Information
-
Campus Name
Tap to enter information
-
Building Name
- Alexander Turnbull Building /ja-h
- Collins Building /ja-q
- McCance Building /ja-g
- St Paul's Chaplaincy Centre /ja-f
- University Centre /ja-d
- Graham Hills Building /ja-p
- Livingstone Tower /ja-l
- Curran Building /ja-at
- Lord Hope Building /ja-ae
- Sir William Duncan Building /ja-x
- SIBS Building Robertson Wing /ja-ab
- SIBS Hamentt Building /ja-b
- Wolfsen Centre /ja-w
- Henry Dyer Building /ja-t
- James Weir Building /ja-m
- Royal College Building /ja-r
- Students Union /ja-aa
- Thomas Graham Building /ja-c
- Architecture Building /ja-a1
- Colville Building /ja-e
- John Anderson Building /ja-k
- Barony Hall /ja-ay
- Ramshorn Theatre and Graveyard /ja-ax
- Naval Architecture Building /ja-na
- PNDC Building /ja-pn
- AFRC Building /ja-af
- Externals
Tap to enter information
-
Building Name
- Andrew Ure Hall /ja-ak
- Brikbeck Court /ja-ad
- Chancellor's Hall /ja-bc
- Forbes Hall /ja-as
- Garnett Hall /ja-ar
- James Blyth Court /ja-bb
- James Goold Hall /ja-be
- James Young Hall /ja-bd
- Lord Todd /ja-aq
- Murray Hall /ja-ap
- Patrick Thomas Court /ja-aw
- Thomas Campbell Court /ja-ba
- Externals
Tap to enter information
-
Building Name
-
Floor/Level
-
University of Strathclyde
-
Conducted on
-
Prepared by
-
File Name
-
Room Details
Room
-
Room Name/Number
-
Room has no defects
-
Enter Element
Element
-
Elements
- MECHANICAL
- Heating System /8
- Steam System /9
- Ventilation and Air Conditioning /10
- Drainage /13
- Piped Mechanical gases and Vacuum /14
- Hot Cold and Mains Water /15
- Boiler, Calorifier Plant /17
- Mechanical Fixed Plant /18
- Fuel, Water Storage and Distribution /19
- External Works /6
- ELECTRICAL
- Electrical Installation /7
- Communications: Alarm and Safety /11
- Communications: Phones and Paging /12
- Lifts /16
- Electrical Fixed Plant /18
- Electrical Fuel, Water Storage and Distribution /19
- Other /100
- LEGISLATIVE
- Health and Safety Elec /1 (L)
- Electrical Safety /2 (L)
- Asbestos /5 (L)
- Health and Safety Mech /1 (L)
- Legionellaosis Safety /3 (L)
- Hazardous Substances Safety /4 (L)
- Water Safety /8 (L)
- Environmental Safety /9 (L)
- Gas Safety /10 (L)
- Flammable Liquids and Petroleum Safety /11 (L)
- Pressure Systems Safety /12 (L)
- Food Safety /13 (L)
- Animal Procedures Safety /14 (L)
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
- Ductwork Grilles Diffusers /1
- Fans /2
- Filters /3
- Heating and Cooling Batteries /4
- Humidifiers /5
- Refrigeration Plant /6
- Controls /7
- Fan Coil Units /8
- Chilled Beams /9
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
- Domestic Cold Water /1
- Domestic Hot Water /2
- Drinking Water /3
- Hosereels /4
- Hydrants /5
- Wet/Dry Risers /6
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
- Compressor /5
- Condenser /7
- AC Unit /8
- Extractor /9
- Water Treatment Plant /10
- Pressure Vessel /11
- Heater /12
- Steam Receiver or Well /13
- Vacuum Plant /15
- Extract Hood or Equipment /16
- Lifting Equipment /17
- Incinerator or Waste Disposal /18
- Autoclaves or Steriliser /21
- Cold or Hot Rooms /22
- Cooling Towers /23
- Equipment or Plant /24
- Storage Vessel /25
- Service Distribution /26
- Gas Suppression Systems /28
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
- Passenger Lifts (Traditional) /1
- Passenger Lifts (MRL) /2
- Goods Lifts /3
- Hoists /4
- EVCS /5
- Platforms Lifts /6
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
- Car Park Barriers /1
- Capacitors /2
- Roller Shutter Doors /3
- Door Access Control /4
- Generator /6
- Batteries and Chargers /14
- I.T. Installation /19
- CCTV /20
- UPS /27
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Electricity Meter /3
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Variable Sub Element
- Escapes and Exits /1
- Safety Notices /2
- Safety /3
- Ionising Radiation /4
- Firefighting /5
- VDU Furniture /6
- Radiological Protection /8
- Spread of Flame /9
- Dry Riser /10
- External Lighting /11
- Hose Reel /13
- Bar Licence /14
- Manual Handling /15
- Occupiers Liability /16
- Pest Control /17
- Lightning Protection /18
- Missing Variable /255
-
Condition Coding
-
A - As New, B - Serviceable with minor repairs, C - Operational, but major works required in 5 years, D - Unsafe, Inoperable, breakdown imminent, DX - Failed or in dangerous condition
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- GENRAL
- Electrical installation showing signs of deterioration
- Installation uses redundant equipment
- Installation uses redundant accessories
- Installation has damaged or missing equipment
- Inadequate means of isolation
- Damaged flexible conduits
- Inadequate mechanical protection of cabling systems
- LIGHTING
- Installation uses redundant right sources
- Light fittings showing signs of deterioration
- Inappropriate lighting for the type of works carried out
- Inadequate emergency lighting
- Inadequate lighting levels
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures
-
Sub Element
-
Condition Coding
-
CX - Lack of compliance within a defined period, DX - Lack of compliance with current legislation, UX - Lack of compliance with current legislation, unsafe and/or likely to cause accident
-
Standard comments
- Room is unheated
- Room is unventilated
- Drainage is installed with no trap evident
- Pipework installation with redundant dead legs
- Minor strip out of redundant services required
- Uninsulated water services pipework
- Evidence of leakage from pipework joint
- serious corrosion evident
- Reinstate missing insulation
- Reinstate missing insulation in plantroom
- Gas cylinder not restrained
- Replace damaged emitter
- Replace obsolete R22 system
- Replace 2 pipe FCU at end of life
- Replace 4 pipe FCU at end of life
- Replace split AC system at end of life
- Replace cylinder regulator
- Increase fume cupboard duct discharge height
- Replace missing grille
- Replace damaged grille
- Repair loose grille
- Replace wall mounted control panel at end of life
- Replace floor mounted control panel at end of life
-
Notes
-
Priority Code
-
P1 - Immediately, P2 - Within 3 years, P3 - Within 5 years, P4 - Within 6-10 years
-
Pictures