Interior Studs

  • Verify Stud size/gauge as shown on cold form framing structural drawings (CF series)

  • Verify Stud spacing per CF drawings

  • Verify integrity of studs (cut-outs, notches, kinks, bends are not acceptable)

  • Verify stud framing around door head/jamb

  • Verify stud walls are braced/kicked properly

  • Verify corner details per CF drawings

  • Verify installation of horizontal bracing

  • Verify Wall surface is in an even plane with no bowing or twisting studs

  • Verify framing at fire doors

  • Verify location of openings for fire hose cabinets, interior doors, interior windows, fire extinguishers

  • Steel door frame--verify stud connection at all anchor points

  • Firesafing and strapping at STC rated walls

  • Temp. screws pulled out at slip connections

  • No stud suspended from duct, pipe, conduit or their associated supports

  • Foam isolation strip between interior and exterior studs

Mechanical

  • Plumbing/Piping-Correct pipe sizes and locations

  • Plumbing/Piping-Verify pipe integrity--look for gaps, cuts, gouges, holes

  • Plumbing/Piping--copper pipe supported by plastic or lined with EPDM

  • Hangers--verify all connected to structure

  • Hangers-verify spacing

  • Hangers--pipes supported within 12" of 90 deg pipe bend

  • Hangers-verify support spacing at joints

  • Plumbing fixtures--verify rough-in quality and location

  • Plumbing/Piping--verify cleanout locations

  • Plumbing/Piping--verify floor penetrations are sealed

  • Plumbing/Piping--verify fire rated wall penetrations are installed per specifications

  • Plumbing/Piping--confirm all pipe has passed hydrostatic testing

  • Plumbing/Piping-city inspections performed and signed-off

  • HVAC--Correct duct sizes and locations

  • HVAC-Verify location and size of fire/smoke dampers

  • HVAC-Verify integrity of ducts and supports (cuts, bends, damage are unacceptable)

  • Insulation installed completely

  • Insulation--exposed ends covered in mastic

Electrical

  • Examine conduit for damage (crimping, improper bends, etc)

  • All conduit installed and wire pulled

  • Grommets for fire alarm provided

  • Conduit penetrations in floors are fire-caulked

  • Correct locations for Telecom/Data fixtures

  • Correct locations for outlets and switches

  • Correct size of electrical boxes

  • Support of electrical boxes sufficient

  • Verify rough-in for fire alarm

  • Verify locations of fire alarm devices

  • Verify conduit supported per specifications

  • Verify unused openings in junction boxes are plugged

Steel/Misc. Metals

  • Fireproofing at structural steel patched

  • Supports for vanities installed

  • Bottom track is clean

Backing/Blocking

  • Cabinets/Counter tops

  • Fire Extinguishers/Hose Cabinets

  • Toilet Accessories/Partitions

  • Handrail/Chair rail

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.