Information

  • Client / Site

  • Location
  • Conducted on

  • Case No:

  • Prepared by

  • Personnel

  • Document No.

Inspection Information

  • Type of Inspection

  • Plan Review No:

  • Permit Number

  • Contact Information

  • Contact Name

  • Phone

  • Email

  • Occupancy Type

  • Knox Box located

  • Knox Box located

  • Knox Box located

Permits

  • Permits Posted IFC 105.3.5

  • Operational Permit Required IFC 105.6

Fire Department Access

  • Fire Lanes unobstructed width of 20 ft and 13-6 ft high. IFC 503.2.1

  • Approved signs or markings IFC 503.3

  • Fire lanes shall not be obstructed including parked cars. IFC 503.4

  • Post and maintain street address so it is visible from the street with minimum 4" letters residential or 6" for commercial. IFC 505.1

  • Approved Key Box is required when immediate access is necessary. Provide Keys for entry and interior doors, elevator, and fire systems. IFC 506.1

  • Fire lanes, hydrants, and equipment must remain clear of obstructions that may inhibit use. IFC 507.5.4

  • A 3-foot clear space shall be maintained around hydrants. IFC 507.5.5

  • Other

Fire Protection Equipment and Systems

  • Storage must be 18" below sprinkler heads, and 24" from the ceiling in unsprinklered buildings. IFC 315.2.1

  • Fire protection equipment must be maintained and/or repaired. IFC 901.6

  • Sprinkler heads found to be corroded, dirty, greasy, or covered with paint must be cleaned or replaced. IFC 901.6

  • Extinguishing systems must be serviced at regular intervals; sprinklers & fire extinguishers annually, hood and duct systems 3, 6, or 12 months. IFC 906.6.1

  • Provide Class K extinguisher within 30 feet of cooking areas. IFC 904.11.5

  • Commercial occupancies must have 2A:10BC and be sufficiently charged. IFC 906.3

  • Extinguishers are to be located so maximum travel distance is 75 feet for ordinary combustibles or 30 feet for flammable liquids or similar materials. IFC 906.3.1

  • Extinguishers shall be mounted on brackets or in cabinets, or set on shelves no higher than 54" or lower than 48" above the floor. A sign indicating location is necessary when it is not visible. IFC 906.9

  • Fire Alarm systems shall be tested annually. IFC 907.9

  • Other

Fire Doors

  • Reinstall fire door(s) removed. IFC 703.1

  • Do not block or restrain fire door(s) which must be maintained self closing and remain in closed position except in actual use. IFC 703.2

  • Repair fire door(s) so they open freely, close completely, and latch when released

  • Other

Rubbish, Debris, Combustable Materials

  • Remove and properly dispose of tall grass, brush, and/or debris. IFC 304.1.2

  • Remove and properly dispose of debris. IFC 304.2

  • Combustible waste must be placed in covered metal containers. IFC 304.3.1

  • Exterior dumpsters greater than 1 CY shall not be within 5 feet of combustible construction. IFC 304.3.4

  • Remove accumulations of grease from range hood, range, and connecting flue. Clean periodically. IFC 904.11.6.3

  • Other

Combustable Storage

  • Stock and/or storage must be at least 24" from ceiling or 18" below sprinkler heads. IFC 315.2.1

  • Remove all flammable or combustible materials from unfinished basement. IFC 315.2.4

  • Storage in attic is not allowed unless protected by sprinkler system or 1 hour construction. IFC 315.2.4

  • Combustible storage is not allowed in Boiler, Mechanical, or Electrical Panel rooms. IFC 315.2.3

  • Heating devices such as furnaces, wall heaters, water heaters, and the Like must have adequate clearance from combustible materials. IFC 603.5.1

  • Other

Miscellaneous

  • Requirements that are essential for public safety but not specifically mentioned in the IFC shall be determined by the AHJ. IFC 102.8

  • Any installation that requires inspection prior to use and is covered or concealed prior to inspection shall be exposed for inspection. IFC 106.3

  • OPENINGS WALLS / CEILINGS: Repair/seal unprotected opening with fire resistive materials. IFC 703.1

  • COMPRESSED GAS: Secure/chain cylinders upright in approved manner. IFC 3003.5.3

  • LP GAS: discontinue unapproved use of LP gas in the building

  • Other

Exits

  • No storage under stairways unless protected by 1 hour construction

  • Exit doors shall swing in direction of travel if it services a hazardous area or occupant load of 50 or more. IFC 1008.1.2

  • Exit doors shall operate from the inside without the use of a key or any special knowledge or effort. IFC 1008.1.9

  • Post sign above main exit in 1" letters: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. IFC 1008.1.9 3

  • Minimum stairway width shall not be less than 44" or 36" if occupant load is 49 or less. IFC 1009.1

  • Exit signs are required at exit doorways and where necessary to clearly indicate the direction of egress. IFC 1011.1

  • Where lighted exit signs are installed they will have 2 working bulbs. IFC 1011,.2

  • Exit ways and doorways must kept free of obstructions and obstacles, including temporary storage. IFC 1030.3

  • Other

Assembly Occupancies

  • Conspicuously post a durable sign indicating the maximum room occupancy. IFC 1004.3

  • Other

Flammable Liquids

  • All spray operations exceeding 9 square feet must be done within an approved spray booth, room or area.

  • Flammable liquids in combined amount exceeding 10 gallons must've stored in a flammable liquids cabinet. Amount stored in such cabinets cannot exceed 120 gallons. Maximum of 3 cabinets in a room. Quantities in excess of this must be stored in an approved flammable liquid storage room. IFC 3404.4.4

  • Flammable liquid containers under 30 gallons cannot be stacked more than 2 high (or 3 feet; whichever is greater) and containers over 30 gallons cannot be stacked. IFC 3404.3.5.2

  • Warning signs are required on all flammable liquid containers, entrances to storage rooms, storage cabinets and at service stations where flammable liquids are stored and dispensed. IFC 3403.5

  • Other

Electrical

  • Unused electrical panels must be covered (no tape). IFC 605.1

  • Wiring or circuits that are no longer in use must be removed. IFC 605.1

  • Clearance in front of panels at least 30 inches. IFC 605.3

  • Doors into electrical control panel rooms shall be marked with sign stating ELECTRICAL ROOM. IFC 605.3.1

  • Multi Plug Adaptors are not allowed except for those with a fused or circuit breaker protected " pore strip". Power strips can not be connected end to end. IFC 605.4

  • Electrical cords cannot run through doorways, windows, or similar openings, located in foot traffic or were damage may occur. IFC 605.4.3

  • Extension Cords cannot be used for permanent wiring of lights or equipment. Only one device may be used per cord when using extension cords. IFC 605.5

  • Damaged electrical cords must be replaced or repaired. In line splices are not allowed. IFC 606.5.3

  • Cover plates must be provided for light switches, outlets, and/or any junction box with exposed wiring. IFC 606.6

  • Other

Signatures

  • Violations found

  • A reinspection will be required on

  • A reinspection is not required but you must attend to the items noted above

  • Inspector

  • Received by

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.