Title Page
-
Property/Site
-
Address
-
Assessed by
-
Conducted on
Legionnaires Risk Assessment Template
Cooling Tower System
-
Cooling Tower
-
Take a photo of the cooling tower, including its make, model, year of manufacture, and type.
The Written Scheme
-
Is there a written scheme for controlling the risk from exposure to legionella bacteria?
-
Does the scheme contain an up-to-date plan and instructions for operating the sytem?
-
Does the plan show all cooling towers, system control valves, and standby equipment, e.g. spare pumps?
-
Does the plan show the location of the system bleed valves and drain valve?
-
Does the plan show all associated storage tanks and pipework?
-
Does the plan show the location of chemical dosing points and/or injection points?
-
Does the plan show the origin of the water supply?
-
Does the plan show any parts that may be temporarily out of use?
-
Does the scheme contain details of the precautions to be taken to control the risk of exposure to legionella bacteria?
-
Does the scheme contain details of the checks that are to be carried out (and their frequency) to ensure that the scheme is effective?
-
Is there any tenant, resident or regular visitor particularly suscetible to legionella due to age, health or lifestyle?
Design & Construction
-
Are drift eliminators fitted correctly?
-
Are drift eliminators effective in reducing drift?
-
Are all visible surfaces free from slime or algae, scale, and corrosion?
-
Does the water flow evenly across the fill pack?
-
Have dead legs/blind ends and redundant pipework & plant been removed as far as possible?
-
Are those parts of the tower that become wet, accessible and/or removable for cleaning?
Operation & Maintenance
-
Is the cooling system in regular operation?
-
Are there procedures in place to operate standby equipment on a rotational basis?
-
Is there an operations manual for the cooling system?
-
If the tower is used intermittently or is required at short notice, is it run at least once a week, so that water treatment chemicals are circulated to all parts of the system?
-
If the tower is out of use for longer than a week, are there procedures in place to bring the tower back into operation safely?
Water Treatment Program
-
Is there a water treatment program in place?
-
Are chemicals/biocides used to control scale, corrosion, fouling, and microbiological activity?
-
List methods used below.
-
If non-oxidising biocides are used, are two used alternately?
-
Are chemicals dosed automatically?
-
Are the pumps calibrated regularly?
Monitoring
-
Is there a daily check to make sure that the system is operating as described in the operations manual?
-
Is there a daily visual check of the cleanliness of the water in the system?
-
Is the physical condition of the system checked at least every week?
-
Is the chemical composition of the cooling and make-up water monitored on a regular basis?
-
Are the safe operating limits for each parameter which is being measured, known and recorded in the operating manual?
-
Is the corrective action for out of limit situations known and included in the operations manual?
-
Are results of all tests and checks recorded, together with details of any remedial action taken (if required)?
-
Are dip slides taken on at least a weekly basis?
-
Are slides incubated in an incubator (at 30°C for 48 hours)?
-
Are results recorded, so trends over time can be seen?
-
Are samples for legionella taken on at least a quarterly basis?
-
Have the circumstances when more frequent sampling may be required been identified and recorded?
Cleaning & Disinfection
-
Is there a written procedure for regular cleaning and disinfection of the system?
-
Does this take place at least every six months?
-
If the system is not shut down every six months, list reasons and alternative measures taken to ensure the cleanliness of the system below.
-
Does the cleaning and disinfection procedure include the initial concentration of oxidizing biocide in use for the pre- and post-cleaning disinfection stages?
-
Does the cleaning and disinfection procedure include contact time for each disinfection stage and methods for carrying out cleaning, including the removal of packing?
-
If packs cannot be removed, are there alternative methods of making sure they remain clean in place?
-
List methods below.
-
Are measures taken to protect staff when carrying out cleaning of the tower?
-
List precautions below.
Sign Off
-
Additional Observations
-
Landlord Name & Signature
-
Legionella-Responsible Person Name & Signature