letter boxes not FR30
- 22. Corridor in heavy use
- 23. No seals doors in critical areas
- 24. U2v that glazing is to standard
- 25. Side glazing no to std
- 26. Excess gap
- 27. Risk bathrm-upgrade fr30sc
- 28. Door sticking at bottom
- 29. Not to modern day stds
- 30. Non FR letter box
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
5.2 Are fire resisting partitions compliant with current guidance or otherwise satisfactory and installed/maintained to an appropriate standard?
-
Concern
Concern
-
Select Concern
- 1. Partition not FR30
- 2. Partition in disrepair
- 3. Glazing not FR below 1.1m
- 4. Partition not FR60
- 5. FR60 partion needs repair
- 6. Risk bathrm-FR30
- 7. U2v glazing is FR30
- 8. U2v that partition is FR30
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
5.3 Are doors on escape routes compliant with relevant guidance, or otherwise capable of being used effectively in an emergency?
-
Concern
Concern
-
Select Concern
- 1. Doors obstructed externally
- 2. Door not maintained FFF
- 3. Door opens against MoE
- 4. Door sticks - not opening
- 5. Emergency open device broken
- 6. Manual door override not clear
- 7. No manual override for doors
- 8. Electric doors release on FA
- 9. Inappropriate door fastening
- 10. Blocked exit
- 11. Final exit blocked
- 12. Elect doors open on FA/mains fail
- 13. Platform O/S exit door not viable
- 14. Exit door multiple fastenings
- 15. TT lock-no sign
- 16. Pin open doors
- 17. Door opens out over a step
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Signs and Notices
Signs and Notices
-
Signs and notices must be used, where necessary, to help people identify escape routes, find firefighting equipment and provide emergency information to occupants.
-
6.1 is the provision of suitable signs and notices in compliance with relevant guidance, or otherwise acceptable?
Concern
-
Select Concern
- 1. Fire 'Door Keep Shut' req
- 2. 'Fire Door Keep Locked' req
- 3. Missing - 'Push Bar to Open'
- 4. Missing - 'Push Pad to Open'
- 5. Missing - 'Fire Exit'
- 6. Missing - directional signs
- 7. Fire routine notices missing
- 8. Out of date - 'Fire Routine'
- 9. No extinguisher sign
- 10. Incorrectly sited - 'Fire Exit'
- 11. Signs not compliant with regs
- 12. Fire signs not properly fixed
- 13. Missing - 'Fire Exit Keep Clear'
- 14. Signs are too small
- 15. Missing - 'Fire Shutter - Keep Clear'
- 16. Missing - 'Fire Shutter - No Throughfare"
- 17. Redundant fire signs in use
- 18. Missing - 'Do not use lift'
- 19. Missing - 'No Smoking'
- 20. Missing - 'Dry/Wet Riser'
- 21. Missing - 'Call Point'
- 22. refuge areas not identified
- 23. Fire fighting lobby no sign
- 24. Cooker shut down not clear
- 25. Flam storage not indicated
- 26. Fire Routine Notice
- 27. Fire Routine Notice inaccurate
- 28. FR notice is multi occ differ
- 29. Insufficient directional signs
- 30. Directional signs inappropriate
- 31. Confusing signs
- 32. Staff/public RNs
- 33. Different RNs
- 34. Ood FR notices
- 35. Old FR notice
- 36. Signs do not comply with regs altho functional
- 37. Automatic fire door keep clear sign required
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Fire Fighting Equipment
Fire Fighting Equipment
-
Firefighting equipment suitable for the risks in your premises must be provided. Appropriate training is required, and the equipment should be checked on a regular basis and maintained by a competent person.
-
7.1 Is the provision etc of portable fire fighting equipment in accordance with relevant guidance, or satisfactory relevant to the risk at the premises?
-
Concern
Concern
-
Select Concern
- 1. Insufficient equipment
- 2. Equipment not serviced
- 3. Equipment wrong siting
- 4. Equipment not secured
- 5. Too many extinguishers
- 6. Extinguishers not to BS EN3
- 7. Hose reels inappropriate media
- 8. Exts obstructed
- 9. Insuff equip but OK
- 10. Equip not req
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
7.2 Are fire suppression systems installed and maintained in compliance with current standards and/or appropriate, satisfactory installed and adequately maintained?
Concern
-
Select Concern
- 1. Suppression system required
- 2. Instructions for use missing
- 3. no training in Supp Stsyem
- 4. Discharge heads not functional
- 5. Greater sprinkler coverage rqd
- 6. Storage above sprinkler heads
- 7. Suppression system damaged
- 8. Maintenance not to standard
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Fire Alarms
Fire Alarms
-
The level of automatic fire detection required in your premises will be designed to support the evacuation strategy. The design should consider any specific risks on your premises.
-
8.1 Is the fire alarm system compliant with relevant standards, or otherwise suitable for the risk, and appropriately installed and maintained?
Concern
-
Select Concern
- 1. No means of raising alarm
- 2. No fire alarm system provided
- 3. Insufficient call points
- 4. insufficient detectors
- 5. ineffective alarm system zoning
- 6. Call point obscured
- 7. Call point required
- 8. Alarm not loud enough
- 9. Audibility of FA untested
- 10. No AFD provided in area
- 11. No visual alarm
- 12. No visual waning system
- 13. Defective LED in Detector
- 14. No means to summon FB
- 15. No AFD compensatory features
- 16. Detector removed from fitting
- 17. Inadequate AFD for sleeping risk
- 18. Inadequate AFD
- 19. Need to confirm alarm L2 min
- 20. L1 req
- 21. L2 req
- 22. L3 req
- 23. L4 req
- 24. No part6 system
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
8.2 Is the fire alarm system maintained, tested and records kept, in compliance with relevant guidance, or to an otherwise acceptable level?
Concern
-
Select Concern
- 1. Not tested comp
- 2. No records
- 3. Inadequate log book
- 4. 5839 occ/ L1 test
- 5. records comp testing
- 6. No L1/occ test rec
- 7. Central records
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Lighting
Lighting
-
The premises must be provided with sufficient general lighting to ensure the occupants can utilise escape routes safely in an emergency. If the supply of normal lighting fails emergency lighting may be required.
-
9.1 Has the building sufficient general lighting, in compliance with relevant guidance or is lighting satisfactory for purpose?
Concern
-
Select Concern
- 1. Insuffic gen lighting on MoE
- 2. Light fitting defective
- 3. Gen lighting ext insufficient
- 4. no switch for external lights
- 5. Switch for ext lights unmarked
- 6. Borrowed lighting
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
9.2 Is the building protected by an emergency lighting system, compliant with relevant guidance, or otherwise acceptable?
Concern
-
Select Concern
- 1. No EL system provided
- 2. EL level inadequate
- 3. EL needs extending
- 4. Windowless room - no EL
- 5. No EL in corridors over 30mtrs
- 6. No EL in room over 60m2
- 7. No EL on stairs over 18m high
- 8. No EL provided externally
- 9. No EL in toilet over 8m2
- 10. EL damaged / defective
- 11. Not enough illum exit signs
- 12. Not enough EL units
- 13. Inadequate lighting to RV points
- 14. LED not viable to identify EL
- 15. LED for operational defecive
- 16. EL insuff-torches?
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
-
9.3 Is the emergency lighting system maintained and tested in accordance with relevant guidance or otherwise satisfactory?
Concern
-
Select Concern
- 1. EL not comp tested
- 2. Inadequate Log Book
- 3. Central records
- 4. 5266 occ/L1 test
- 5. Records comp test
- 6. No L1/occ test rec
- 99. Other
-
Evidence if appropriate
-
Action required
-
Recommended completion date
Risk Rating
Risk Rating
-
Overall risk rating for the premises...
Sign Off
-
On Site Representative
-
Assessor's Signature