Title Page
-
Document No.
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
5th Floor
Evac Chair
-
Location : 5th Floor Staircase 1
-
Visual inspection?
Refuge Call Box
-
Location : 5th Floor Staircase 1
-
Visual inspection?
Fire Doors
-
Doors leading from Staircase 1 to 5th floor
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Bell
-
Location : 5th Floor corridor - above 5.01 door (Staircase 1 side)
-
Visual inspection?
Fire Call point : L2ADD90
-
Location : 5th Floor corridor - opposite 5.01 and near to Staircase 1
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (5)
-
Location : 5th Floor corridor - opposite 5.01 and near to Staircase 1
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (6)
-
Location : 5th Floor corridor - opposite 5.01 and near to Staircase 1
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Doors
-
Location : Midway down 5th floor corridor between 5.01 and 5.04
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point LP2ADD104
-
Location : 5th floor corridor next to 5.04 door (Staircase 2 side)
-
Does the call point appear undamaged with glass intact?
Fire Bell
-
Location : 5th floor corridor opposite 5.04 (Staircase 2 side)
-
Visual inspection?
Fire Doors
-
Location : 5th Floor from corridor to Staircase 2
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Foam Fire Extinguisher (4)
-
Location : 5th Floor staircase 2
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Extinguisher still within service period?
-
Is there an information leaflet next to extinguisher?
Co2 Fire Extinguisher (3)
-
Location : 5th Floor staircase 2
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Call point : LP2ADD99
-
Location : 5th Floor staircase 2
-
Does the call point appear undamaged with glass intact?
Evac Chair
-
Location : 5th Floor staircase 2
-
Visual inspection?
Refuge Call Box
-
Location : 5th Floor staircase 2
-
Visual inspection?
Other Comments for 5th Floor
-
Include details of any observations or recommendations for this floor (i.e obstructions, fire hazards or missing fire signage)
4th Floor
Refuge Call Box
-
Location : 4th Floor Staircase 2
-
Visual inspection?
Fire Call point LP2ADD88
-
Location : 4th Floor Staircase 2
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (10)
-
Location : 4th Floor Staircase 2
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (9)
-
Location : 4th Floor Staircase 2
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Doors
-
Location : 4th floor from staircase 2 to classroom corridor
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point LP2ADD85
-
Location : 4th floor classroom corridor, near 4.03
-
Does the call point appear undamaged with glass intact?
Fire Bell
-
Location : 4th floor classroom corridor, near 4.03
-
Visual inspection?
Fire Doors
-
Location : 4th floor classroom corridor between 4.03 and 4.04
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Bell
-
Location : 4th floor corridor near 4.01A
-
Visual inspection?
Fire Call point (No Code)
-
Location : 4th floor classroom corridor, next to 4.05
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (7)
-
Location : 4th floor classroom corridor, next to 4.05
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (8)
-
Location : 4th floor classroom corridor, next to 4.05
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Doors
-
Location : From 4th floor corridor onto staircase 1
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Evac Chair
-
Location : 4th Floor Staircase 1
-
Visual inspection?
Refuge Call Box
-
Location : 4th Floor Staircase 1
-
Visual inspection?
Fire Call point LPADD78
-
Location : 4th Floor Staircase 1
-
Does the call point appear undamaged with glass intact?
Fire Bell
-
Location : 4th Floor Staircase 1
-
Visual inspection?
Other Comments for 4th Floor
-
Include details of any observations or recommendations for this floor (i.e obstructions, fire hazards or missing fire signage)
3rd Floor
Fire Call point LP2ADD63
-
Location : 3rd Floor Staircase 1
-
Does the call point appear undamaged with glass intact?
Fire Bell
-
Location : 3rd Floor Staircase 1
-
Visual inspection?
Refuge Call Box
-
Location : 3rd Floor Staircase 1
-
Visual inspection?
Fire Doors
-
Location : Third floor from Staircase 1 to classroom corridor
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point LP2ADD65
-
Location : 3rd Floor Corridor, next to Home Environment Room
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (26)
-
Location : 3rd Floor Corridor, next to Home Environment Room
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (25)
-
Location : 3rd Floor Corridor, next to Home Environment Room
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Bell
-
Location : 3rd Floor Corridor, above Shower room
-
Visual inspection?
Fire Doors
-
Location : 3rd Floor classroom corridor, midway between 3.20 and 3.19
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Bell
-
Location : 3rd Floor Corridor, in counselling room corridor
-
Visual inspection?
Fire Bell
-
Location : 3rd Floor Corridor, near 3.18
-
Visual inspection?
Fire Doors
-
Location : 3rd Floor corridor between 3.18 and lift by staircase 2
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point LP2ADD76
-
Location : 3rd Floor Corridor, by entrance to Staircase 2
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (22)
-
Location : 3rd Floor Corridor, by entrance to Staircase 2
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (21)
-
Location : 3rd Floor Corridor, by entrance to Staircase 2
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Bell
-
Location : 3rd Floor Corridor, by entrance to Staircase 2
-
Visual inspection?
Fire Doors
-
Location : 3rd Floor to Staircase 2 from lift area
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point LP2ADD72
-
Location : 3rd Floor Staircase 2
-
Does the call point appear undamaged with glass intact?
Refuge Call Box
-
Location : 3rd Floor Staircase 2
-
Visual inspection?
Evac Chair
-
Location : 3rd Floor Staircase 2
-
Visual inspection?
Fire Bell
-
Location : 3rd Floor Staircase 2
-
Visual inspection?
Fire Doors
-
Location : 3rd Floor corridor next to Medical Stockroom
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Doors
-
Location : 3rd Floor corridor onto Staircase 3, Practice Suite 1 side
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point LP1ADD83
-
Location : 3rd Floor Staircase 3
-
Does the call point appear undamaged with glass intact?
Refuge Call Box
-
Location : 3rd Floor Staircase 3
-
Visual inspection?
Fire Bell
-
Location : 3rd Floor Staircase 3
-
Visual inspection?
Fire Doors
-
Location : 3rd Floor corridor from Staircase 3, Practice Suite 2 side
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Foam Fire Extinguisher (13)
-
Location : Third floor corridor opposite Practice Suite 2
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (14)
-
Location : Third floor corridor opposite Practice Suite 3
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Call point LP1ADD71
-
Location : Third floor corridor opposite Practice Suite 3
-
Does the call point appear undamaged with glass intact?
Push Bar Emergency Exit
-
Location : Third floor corridor opposite Practice Suite 3, going onto external fire escape
-
Push bar in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Comment on any damage :
Other Comments : Third Floor
-
Include details of any observations or recommendations for this floor (i.e obstructions, fire hazards or missing fire signage)
2nd Floor
Fire Bell
-
Location : 2nd Floor corridor, opposite 2.07
-
Visual inspection?
Foam Fire Extinguisher (32)
-
Location : 2nd Floor corridor, opposite 2.03
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Call point (LP1ADD53)
-
Location : 2nd Floor corridor, opposite 2.03
-
Does the call point appear undamaged with glass intact?
Push Bar Emergency Exit
-
Location : 2nd floor corridor opposite 2.03, going onto external fire escape
-
Push bar in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Comment on any damage :
Fire Bell
-
Location : 2nd Floor corridor, opposite 2.02
-
Visual inspection?
Fire Doors
-
Location : 2nd Floor, onto Staircase 3 (2.01 side)
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Evac Chair
-
Location : 2nd Floor, Staircase 3
-
Visual inspection?
Refuge Call Box
-
Location : 2nd Floor, Staircase 3
-
Visual inspection?
Fire Call point (LD1ADD84)
-
Location : 2nd Floor, Staircase 3
-
Does the call point appear undamaged with glass intact?
Fire Doors
-
Location : 2nd Floor, onto Staircase 3 (2.24 side)
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Bell
-
Location : 2nd Floor, Corridor opposite 2.23
-
Visual inspection?
Foam Fire Extinguisher (31)
-
Location : 2nd Floor, Corridor opposite 2.23
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (79)
-
Location : 2nd Floor, Corridor opposite 2.23
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Doors
-
Location : 2nd Floor, Opposite 2.24 going towards Staircase 2
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Bell
-
Location : 2nd Floor, by entry to Staircase 2
-
Visual inspection?
Fire Call point (L4ADD61)
-
Location : 2nd Floor, by entry to Staircase 2
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (30)
-
Location : 2nd Floor, by entry to Staircase 2
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (29)
-
Location : 2nd Floor, by entry to Staircase 2
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Doors
-
Location : 2nd Floor, entrance to Staircase 2 from lift area
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point (LP2ADD59)
-
Location : 2nd Floor, Staircase 2
-
Does the call point appear undamaged with glass intact?
Refuge Call Box
-
Location : 2nd Floor, Staircase 2
-
Visual inspection?
Fire Doors
-
Location : 2nd Floor, near lift area going towards 2.15
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Bell
-
Location : 2nd Floor corridor above 2.20
-
Visual inspection?
Fire Doors
-
Location : 2nd Floor corridor between 2.15 and 2.16
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Bell
-
Location : 2nd Floor corridor between 2.16 & 2.17
-
Visual inspection?
Fire Call point (L4/Z30/51)
-
Location : 2nd Floor corridor next to 2.17, by Staircase 1
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (28)
-
Location : 2nd Floor corridor next to 2.17, by Staircase 1
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (27)
-
Location : 2nd Floor corridor next to 2.17, by Staircase 1
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Bell
-
Location : 2nd Floor corridor above toilets, near Staircase 1
-
Visual inspection?
Fire Doors
-
Location : 2nd Floor entry to Staircase 1
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Evac Chair
-
Location : 2nd Floor, Staircase 1
-
Visual inspection?
Refuge Call Box
-
Location : 2nd Floor, Staircase 1
-
Visual inspection?
Fire Call point (LP2ADD49)
-
Location : 2nd Floor, Staircase 1
-
Does the call point appear undamaged with glass intact?
Other Comments : Second Floor
-
Include details of any observations or recommendations for this floor (i.e obstructions, fire hazards or missing fire signage)
1st Floor
Refuge Call Box
-
Location : 1st Floor, Staircase 1
-
Visual inspection?
Fire Call point (LP2ADD30)
-
Location : 1st Floor, Staircase 1
-
Does the call point appear undamaged with glass intact?
Card Read Lock - Not activated
-
Location : 1st Floor, outside admin office (Staircase 1 end)
-
Visual inspection?
Fire Doors
-
Location : 1st Floor entrance to Admin office (Staircase 1 end)
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point (LP4/228/38)
-
Location : 1st Floor, In the Admin office, next to rear Exit to Staircase 1)
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (46)
-
Location : 1st Floor, In the Admin office, next to rear Exit to Staircase 1
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (45)
-
Location : 1st Floor, In the Admin office, next to rear Exit to Staircase 1
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Bell
-
Location : 1st Floor, In the Admin office, next to rear Exit to Staircase 1
-
Visual inspection?
Green Door Release Box
-
Location : 1st Floor, In the Admin office, next to rear Exit to Staircase 1
-
Visual inspection?
Fire Bell
-
Location : 1st Floor, In the Admin office, next to exit to Staircase 2
-
Visual inspection?
Green Door Release Box
-
Location : 1st Floor, In the Admin office, next to exit to Staircase 2
-
Visual inspection?
Fire Doors
-
Location : 1st Floor entrance to Admin office (Staircase 2 end)
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Card Read Lock
-
Location : 1st Floor, outside admin office (Staircase 2 end)
-
Visual inspection?
Fire Call point (LP4/Z28/15)
-
Location : 1st Floor corridor, near Staircase 2
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (44)
-
Location : 1st Floor corridor, near Staircase 2
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (43)
-
Location : 1st Floor corridor, near Staircase 2
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Bell
-
Location : 1st Floor corridor, near Staircase 2
-
Visual inspection?
Fire Doors
-
Location : 1st Floor corridor, entrance to Staircase 2
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Evac Chair
-
Location : 1st Floor, Staircase 2
-
Visual inspection?
Refuge Call Box
-
Location : 1st Floor, Staircase 2
-
Visual inspection?
Fire Call point (LP2ADD45)
-
Location : 1st Floor, Staircase 2
-
Does the call point appear undamaged with glass intact?
Fire Doors
-
Location : 1st Floor door into reception area (From Staircase 2 direction)
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Bell
-
Location : 1st Floor reception area, above 1.12 Dementia lab
-
Visual inspection?
Fire Call point (LP1ADD86)
-
Location : 1st Floor, Staircase 3
-
Does the call point appear undamaged with glass intact?
Fire Bell
-
Location : 1st Floor reception area, on pilar opposite lift
-
Visual inspection?
Foam Fire Extinguisher (42)
-
Location : 1st Floor reception area
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (41)
-
Location : 1st Floor reception area
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Doors
-
Location : 1st Floor reception exit towards 1.03
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point (No Code)
-
Location : 1st floor corridor between reception and 1.03
-
Does the call point appear undamaged with glass intact?
Push Bar Emergency Exit
-
Location : 1st floor corridor between reception and 1.03, leading onto external fire escape
-
Push bar in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Comment on any damage :
Other Comments : 1st Floor
-
Include details of any observations or recommendations for this floor (i.e obstructions, fire hazards or missing fire signage)
Ground Floor
Fire Call point (LP1ADD31)
-
Location : Ground floor, Next to Electric Fire Door Exit
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (63)
-
Location : Ground floor, Next to Electric Fire Door Exit
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Green Door Release Box
-
Location : Ground floor, Next to Electric Fire Door Exit
-
Visual inspection?
Fire Doors
-
Location : Ground Floor, next to lift by Staircase 3
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Foam Fire Extinguisher (64)
-
Location : Ground floor, Bottom of Staircase 3
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Doors
-
Location : Ground floor, by Fire Alarm Panel walking towards Lift and canteen
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Green Door Release Box
-
Location : Ground floor, opposite lift by Staircase 2
-
Visual inspection?
Fire Doors
-
Location : Ground floor, by Lift heading towards Staircase 2
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Doors
-
Location : Ground floor, onto Staircase 2
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Electric Fire Door Exit (Push button operated)
-
Location : Ground floor, exit to small car park from Staircase 2
-
Push bar in good working order?
-
Hinges in good working order?
-
Comment on any damage :
Green Door Release Box
-
Location : Ground floor, exit to small car park from Staircase 2
-
Visual inspection?
Fire Call point (LP1ADD29)
-
Location : Ground floor, exit to small car park from Staircase 2
-
Does the call point appear undamaged with glass intact?
Foam Fire Extinguisher (51)
-
Location : Ground floor, Canteen, opposite vending machines
-
Is the extinguisher present and secured in place?
-
Is the pressure ok?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Co2 Fire Extinguisher (78)
-
Location : Ground floor, Canteen, next to vending machines
-
Is the extinguisher present and secured in place?
-
Is the tag in place?
-
Is there an information leaflet next to extinguisher?
-
Extinguisher still within service period?
Fire Call point (LP3ADD14)
-
Location : Ground floor, Canteen, close to vending machines
-
Does the call point appear undamaged with glass intact?
Fire Call point (NO CODE)
-
Location : Ground floor, Canteen, near large doors out to garden area
-
Does the call point appear undamaged with glass intact?
Green Door Release Box
-
Location : Ground Floor, in Canteen close to Staircase 1 exit
-
Visual inspection?
Fire Doors
-
Location : Ground floor, rear canteen entrance
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Doors
-
Location : Ground floor, onto Staircase 1
-
Handles in good working order?
-
Hinges in good working order?
-
Glass - visible inspection
-
Auto shutter - do both doors self close without any issues?<br>
-
Comment on any damage :
Fire Call point (LP3ADD19)
-
Location : Ground floor, bottom of Staircase 1
-
Does the call point appear undamaged with glass intact?
Green Door Release Box
-
Location : Ground floor, bottom of Staircase 1
-
Visual inspection?
Electric Fire Door Exit (Push button operated)
-
Location : Ground floor, bottom of Staircase 1, exit to Car Park
-
Push bar in good working order?
-
Hinges in good working order?
-
Comment on any damage :
Other Comments : Ground Floor
-
Include details of any observations or recommendations for this floor (i.e obstructions, fire hazards or missing fire signage)