Title Page

  • Site conducted

  • Conducted on

  • Shift

  • Engineer

  • Prepared by

  • Location

UTC 1

  • Normal Power

  • MD A1 MB

  • MD A1 DGSA

  • MD A1 TIE

  • Alarms

UTC 2

  • Normal Power

  • MD B1 TIE

  • MD B1 DGSA

  • MD A1 MB

  • Alarms

MD A1 & MO B1 Control Status

  • MD A1 Retransfer

  • MD A1 Load Test

  • MD B1 Retransfer

  • MD B1 Load Test

  • Active Alarms

Touch Screens

  • EPMS and SCADA

Master Status

  • Master Control

  • Gen Demand Mode

  • Load Control

  • Transition Mode

  • Bus Config

  • First Line

No Load Test

  • Critical Load Bypass

  • UPS Bypass

  • SUB A

  • SUB B

  • Load Bank Test

  • Load Shed

Master Control

  • DGSA Tie

  • PLC 1 in control

  • GCA in control

  • Utility First Line of Defense

  • Alarms

DGSA

Gen 1

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 2

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 3

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 4

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 5

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 6

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 7

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 8

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

MD-A1

  • Status

  • Alarm

  • Bypass B1

  • Bypass B22?

  • MD-A1 MIB

  • CS-IA

  • CS-2A

  • MD-A1 SW-1

  • MS-1A

  • MS-2A

  • AC-Volts

  • MLB

  • AC-AMPS

  • Gen Main

  • mW

  • Tie

  • Alarms

  • MD-A2

  • EMPS Touch Screen

  • EMPS Touch Screen Working

MD-B1

  • Status

  • Alarm

  • Bypass B1

  • Bypass A2

  • MD-B1 MIB

  • CS-IB

  • CS-2B

  • MD-B1 SW-1

  • MS-1B

  • MS-2B

  • AC-Volts

  • MLB

  • AC-AMPS

  • Gen Main

  • mW

  • Tie

  • Alarms

  • MD-B2

  • EMPS Touch Screen

  • EMPS Touch Screen Working

SUB A

  • Status

  • Alarm

Sub B

  • Status

  • Alarm

MLB

  • Status

  • Alarm

Tie

  • Status

  • Alarm

Electrical Closet W148 MD A1 MIB

  • "A" Battery Charging Station DC Volts

  • "A" Battery Charging Station DC Amps

  • "A" Battery Charging Station Alarms

  • "B" Battery Charging Station DC Volts

  • "B" Battery Charging Station DC Amps

  • "B" Battery Charging Station Alarms

MD-A2

  • M8-3A

  • M8-4A

  • MA-5A

  • C8-3A

  • C8-4A

  • C8-5A

  • EPMS Touch Screen

  • EPMS Touch Screen Working

MD-B2

  • M8-3B

  • M8-4B

  • MA-5B

  • C8-3B

  • C8-4B

  • C8-5B

  • EPMS Touch Screen

  • EPMS Touch Screen Working

Generator Plant

Generators

  • Equipment Designation

DGSA

Gen 1

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 2

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 3

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 4

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 5

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 6

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

Gen 7

  • Equipment Designation

  • Status

  • Hour Meter

  • Alarms

  • Controls

  • Engine Temp

  • DC Volts

  • Alarms

  • Oil Tank Level

  • Front Jacket hester

  • Rear Jacket hester

  • A Distribution Breaker

Generator Battery Charges

Gen 1

  • DC Volts

  • DC Amps

  • Alarms

  • DC-Volts

  • DC-Amps

  • Alarms

  • ATS 1 & 2 Source

  • ATS 1 & 2 Alarms

  • ATS 3 & 4 Source

  • ATS 3 & 4 Alarms

Gen 2

  • DC Volts

  • DC Amps

  • Alarms

  • DC-Volts

  • DC-Amps

  • Alarms

  • ATS 1 & 2 Source

  • ATS 1 & 2 Alarms

  • ATS 3 & 4 Source

  • ATS 3 & 4 Alarms

Gen 3

  • DC Volts

  • DC Amps

  • Alarms

  • DC-Volts

  • DC-Amps

  • Alarms

  • ATS 1 & 2 Source

  • ATS 1 & 2 Alarms

  • ATS 3 & 4 Source

  • ATS 3 & 4 Alarms

Gen 4

  • DC Volts

  • DC Amps

  • Alarms

  • DC-Volts

  • DC-Amps

  • Alarms

  • ATS 1 & 2 Source

  • ATS 1 & 2 Alarms

  • ATS 3 & 4 Source

  • ATS 3 & 4 Alarms

Gen 5

  • DC Volts

  • DC Amps

  • Alarms

  • DC-Volts

  • DC-Amps

  • Alarms

  • ATS 5 & 6 Source

  • ATS 5 & 6 Alarms

  • ATS 7 & 8 Source

  • ATS 7 & 8 Alarms

Gen 6

  • DC Volts

  • DC Amps

  • Alarms

  • DC-Volts

  • DC-Amps

  • Alarms

  • ATS 5 & 6 Source

  • ATS 5 & 6 Alarms

  • ATS 7 & 8 Source

  • ATS 7 & 8 Alarms

Gen 7

  • DC Volts

  • DC Amps

  • Alarms

  • DC-Volts

  • DC-Amps

  • Alarms

  • ATS 5 & 6 Source

  • ATS 5 & 6 Alarms

  • ATS 7 & 8 Source

  • ATS 7 & 8 Alarms

Gen 8

  • DC Volts

  • DC Amps

  • Alarms

  • DC-Volts

  • DC-Amps

  • Alarms

  • ATS 5 & 6 Source

  • ATS 5 & 6 Alarms

  • ATS 7 & 8 Source

  • ATS 7 & 8 Alarms

Fuel Oil System

  • Tank Selection

  • FO Tank 1 Level

  • FO Tank 1 Fuel Level

  • FO Tank 1 Alarms

  • FO Tank 2 Level

  • FO Tank 2 Low Fuel

  • FO Tank 2 Alarms

  • Total Fuel

  • FOP - 1 Controls

  • FOP - 1 Alarms

  • FOP - 2 Controls

  • FOP - 2 Alarms

  • FOP - 3 Controls

  • FOP- 3 Alarms

  • FOP - 4 Controls

  • FOP - 4 Alarms

  • Fuel Polisher Controls

  • Fuel Polisher Alarms

Day Tanks

Day Tank 1

  • Day Tank 1 Source

  • Day Tank 1 Level -%

  • Day Tank 1 Alarms

Day Tank 2

  • Day Tank 2 Source

  • Day Tank 2 Level -%

  • Day Tank 2 Alarms

Day Tank 3

  • Day Tank 3 Source

  • Day Tank 3 Level -%

  • Day Tank 3 Alarms

Day Tank 4

  • Day Tank 4 Source

  • Day Tank 4 Level -%

  • Day Tank 4 Alarms

Day Tank 5

  • Day Tank 5 Source

  • Day Tank 5 Level -%

  • Day Tank 5 Alarms

Day Tank 6

  • Day Tank 6 Source

  • Day Tank 6 Level -%

  • Day Tank 6 Alarms

Day Tank 7

  • Day Tank 7 Source

  • Day Tank 7 Level -%

  • Day Tank 7 Alarms

Day Tank 8

  • Day Tank 8 Source

  • Day Tank 8 Level -%

  • Day Tank 8 Alarms

MLB

  • MLB Primary

  • MLB Alternate

  • AC Volts

  • AC Amps

  • kW

  • Alarms

  • MLBA - M Main

  • MLBA - 1 UPS 3B,4B,5B

  • MLBA - 2 UPS 3A,4A,5A

  • MLBA - 3 UPS 3B,4B,5B

  • MLBA - 4 UPS 1A, 2A

  • MLBA - T Tie

  • MLBA - 5 Spare

  • MLBA - 6 UPS 1&2 Load Test

  • MLBA - 7 UPS 3,4 & 5 Load Test

  • MLBA - 8 Load Bank

  • CRH1- 21

  • Preferred Source

  • Discharge F

  • Alarms

  • CRH2- 22

  • Preferred Source

  • Discharge F

  • Alarms

  • Access Center/ATS

  • Alarms

Mechanical Substations

Mech A MS-1A & MS-2A

MVTS - MS-1A

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

MVTS - MS-2A

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

MS - 1A

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

MS - 2A

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

EPMS Touch Screens

  • Source

  • Off / On Status

  • Working

CRAH - 1-17

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CRAH - 1-18

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

PDU BMA

  • Source

  • Alarms

Mech B MS - 1B MS - 2B

MVTS MV 1B

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

MVTS MV 2B

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

MS 1B

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

MS - 2B

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

EPMS Touch Screen

  • Status

  • Working

CRAH - 1-19

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CRAH - 1-20

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

PDU BMA

  • Source

  • Alarms

Meet Me Room E-145

CRAH - 1-41

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CRAH - 1-42

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

PDU CS A

  • Alarms

PDU CS B

  • Alarms

MS 3 A

MVTS MS 3A

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

  • Touch Screen

  • Working

MS - 3A

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

CRAH - 1-37

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CRAH - 1-39

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

MS 3 B

MVTS MS 3B

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

  • Touch Screen

  • Working

MS - 3B

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

EPMS Touch Screen

  • Status

  • Working

CRAH - 1-38

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CRAH - 1-40

  • On/Off

  • Preferred Source

  • Temp

Meet Me Room E-180

CRAH - 1-43

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CRAH - 1-44

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

PDU CN-A

  • Alarms

PDU CN-B

  • Alarms

Mech Rm 4A W170

MVTS MS 4A

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

MVTS MS 5A

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

CS 4A

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

CS 4A

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

CRAH - 1-45

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CRAH - 1-46

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

EPMS Touch Screen

  • Status

  • working

Mech Rm E112

MVTS CS 4B

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

  • Touch Screen

  • Working

MVTS MS 5B

  • MVTS MS 4B

  • Primary

  • Alternate

  • System Test

  • Local/ Remote

  • Retransfer

  • TD 1

  • TD 2

  • TD 3

  • Volts

  • Amps

  • kW

  • Alarms

  • Touch Screen

  • Working

CS 4B

  • Main

  • Tie

  • AC Amps

  • AC Volts

  • kW

  • Alarms

MS -4B

  • Main

  • Tie

  • AC Volts

  • AC Amps

  • kW

  • Alarms

CRAH - 1-47

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CRAH - 1-48

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

EPMS Touch Screen

  • Status

  • Working

Load Bank Room W172 / Load Bank

  • UPS- 4A

  • UPS - 4B

  • UPS- 4A Future

  • UPS- 4B Future

Chiller Plant A

MCC A 1

  • PCHWP #1 On /Off

  • PCHWP #1 Frequency

  • PCHWP #1 Amps

  • PCHWP #1 kW

  • PCHWP #1 Alarms

  • CWP #1 On /Off

  • CWP #1 Frequency

  • CWP #1 Amps

  • CWP #1 kW

  • CWP #1 Alarms

  • SCHWP #1 On /Off

  • SCHWP #1 Frequency

  • SCHWP #1 Amps

  • SCHWP #1 kW

  • SCHWP #1 Alarms

  • CT FAN #1-1 On /Off

  • CT FAN #1-1 #1 Frequency

  • CT FAN #1-1 Amps

  • CT FAN #1-1 kW

  • CT FAN #1-1 Alarms

  • CT FAN #1-2 On /Off

  • CT FAN #1-2 #1 Frequency

  • CT FAN #1-2 Amps

  • CT FAN #1-2 kW

  • CT FAN #1-2 Alarms

Chiller WCC #1

  • WCC #1

  • WCC #1 Load %

  • WCC #1 In Put kW

  • WCC #1 CHWS

  • WCC #1 Alarms

One Line Equipment System Line ups

  • Towers 1,2,3.4.5

  • Chillers1,2,3,4,5

  • SCHWPs 1,2,3,4,5

MCC A 2

  • PCHWP #2 On /Off

  • PCHWP #2 Frequency

  • PCHWP #2 Amps

  • PCHWP #2 kW

  • PCHWP #2 Alarms

  • CWP #2 On /Off

  • CWP #2 Frequency

  • CWP #2 Amps

  • CWP #2 kW

  • CWP #2 Alarms

  • SCHWP #2 On /Off

  • SCHWP #2 Frequency

  • SCHWP #2 Amps

  • SCHWP #2 kW

  • SCHWP #2 Alarms

  • CT FAN # 2-1 On /Off

  • CT FAN #2-1 #1 Frequency

  • CT FAN #2-1 Amps

  • CT FAN #2-1 kW

  • CT FAN #2-1 Alarms

  • CT FAN #2-2 On /Off

  • CT FAN #2-2 #1 Frequency

  • CT FAN #2-2 Amps

  • CT FAN #2-2 kW

  • CT FAN #2-2 Alarms

Chiller WCC #2

  • WCC #2

  • WCC #2 Load %

  • WCC #2 In Put kW

  • WCC #2 CHWS

  • WCC #2 Alarms

Water Meters

  • M/U East

  • M/U West

  • South Irrigation

MCC A 3

  • PCHWP #3 On /Off

  • PCHWP #3 Frequency

  • PCHWP #3 Amps

  • PCHWP #3 kW

  • PCHWP #3 Alarms

  • CWP #3 On /Off

  • CWP #3 Frequency

  • CWP #3 Amps

  • CWP #3 kW

  • CWP #3 Alarms

  • SCHWP #3 On /Off

  • SCHWP #3 Frequency

  • SCHWP #3 Amps

  • SCHWP #3 kW

  • SCHWP #3 Alarms

  • CT FAN # 3-1 On /Off

  • CT FAN #3-1 #1 Frequency

  • CT FAN #3-1 Amps

  • CT FAN #3-1 kW

  • CT FAN #3-1 Alarms

  • CT FAN #3-2 On /Off

  • CT FAN #3-2 #1 Frequency

  • CT FAN #3-2 Amps

  • CT FAN #3-2 kW

  • CT FAN #3-2 Alarms

Chiller WCC #3

  • WCC #3

  • WCC #3 Load %

  • WCC #3 In Put kW

  • WCC #3 CHWS

  • WCC #3 Alarms

Sand ? System

  • System Status

  • Blowdown Meter

  • BW Counter

  • Alarms

MCC A 4

  • PCHWP #4 On /Off

  • PCHWP #4 Frequency

  • PCHWP #4 Amps

  • PCHWP #4 kW

  • PCHWP #4 Alarms

  • CWP #4 On /Off

  • CWP #4 Frequency

  • CWP #4 Amps

  • CWP #4 kW

  • CWP #4 Alarms

  • SCHWP #4 On /Off

  • SCHWP #4 Frequency

  • SCHWP #4 Amps

  • SCHWP #4 kW

  • SCHWP #4 Alarms

  • CT FAN #4-1 On /Off

  • CT FAN #4-1 #1 Frequency

  • CT FAN #4-1 Amps

  • CT FAN #4-1 kW

  • CT FAN #4-1 Alarms

  • CT FAN #4-2 On /Off

  • CT FAN #4-2 #1 Frequency

  • CT FAN #4-2 Amps

  • CT FAN #4-2 kW

  • CT FAN #4-2 Alarms

Chiller WCC #4

  • WCC #4

  • WCC #4 Load %

  • WCC #4 In Put kW

  • WCC #4 CHWS

  • WCC #4 Alarms

Air Compressor

  • Main Compressor

  • Control

  • Main Dryer

  • Main PSI

  • Control PSI

  • Primary Cooling Tower Blowdown

  • Back up Cooling Tower Blowdown

  • Air Compression #1-1

  • Control

  • Main Dryer

  • Main PSI

  • Control PSI

  • Filter

  • Dryer

  • Primary Cooling Tower Blowdown

  • Back up Cooling Tower Blowdown

  • Air Compression #1-2

  • Control

  • Main Dryer

  • Main PSI

  • Control PSI

  • Filter

  • Dryer

  • Primary Cooling Tower Blowdown

  • Back up Cooling Tower Blowdown

Sand Fillers

CHW / Sand Filter A6

  • On/Off

  • Inlet #

  • Outlet #

  • Access Center Domestic

  • Access Center Domestic Fire

CHW / Sand Filter A1

  • On/Off

  • Inlet #

  • Outlet #

  • CPW 1 Heater 1

  • CPW 1 Heater 2

  • Access Center Domestic

  • Access Center Domestic Fire

CHW / Sand Filter A2

  • On/Off

  • Inlet #

  • Outlet #

  • CPW 2 Heater 1

  • CPW 2 Heater 2

  • Access Center Domestic

  • Access Center Domestic Fire

CHW / Sand Filter A3

  • On/Off

  • Inlet #

  • Outlet #

  • CPW 3 Heater 1

  • CPW 3 Heater 2

  • Access Center Domestic

  • Access Center Domestic Fire

CHW / Sand Filter A4

  • On/Off

  • Inlet #

  • Outlet #

  • CPW 4 Heater 1

  • CPW 4 Heater 2

  • Access Center Domestic

  • Access Center Domestic Fire

CHW / Sand Filter A5

  • On/Off

  • Inlet #

  • Outlet #

  • CPW 5 Heater 1

  • CPW 5 Heater 2

  • Access Center Domestic

  • Access Center Domestic Fire

Plant EPMS Touch Screen

  • Status

  • Working

Heat Trace Panels Tower A Panel

  • Power Available

  • Breaker Trip

  • Control

  • Energized

Building Rounds

CS1A

  • Specify UPS

  • Status

  • Veb

  • Vbc

  • Vca

  • la

  • lb

  • Batt V

  • Batt A

  • kW

  • kVA

MVTS

  • Primary

  • Vavg

  • IAVg

  • kW

  • Control

  • Re-TXFR

  • System Test

  • Alarm

  • Alternate

  • Vavg

  • IAVg

  • kW

  • Control

  • Re-TXFR

  • System Test

  • Alarm

  • TD 1 (90s)

  • TD 2 (300s)

  • TD 3 (15a)

CM 4000

  • CS1A

  • Vavg

  • IAVg

  • kW

  • Alarms

  • SCC 1A

  • Vavg

  • IAVg

  • kW

  • Alarms

  • CRAH
  • Specify

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

CS1B

  • Specify UPS

  • Status

  • Veb

  • Vbc

  • Vca

  • la

  • lb

  • Batt V

  • Batt A

  • kW

  • kVA

MVTS

  • Primary

  • Vavg

  • IAVg

  • kW

  • Control

  • Re-TXFR

  • System Test

  • Alarm

  • Alternate

  • Vavg

  • IAVg

  • kW

  • Control

  • Re-TXFR

  • System Test

  • Alarm

  • TD 1 (90s)

  • TD 2 (300s)

  • TD 3 (15a)

CM 4000

  • CS1A

  • Vavg

  • IAVg

  • kW

  • Alarms

  • SCC 1A

  • Vavg

  • IAVg

  • kW

  • Alarms

  • CRAH
  • Specify

  • On/Off

  • Preferred Source

  • Temp

  • Alarms

Fire Alarm Equipment

Corridor E133

  • Global PMI (Node14)

  • Alarm

  • Supervisory

  • Trouble

  • Mimic Screen

  • On/Off

  • Working

Fire Pump Room E193

  • Diesel Fire Pump

  • Control

  • Power

  • System Pressure

  • Jacket heater

  • Alarm

  • Trouble

  • Fuel Level

  • Jockey Jump

  • Power

  • Pressure

  • Fire System Meter

Sprinkler System Pre Action Room 192

Wet System 2

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Wet System 6

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Wet System 16

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Wet System 19

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Wet System 20

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Wet System 21

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Wet System 22

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Sprinkler System Pre Action Room W161

Wet System 5

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Dry Pipe 1

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 12

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 15

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 14

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 18

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 17

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Sprinkler System Pre Action Room W152

Wet System 4

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 3

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 6

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 9

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 2

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 8

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Sprinkler System Pre Action Room E143

Wet System 3

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action10

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 5

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 1

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 4

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 7

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 11

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Pre Action 13

  • Supply/Valve

  • Diaphragm

  • System Air

  • Water

  • Air Compressor

  • Dryer

Nitrogen Generator

  • Power

  • Hours

  • System Normal

  • System Bypassed

  • Alarm

1st Floor AHU Equipment

AHU "B"

AHU - 4

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

RF 1-2

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

AHU - 3A

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

AHU - 3B

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

End Suction Pump #6

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

End Suction Pump #7

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

Daily Readings

  • M #09060704 High Flow

  • M #09060704 High Flow

  • North Irrigation Meter

AHU "A"

AHU - A1

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

AHU 2

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

RF 1-1

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

AHU - 1A

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

AHU - 1B

  • On/Off

  • Frequency

  • Amps

  • Supply Temperature

  • Return Temperature

  • Alarms

Tempered Water Heater

  • On/Off

  • Supply Temperature

  • Tempered Water Heater

  • Mixed Temperature

  • Alarms

POD 1 & 2 Battery Rooms

Battery Charger 1A

  • Volts

  • Amps

  • Temperature

  • Alarm

Battery Charger 1B

  • Volts

  • Amps

  • Temperature

  • Alarm

Battery Charger 2A

  • Volts

  • Amps

  • Temperature

  • Alarm

Battery Charger 2B

  • Volts

  • Amps

  • Temperature

  • Alarm

Eye Wash

  • Eye Wash 1A Alarm

  • Eye Wash 1B Alarm

  • Eye Wash 2A Alarm

  • Eye Wash 2B Alarm

POD 1&2 Battery Room Exhaust Fans

EF 1-1

  • On/Off

  • Hand/Off/Auto

  • Alarms

EF 1-2

  • On/Off

  • Hand/Off/Auto

  • Alarms

EF 1-3

  • On/Off

  • Hand/Off/Auto

  • Alarms

POD 3 Battery Room

Battery Charger 3A

  • Volts

  • Amps

  • Temperature

  • Alarms

  • Eye Wash 3A

Battery Charger 3B

  • Volts

  • Amps

  • Temperature

  • Alarms

  • Eye Wash 3B

POD 3 Battery Room Exhaust Fans (W161)

EF 1-8

  • On/Off

  • Hand/Off/Auto

  • Alarms

EF 1-9

  • On/Off

  • Hand/Off/Auto

  • Alarms

Tempered Water Heater

  • On/Off

  • Supply Temperature

  • Mixed Temperature

  • Alarms

PV Inverter Room (W168)

PV 1

  • On/Off

  • Power

  • Day

  • Total

  • Alarms

PV 2

  • On/Off

  • Power

  • Day

  • Total

  • Alarms

CRAH 1-28

  • On/Off

  • Temp

  • Alarms

Lobby Screens (W179)

  • Noveda Systems

  • Working

  • Scale Slide Show Screen

  • Working

MPOE & 2nd Floor Equipment

MPOE North

  • PDU-MPOE-N-A Source

  • PDU-MPOE-N-A Alarm

  • PDU-MPOE-N-B Source

  • PDU-MPOE-N-B Alarm

  • RPP-MPOE-N-A

  • RPP-MPOE-N-B

CRAH 1-163

  • Status

  • Preferred Source

  • Discharge F

  • Alarms

CRAH 1-164

  • Status

  • Preferred Source

  • Discharge F

  • Alarms

MPOE South

  • PDU-MPOE-S-A Source

  • PDU-MPOE-S-A Alarms

  • PDU-MPOE-S-B Sources

  • PDU-MPOE-S-B Alarms

  • RPP-MPOE-S-A

  • RPP-MPOE-S-B

CRAH 1-161

  • Status

  • Preferred Source

  • Discharge F

  • Alarms

CRAH 1-162

  • Status

  • Preferred Source

  • Discharge F

  • Alarms

Active Storage

DEH 1

  • DEH 1 Control

  • DEH 1 Running

  • DEH 1 Timer

  • DEH 1 Alarms

DEH 2

  • DEH 2 Control

  • DEH 2 Running

  • DEH 2 Timer

  • DEH 2 Alarms

DEH 3

  • DEH 3 Control

  • DEH 3 Running

  • DEH 3 Timer

  • DEH 3 Alarms

CRAH 1-165

  • Status

  • Return F

  • Humidity

  • Alarms

CRAH 1-161

  • Status

  • Return F

  • Humidity

  • Alarms

Fenwal (Novec) Panel

  • Alarm

  • Supervisory

  • Trouble

FM 200 Closet 264A - Tape Library

FM 200

  • Alarm

  • Supervisory

  • Trouble

2nd Floor AHU Equipment

AHU - 248

  • AHU 5 Status

  • AHU 5 Frequency

  • AHU 5 Amps

  • AHU 5 Supply Temperature

  • AHU 5 Return Temperature

  • AHU 5 Alarms

  • AHU 7 Status

  • AHU 7 Frequency

  • AHU 7 Amps

  • AHU 7 Supply Temperature

  • AHU 7 Return Temperature

  • AHU 7 Alarms

  • RF 2-5 Status

  • RF 2-5 Frequency

  • RF 2-5 Amps

  • RF 2-5 Supply Temperature

  • RF 2-5 Return Temperature

  • RF 2-5 Alarms

  • RF 2-6 Status

  • RF 2-6 Frequency

  • RF 2-6 Amps

  • RF 2-6 Supply Temperature

  • RF 2-6 Return Temperature

  • RF 2-6 Alarms

  • AHU - 9 Status

  • AHU - 9 Frequency

  • AHU - 9 Amps

  • AHU - 9 Supply Temperature

  • AHU - 9 Return Temperature

  • AHU - 9 Alarms

  • AHU - 8 Status

  • AHU - 8 Frequency

  • AHU - 8 Amps

  • AHU - 8 Supply Temperature

  • AHU - 8 Return Temperature

  • AHU - 8 Alarms

  • AHU - 6 Status

  • AHU - 6 Frequency

  • AHU - 6 Amps

  • AHU - 6 Supply Temperature

  • AHU - 6 Return Temperature

  • AHU - 6 Alarms

  • RF 2-4 Status

  • RF 2-4 Frequency

  • RF 2-4 Amps

  • RF 2-4 Supply Temperature

  • RF 2-4 Return Temperature

  • RF 2-4 Alarms

Air Compressor #2

  • Control

  • Main Dryer

  • PSI

  • Filter 1

  • Filter 2

  • Dryer 1

  • Dryer 2

  • Filter 3

  • Filter 4

  • PSI

POD 1 & Gallery 1A/1B

Leak Detection 1A

  • Status

  • Alarm

Leak Detection 1B

  • Status

  • Alarm

Corridor W213 - Touch Screen

  • Fieldview Touch screen

  • Working

Gallery 1B VFD Ratum Fan 2-2

  • Status

  • Frequency

  • Amps

  • Alarms

Gallery 1A CRAH Units

Gallery A CRAH Units

  • CRAH 2-1

  • CRAH 2-1 Preferred Sources

  • CRAH 2-1 Discharge F

  • CRAH 2-1 Alarms

  • CRAH 2-2

  • CRAH 2-2 Preferred Sources

  • CRAH 2-2 Discharge F

  • CRAH 2-2 Alarms

  • CRAH 2-3

  • CRAH 2-3 Preferred Sources

  • CRAH 2-3 Discharge F

  • CRAH 2-3 Alarms

  • CRAH 2-4

  • CRAH 2-4 Preferred Sources

  • CRAH 2-4 Discharge F

  • CRAH 2-4 Alarms

  • CRAH 2-5

  • CRAH 2-5 Preferred Sources

  • CRAH 2-5 Discharge F

  • CRAH 2-5 Alarms

  • CRAH 2-7

  • CRAH 2-7 Preferred Sources

  • CRAH 2-7 Discharge F

  • CRAH 2-7 Alarms

  • CRAH 2-8

  • CRAH 2-8 Preferred Sources

  • CRAH 2-8 Discharge F

  • CRAH 2-8 Alarms

  • CRAH 2-10

  • CRAH 2-10 Discharge F

  • CRAH 2-10 Preferred Sources

  • CRAH 2-10 Alarms

  • CRAH 2-11

  • CRAH 2-11 Preferred Sources

  • CRAH 2-11 Discharge F

  • CRAH 2-11 Alarms

  • CRAH 2-12

  • CRAH 2-12 Preferred Sources

  • CRAH 2-12 Discharge F

  • CRAH 2-12 Alarms

  • CRAH 2-14

  • CRAH 2-14 Discharge F

  • CRAH 2-14 Preferred Sources

  • CRAH 2-14 Alarms

Gallery 1B CRAH Units

  • CRAH 2-15

  • CRAH 2-15 Preferred Sources

  • CRAH 2-15 Discharge F

  • CRAH 2-15 Alarms

  • CRAH 2-16

  • CRAH 2-16 Preferred Sources

  • CRAH 2-16 Discharge F

  • CRAH 2-16 Alarms

  • CRAH 2-17

  • CRAH 2-17 Preferred Sources

  • CRAH 2-17 Discharge F

  • CRAH 2-17 Alarms

  • CRAH 2-18

  • CRAH 2-18 Preferred Sources

  • CRAH 2-18 Discharge F

  • CRAH 2-18 Alarms

  • CRAH 2-19

  • CRAH 2-19 Preferred Sources

  • CRAH 2-19 Discharge F

  • CRAH 2-19 Alarms

  • CRAH 2-21

  • CRAH 2-21 Preferred Sources

  • CRAH 2-21 Discharge F

  • CRAH 2-21 Alarms

  • CRAH 2-22

  • CRAH 2- 22 Preferred Sources

  • CRAH 2-22 Discharge F

  • CRAH 2-22 Alarms

  • CRAH 2-23

  • CRAH 2-23 Discharge F

  • CRAH 2-23 Preferred Sources

  • CRAH 2-23 Alarms

  • CRAH 2-25

  • CRAH 2-25 Preferred Sources

  • CRAH 2-25 Discharge F

  • CRAH 2-25 Alarms

  • CRAH 2-26

  • CRAH 2-26 Preferred Sources

  • CRAH 2-26 Discharge F

  • CRAH 2-26 Alarms

  • CRAH 2-27

  • CRAH 2-27 Discharge F

  • CRAH 2-27 Preferred Sources

  • CRAH 2-27 Alarms

Gallery 1A PDU

  • PDU-1A-1 Source

  • PDU-1A-1Alarm

  • PDU-1A-2 Source

  • PDU-1A-2 Alarm

  • PDU-1A-3 Source

  • PDU-1A-3 Alarm

  • PDU-1A-4 Source

  • PDU-1A-4 Alarm

  • PDU-1A-5 Source

  • PDU-1A-5 Alarm

  • PDU-1A6 Source

  • PDU-1A-6 Alarm

  • PDU-1A7 Source

  • PDU-1A-7 Alarm

  • PDU-1A-8 Source

  • PDU-1A-8 Alarm

  • PDU-1A-9 Source

  • PDU-1A-9 Alarm

  • PDU-1A-10 Source

  • PDU-1A-10 Alarm

  • PDU-1A-11 Source

  • PDU-1A-11 Alarm

  • PDU-1A-12 Source

  • PDU-1A-12 Alarm

Gallery 1B PDU

  • PDU-1B-1 Source

  • PDU-1B-1 Alarm

  • PDU-1B-2 Source

  • PDU-1B-2 Alarm

  • PDU-1B-3 Source

  • PDU-1B-3 Alarm

  • PDU-1B-4 Source

  • PDU-1B-4 Alarm

  • PDU-1B-5 Source

  • PDU-1B-5 Alarm

  • PDU-1B-6 Source

  • PDU-1B-6 Alarm

  • PDU-1B 7 Source

  • PDU-1B-7 Alarm

  • PDU-1B-8 Source

  • PDU-1B-8 Alarm

  • PDU-1B-9 Source

  • PDU-1B-9 Alarm

  • PDU-1B-10 Source

  • PDU-1B-10 Alarm

  • PDU-1B-11 Source

  • PDU-1B-11 Alarm

  • PDU-1B-12 Source

  • PDU-1B-12 Alarm

POD 1 South

  • RPP - 1A-1-1 Alarms

  • RPP - 1B-1-1 Alarms

  • RPP - 1A-1-2 Alarms

  • RPP - 1B-1-2 Alarms

  • RPP - 1A-1-3 Alarms

  • RPP - 1B-1-3 Alarms

  • RPP - 1A-1-4 Alarms

  • RPP - 1B-1-4 Alarms

  • RPP - 1A-3-1 Alarms

  • RPP - 1B-3-1 Alarms

  • RPP - 1A-3-2 Alarms

  • RPP - 1B-3-2 Alarms

  • RPP - 1A-3-3 Alarms

  • RPP - 1B-3-3 Alarms

  • RPP - 1A-3-4 Alarms

  • RPP - 1B-3-4 Alarms

  • RPP - 1A-5-1 Alarms

  • RPP - 1B-5-1 Alarms

  • RPP - 1A-5-2 Alarms

  • RPP - 1B-5-2 Alarms

  • RPP - 1A-5-3 Alarms

  • RPP - 1B-5-3 Alarms

  • RPP - 1A-5-4 Alarms

  • RPP - 1B-5-4 Alarms

  • RPP - 1A-7-1 Alarms

  • RPP - 1B-7-1 Alarms

  • RPP - 1A-7-2 Alarms

  • RPP - 1B-7-2 Alarms

  • RPP - 1A-7-3 Alarms

  • RPP - 1B-7-3 Alarms

  • RPP - 1A-7-4 Alarms

  • RPP - 1B-7-4 Alarms

  • RPP - 1A-9-1 Alarms

  • RPP - 1B-9-1 Alarms

  • RPP - 1A-9-2 Alarms

  • RPP - 1B-9-2 Alarms

  • RPP - 1A-9-3 Alarms

  • RPP - 1B-9-3 Alarms

  • RPP - 1A-9-4 Alarms

  • RPP - 1B-9-4 Alarms

  • RPP - 1A-11-1 Alarms

  • RPP - 1B-11-1 Alarms

  • RPP - 1A-11-2 Alarms

  • RPP - 1B-11-2 Alarms

  • RPP - 1A-11-3 Alarms

  • RPP - 1B-11-3 Alarms

  • RPP - 1A-11-4 Alarms

  • RPP - 1B-11-4 Alarms

POD 1 North

  • RPP - 1A-2-1 Alarms

  • RPP - 1B-2-1 Alarms

  • RPP - 1A-2-2 Alarms

  • RPP - 1B-2-2 Alarms

  • RPP - 1A-2-3 Alarms

  • RPP - 1B-2-3 Alarms

  • RPP - 1A-2-4 Alarms

  • RPP - 1B-2-4 Alarms

  • RPP - 1A-4-1 Alarms

  • RPP - 1B-4-1 Alarms

  • RPP - 1A-4-2 Alarms

  • RPP - 1B-4-2 Alarms

  • RPP - 1A-4-3 Alarms

  • RPP - 1B-4-3 Alarms

  • RPP - 1A-4-4 Alarms

  • RPP - 1B-4-4 Alarms

  • RPP - 1A-6-1 Alarms

  • RPP - 1B-6-1 Alarms

  • RPP - 1A-6-2 Alarms

  • RPP - 1B-6-2 Alarms

  • RPP - 1A-6-3 Alarms

  • RPP - 1B6-3 Alarms

  • RPP - 1A-6-4 Alarms

  • RPP - 1B-6-4 Alarms

  • RPP - 1A-8-1 Alarms

  • RPP - 1B-8-1 Alarms

  • RPP - 1A-8-2 Alarms

  • RPP - 1B-8-2 Alarms

  • RPP - 1A-8-3 Alarms

  • RPP - 1B-8-3 Alarms

  • RPP - 1A-8-4 Alarms

  • RPP - 1B-8-4 Alarms

  • RPP - 1A-10-1 Alarms

  • RPP - 1B-10-1 Alarms

  • RPP - 1A-10-2 Alarms

  • RPP - 1B-10-2 Alarms

  • RPP - 1A-10-3 Alarms

  • RPP - 1B-10-3 Alarms

  • RPP - 1A-10-4 Alarms

  • RPP - 1B-10-4 Alarms

  • RPP - 1A-12-1 Alarms

  • RPP - 1B-12-1 Alarms

  • RPP - 1A-12-2 Alarms

  • RPP - 1B-12-2 Alarms

  • RPP - 1A-12-3 Alarms

  • RPP - 1B-12-3 Alarms

  • RPP - 1A-12-4 Alarms

  • RPP - 1B-12-4 Alarms

POD 2 & Gallery 2A/2B

Leak Detection 2A

  • Status

  • Alarm

Leak Detection 2B

  • Status

  • Alarm

Gallery 2A VFD Ratum Fan 2-1

  • Status

  • Frequency

  • Amps

  • Alarms

Corridor W213 - Touch Screen

  • Vestibul 282 Fieldview Touch screen Status

  • Vestibul 282 Fieldview Touch screen Working

  • EPMS Touch screen

  • EPMS Touch screen Working

Gallery 1A CRAH Units

Gallery 2A CRAH Units

  • CRAH 2-29

  • CRAH 2-29 Preferred Sources

  • CRAH 2-29 Discharge F

  • CRAH 2-29 Alarms

  • CRAH 2-30

  • CRAH 2-30 Preferred Sources

  • CRAH 2-30 Discharge F

  • CRAH 2-30 Alarms

  • CRAH 2-31

  • CRAH 2-31 Preferred Sources

  • CRAH 2-31 Discharge F

  • CRAH 2-31 Alarms

  • CRAH 2-32

  • CRAH 2-32 Preferred Sources

  • CRAH 2-32 Discharge F

  • CRAH 2-32 Alarms

  • CRAH 2-33

  • CRAH 2-33 Preferred Sources

  • CRAH 2-33 Discharge F

  • CRAH 2-33 Alarms

  • CRAH 2-35

  • CRAH 2-35 Preferred Sources

  • CRAH 2-35 Discharge F

  • CRAH 2-35 Alarms

  • CRAH 2-36

  • CRAH 2-36 Preferred Sources

  • CRAH 2-36 Discharge F

  • CRAH 2-36 Alarms

  • CRAH 2-37

  • CRAH 2-37 Discharge F

  • CRAH 2-37 Preferred Sources

  • CRAH 2-37 Alarms

  • CRAH 2-39

  • CRAH 2-39 Preferred Sources

  • CRAH 2-39 Discharge F

  • CRAH 2-39 Alarms

  • CRAH 2-40

  • CRAH 2-40 Preferred Sources

  • CRAH 2-40 Discharge F

  • CRAH 2-40 Alarms

  • CRAH 2-41

  • CRAH 2-41Discharge F

  • CRAH 2-41 Preferred Sources

  • CRAH 2-41 Alarms

Gallery 1B CRAH Units

  • CRAH 2-43

  • CRAH 2-43 Preferred Sources

  • CRAH 2-43 Discharge F

  • CRAH 2-43 Alarms

  • CRAH 2-44

  • CRAH 2-44 Preferred Sources

  • CRAH 2-44 Discharge F

  • CRAH 2-44 Alarms

  • CRAH 2-45

  • CRAH 2-45 Preferred Sources

  • CRAH 2-45 Discharge F

  • CRAH 2-45 Alarms

  • CRAH 2-46

  • CRAH 2-46 Preferred Sources

  • CRAH 2-46 Discharge F

  • CRAH 2-46 Alarms

  • CRAH 2-47

  • CRAH 2-47 Preferred Sources

  • CRAH 2-47 Discharge F

  • CRAH 2-47 Alarms

  • CRAH 2-49

  • CRAH 2-49 Preferred Sources

  • CRAH 2-49 Discharge F

  • CRAH 2-49 Alarms

  • CRAH 2-50

  • CRAH 2- 50 Preferred Sources

  • CRAH 2-50 Discharge F

  • CRAH 2-50 Alarms

  • CRAH 2-52

  • CRAH 2-52 Discharge F

  • CRAH 2-52 Preferred Sources

  • CRAH 2-52 Alarms

  • CRAH 2-53

  • CRAH 2-53 Preferred Sources

  • CRAH 2-53 Discharge F

  • CRAH 2-53 Alarms

  • CRAH 2-54

  • CRAH 2-54 Preferred Sources

  • CRAH 2-54 Discharge F

  • CRAH 2-54 Alarms

  • CRAH 2-56

  • CRAH 2-56 Discharge F

  • CRAH 2-56 Preferred Sources

  • CRAH 2-56 Alarms

Gallery 2A PDU

  • PDU-2A-1 Source

  • PDU-2A-1Alarm

  • PDU-2A-2 Source

  • PDU-2A-2 Alarm

  • PDU-2A-3 Source

  • PDU-2A-3 Alarm

  • PDU-2A-4 Source

  • PDU-2A-4 Alarm

  • PDU-2A-5 Source

  • PDU-2A-5 Alarm

  • PDU-2A6 Source

  • PDU-2A-6 Alarm

  • PDU-2A7 Source

  • PDU-2A-7 Alarm

  • PDU-2A-8 Source

  • PDU-2A-8 Alarm

  • PDU-2A-9 Source

  • PDU-2A-9 Alarm

  • PDU-2A-10 Source

  • PDU-2A-10 Alarm

  • PDU-2A-11 Source

  • PDU-2A-11 Alarm

  • PDU-2A-12 Source

  • PDU-2A-12 Alarm

Gallery 1B PDU

  • PDU-2B-1 Source

  • PDU-2B-1 Alarm

  • PDU-2B-2 Source

  • PDU-2B-2 Alarm

  • PDU-2B-3 Source

  • PDU-2B-3 Alarm

  • PDU-2B-4 Source

  • PDU-2B-4 Alarm

  • PDU-2B-5 Source

  • PDU-2B-5 Alarm

  • PDU-2B-6 Source

  • PDU-2B-6 Alarm

  • PDU-2B 7 Source

  • PDU-2B-7 Alarm

  • PDU-2B-8 Source

  • PDU-2B-8 Alarm

  • PDU-2B-9 Source

  • PDU-2B-9 Alarm

  • PDU-2B-10 Source

  • PDU-2B-10 Alarm

  • PDU-2B-11 Source

  • PDU-2B-11 Alarm

  • PDU-2B-12 Source

  • PDU-2B-12 Alarm

POD 2 South

  • RPP - 2A-1-1 Alarms

  • RPP - 2B-1-1 Alarms

  • RPP - 2A-1-2 Alarms

  • RPP - 2B-1-2 Alarms

  • RPP - 2A-1-3 Alarms

  • RPP - 2B-1-3 Alarms

  • RPP - 2A-1-4 Alarms

  • RPP - 2B-1-4 Alarms

  • RPP - 2A-3-1 Alarms

  • RPP - 2B-3-1 Alarms

  • RPP - 2A-3-2 Alarms

  • RPP - 2B-3-2 Alarms

  • RPP - 2A-3-3 Alarms

  • RPP -2B-3-3 Alarms

  • RPP - 2A-3-4 Alarms

  • RPP - 2B-3-4 Alarms

  • RPP - 2A-5-1 Alarms

  • RPP - 2B-5-1 Alarms

  • RPP - 2A-5-2 Alarms

  • RPP - 2B-5-2 Alarms

  • RPP - 2A-5-3 Alarms

  • RPP - 2B-5-3 Alarms

  • RPP - 2A-5-4 Alarms

  • RPP - 2B-5-4 Alarms

  • RPP - 2A-7-1 Alarms

  • RPP - 2B-7-1 Alarms

  • RPP - 2A-7-2 Alarms

  • RPP - 2B-7-2 Alarms

  • RPP - 2A-7-3 Alarms

  • RPP - 2B-7-3 Alarms

  • RPP - 2A-7-4 Alarms

  • RPP - 2B-7-4 Alarms

  • RPP - 2A-9-1 Alarms

  • RPP - 2B-9-1 Alarms

  • RPP - 2A-9-2 Alarms

  • RPP - 2B-9-2 Alarms

  • RPP - 2A-9-3 Alarms

  • RPP - 2B-9-3 Alarms

  • RPP - 2A-9-4 Alarms

  • RPP - 2B-9-4 Alarms

  • RPP - 2A-11-1 Alarms

  • RPP - 2B-11-1 Alarms

  • RPP - 2A-11-2 Alarms

  • RPP - 2B-11-2 Alarms

  • RPP - 2A-11-3 Alarms

  • RPP - 2B-11-3 Alarms

  • RPP - 2A-11-4 Alarms

  • RPP - 2B-11-4 Alarms

POD 2 North

  • RPP - 2A-2-1 Alarms

  • RPP - 2B-2-1 Alarms

  • RPP - 2A-2-2 Alarms

  • RPP - 2B-2-2 Alarms

  • RPP - 2A-2-3 Alarms

  • RPP - 2B-2-3 Alarms

  • RPP - 2A-2-4 Alarms

  • RPP - 2B-2-4 Alarms

  • RPP - 2A-4-1 Alarms

  • RPP - 2B-4-1 Alarms

  • RPP - 2A-4-2 Alarms

  • RPP - 2B-4-2 Alarms

  • RPP - 2A-4-3 Alarms

  • RPP - 2B-4-3 Alarms

  • RPP - 2A-4-4 Alarms

  • RPP - 2B-4-4 Alarms

  • RPP - 2A-6-1 Alarms

  • RPP - 2B-6-1 Alarms

  • RPP - 2A-6-2 Alarms

  • RPP - 2B-6-2 Alarms

  • RPP - 2A-6-3 Alarms

  • RPP - 2B 6-3 Alarms

  • RPP - 2B-6-4 Alarms

  • RPP - 2B-6-4 Alarms

  • RPP - 2A-8-1 Alarms

  • RPP - 2B-8-1 Alarms

  • RPP - 2A-8-2 Alarms

  • RPP - 2B-8-2 Alarms

  • RPP - 2A-8-3 Alarms

  • RPP - 2B-8-3 Alarms

  • RPP - 2A-8-4 Alarms

  • RPP - 2B-8-4 Alarms

  • RPP - 2A-10-1 Alarms

  • RPP - 2B-10-1 Alarms

  • RPP - 2A-10-2 Alarms

  • RPP - 2B-10-2 Alarms

  • RPP - 2A-10-3 Alarms

  • RPP - 2B-10-3 Alarms

  • RPP - 2A-10-4 Alarms

  • RPP - 2B-10-4 Alarms

  • RPP - 2A-12-1 Alarms

  • RPP - 2B-12-1 Alarms

  • RPP - 2A-12-2 Alarms

  • RPP - 2B-12-2 Alarms

  • RPP - 2A-12-3 Alarms

  • RPP - 2B-12-3 Alarms

  • RPP - 2A-12-4 Alarms

  • RPP - 2B-12-4 Alarms

POD 3 & Gallery 3A/3B

Leak Detection 3A

  • Status

  • Alarm

Leak Detection 3B

  • Status

  • Alarm

Corridor W213 - Touch Screen

  • Vestibul 282 Fieldview Touch screen Status

  • Vestibul 282 Fieldview Touch screen Working

Gallery 2A VFD Return Fan 3-1

  • Status

  • Frequency

  • Amps

  • Alarms

Gallery 3A CRAH Units

Gallery A CRAH Units

  • CRAH 2-57

  • CRAH 2-57 Preferred Sources

  • CRAH 2-57 Discharge F

  • CRAH 2-57 Alarms

  • CRAH 2-58

  • CRAH 2-58 Preferred Sources

  • CRAH 2-58 Discharge F

  • CRAH 2-58 Alarms

  • CRAH 2-59

  • CRAH 2-59 Preferred Sources

  • CRAH 2-59 Discharge F

  • CRAH 2-59 Alarms

  • CRAH 2-60

  • CRAH 2-60 Preferred Sources

  • CRAH 2-60 Discharge F

  • CRAH 2-60 Alarms

  • CRAH 2-61

  • CRAH 2-61 Preferred Sources

  • CRAH 2-61 Discharge F

  • CRAH 2-61 Alarms

  • CRAH 2-62

  • CRAH 2-62 Preferred Source

  • CRAH 2-62 Discharge F

  • CRAH 2-62 Alarms

  • CRAH 2-63

  • CRAH 2-63 Preferred Sources

  • CRAH 2-63 Discharge F

  • CRAH 2-63 Alarms

  • CRAH 2-64

  • CRAH 2-64 Discharge F

  • CRAH 2-64 Preferred Sources

  • CRAH 2-64 Alarms

  • CRAH 2-65

  • CRAH 2-65 Preferred Sources

  • CRAH 2-65 Discharge F

  • CRAH 2-65 Alarms

  • CRAH 2-66

  • CRAH 2-66 Preferred Sources

  • CRAH 2-66 Discharge F

  • CRAH 2-66 Alarms

  • CRAH 2-67

  • CRAH 2-67 Discharge F

  • CRAH 2-67 Preferred Sources

  • CRAH 2-67 Alarms

  • CRAH 2-68

  • CRAH 2-68 Discharge F

  • CRAH 2-68 Preferred Sources

  • CRAH 2-68 Alarms

  • CRAH 2-69

  • CRAH 2-69 Discharge F

  • CRAH 2-69 Preferred Sources

  • CRAH 2-69 Alarms

  • CRAH 2-70

  • CRAH 2-70 Discharge F

  • CRAH 2-70 Preferred Sources

  • CRAH 2-70 Alarms

Gallery 3B CRAH Units

  • CRAH 2-71

  • CRAH 2-71 Preferred Sources

  • CRAH 2-71 Discharge F

  • CRAH 2-71 Alarms

  • CRAH 2-72

  • CRAH 2-72 Preferred Sources

  • CRAH 2-72 Discharge F

  • CRAH 2-72 Alarms

  • CRAH 2-73

  • CRAH 2-73 Preferred Sources

  • CRAH 2-73 Discharge F

  • CRAH 2-73 Alarms

  • CRAH 2-74

  • CRAH 2-74 Preferred Sources

  • CRAH 2-74 Discharge F

  • CRAH 2-74 Alarms

  • CRAH 2-75

  • CRAH 2-75 Preferred Sources

  • CRAH 2-75 Discharge F

  • CRAH 2-75 Alarms

  • CRAH 2-76

  • CRAH 2-76 Preferred Sources

  • CRAH 2-76 Discharge F

  • CRAH 2-76 Alarms

  • CRAH 2-77

  • CRAH 2- 77 Preferred Sources

  • CRAH 2-77 Discharge F

  • CRAH 2-77 Alarms

  • CRAH 2-78

  • CRAH 2-78 Discharge F

  • CRAH 2-78 Preferred Sources

  • CRAH 2-78 Alarms

  • CRAH 2-79

  • CRAH 2-79 Preferred Sources

  • CRAH 2-79 Discharge F

  • CRAH 2-79 Alarms

  • CRAH 2-80

  • CRAH 2-80 Preferred Sources

  • CRAH 2-80 Discharge F

  • CRAH 2-80 Alarms

  • CRAH 2-81

  • CRAH 2-81 Discharge F

  • CRAH 2-81 Preferred Sources

  • CRAH 2-81 Alarms

  • CRAH 2-82

  • CRAH 2-82 Discharge F

  • CRAH 2-82 Preferred Sources

  • CRAH 2-82 Alarms

  • CRAH 2-83

  • CRAH 2-83 Discharge F

  • CRAH 2-83 Preferred Sources

  • CRAH 2-83 Alarms

  • CRAH 2-84

  • CRAH 2-84 Discharge F

  • CRAH 2-84 Preferred Sources

  • CRAH 2-84 Alarms

Gallery 3A PDU

  • PDU-3A-1 Source

  • PDU-3A-1Alarm

  • PDU-3A-2 Source

  • PDU-3A-2 Alarm

  • PDU-3A-3 Source

  • PDU-3A-3 Alarm

  • PDU-3A-4 Source

  • PDU-3A-4 Alarm

  • PDU-3A-5 Source

  • PDU-3A-5 Alarm

  • PDU-3A6 Source

  • PDU-3A-6 Alarm

  • PDU-3A7 Source

  • PDU-3A-7 Alarm

  • PDU-3A-8 Source

  • PDU-3A-8 Alarm

  • PDU-3A-9 Source

  • PDU-3A-9 Alarm

  • PDU-3A-10 Source

  • PDU-3A-10 Alarm

  • PDU-3A-11 Source

  • PDU-3A-11 Alarm

  • PDU-3A-12 Source

  • PDU-3A-12 Alarm

Gallery 3B PDU

  • PDU-3B-1 Source

  • PDU-3B-1 Alarm

  • PDU-3B-2 Source

  • PDU-3B-2 Alarm

  • PDU-3B-3 Source

  • PDU-3B-3 Alarm

  • PDU-3B-4 Source

  • PDU-3B-4 Alarm

  • PDU-3B-5 Source

  • PDU-3B-5 Alarm

  • PDU-3B-6 Source

  • PDU-3B-6 Alarm

  • PDU-3B 7 Source

  • PDU-3B-7 Alarm

  • PDU-3B-8 Source

  • PDU-3B-8 Alarm

  • PDU-3B-9 Source

  • PDU-3B-9 Alarm

  • PDU-3B-10 Source

  • PDU-3B-10 Alarm

  • PDU-3B-11 Source

  • PDU-3B-11 Alarm

  • PDU-3B-12 Source

  • PDU-3B-12 Alarm

POD 3 South

  • RPP - 3A-1-1 Alarms

  • RPP - 3B-1-1 Alarms

  • RPP - 3A-1-2 Alarms

  • RPP - 3B-1-2 Alarms

  • RPP - 3A-1-3 Alarms

  • RPP - 3B-1-3 Alarms

  • RPP - 3A-1-4 Alarms

  • RPP - 3B-1-4 Alarms

  • RPP - 3A-3-1 Alarms

  • RPP - 3B-3-1 Alarms

  • RPP - 3A-3-2 Alarms

  • RPP - 3B-3-2 Alarms

  • RPP - 3A-3-3 Alarms

  • RPP - 3B-3-3 Alarms

  • RPP - 3A-3-4 Alarms

  • RPP - 3B-3-4 Alarms

  • RPP -3A-5-1 Alarms

  • RPP - 3B-5-1 Alarms

  • RPP - 3A-5-2 Alarms

  • RPP - 3B-5-2 Alarms

  • RPP - 3A-5-3 Alarms

  • RPP - 3B-5-3 Alarms

  • RPP - 3A-5-4 Alarms

  • RPP - 3B-5-4 Alarms

  • RPP - 3A-7-1 Alarms

  • RPP - 3B-7-1 Alarms

  • RPP - 3A-7-2 Alarms

  • RPP - 3B-7-2 Alarms

  • RPP - 3A-7-3 Alarms

  • RPP - 3B-7-3 Alarms

  • RPP - 3A-7-4 Alarms

  • RPP - 3B-7-4 Alarms

  • RPP - 3A-9-1 Alarms

  • RPP - 3B-9-1 Alarms

  • RPP - 3A-9-2 Alarms

  • RPP - 3B-9-2 Alarms

  • RPP - 3A-9-3 Alarms

  • RPP - 3B-9-3 Alarms

  • RPP - 3A-9-4 Alarms

  • RPP - 3B-9-4 Alarms

  • RPP - 3A-11-1 Alarms

  • RPP - 3B-11-1 Alarms

  • RPP - 3A-11-2 Alarms

  • RPP - 3B-11-2 Alarms

  • RPP - 3A-11-3 Alarms

  • RPP - 3B-11-3 Alarms

  • RPP - 3A-11-4 Alarms

  • RPP - 3B-11-4 Alarms

POD 3 North

  • RPP - 3A-2-1 Alarms

  • RPP - 3B-2-1 Alarms

  • RPP - 3A-2-2 Alarms

  • RPP - 3B-2-2 Alarms

  • RPP - 3A-2-3 Alarms

  • RPP - 3B-2-3 Alarms

  • RPP - 3A-2-4 Alarms

  • RPP - 3B-2-4 Alarms

  • RPP - 3A-4-1 Alarms

  • RPP - 3B-4-1 Alarms

  • RPP - 3A-4-2 Alarms

  • RPP - 3B-4-2 Alarms

  • RPP -3-A-4-3 Alarms

  • RPP - 3B-4-3 Alarms

  • RPP - 3A-4-4 Alarms

  • RPP - 3B-4-4 Alarms

  • RPP - 3A-6-1 Alarms

  • RPP - 3B-6-1 Alarms

  • RPP - 3A-6-2 Alarms

  • RPP - 3B-6-2 Alarms

  • RPP - 3A-6-3 Alarms

  • RPP - 3B6-3 Alarms

  • RPP - 3A-6-4 Alarms

  • RPP - 3B-6-4 Alarms

  • RPP - 3A-8-1 Alarms

  • RPP - 3B-8-1 Alarms

  • RPP - 3A-8-2 Alarms

  • RPP - 3B-8-2 Alarms

  • RPP - 3A-8-3 Alarms

  • RPP - 3B-8-3 Alarms

  • RPP - 3A-8-4 Alarms

  • RPP - 3B-8-4 Alarms

  • RPP - 3A-10-1 Alarms

  • RPP - 3B-10-1 Alarms

  • RPP - 3A-10-2 Alarms

  • RPP - 3B-10-2 Alarms

  • RPP - 3A-10-3 Alarms

  • RPP - 3B-10-3 Alarms

  • RPP - 3A-10-4 Alarms

  • RPP - 3B-10-4 Alarms

  • RPP - 3A-12-1 Alarms

  • RPP - 3B-12-1 Alarms

  • RPP - 3A-12-2 Alarms

  • RPP - 3B-12-2 Alarms

  • RPP - 3A-12-3 Alarms

  • RPP - 3B-12-3 Alarms

  • RPP - 3A-12-4 Alarms

  • RPP - 3B-12-4 Alarm

POD 4 & Gallery 4A/4B

Corridor W220 - Touch Screen

  • EPMS Touch screen

  • EPMS Touch screen Working

Gallery 2A VFD Return Fan 2-7

  • Status

  • Frequency

  • Amps

  • Alarms

Leak Detection 4A

  • 4A-1 Status

  • 4A-1 Alarm

  • 4A-2 Status

  • 4A-2 Alarm

  • 4A-3 Status

  • 4A-3 Alarm

Leak Detection 4B

  • 4B-1 Status

  • 4B-1 Alarm

  • 4B-2 Status

  • 4B-2 Alarm

  • 4B-3 Status

  • 4B-3 Alarm

Gallery 4A CRAH Units

Gallery A CRAH Units

  • CRAH 2-85

  • CRAH 2-85 Preferred Sources

  • CRAH 2-85 Discharge F

  • CRAH 2-85 Alarms

  • CRAH 2-86

  • CRAH 2-86 Preferred Sources

  • CRAH 2-86 Discharge F

  • CRAH 2-86 Alarms

  • CRAH 2-87

  • CRAH 2-87 Preferred Sources

  • CRAH 2-87 Discharge F

  • CRAH 2-87 Alarms

  • CRAH 2-91

  • CRAH 2-91 Preferred Sources

  • CRAH 2-91 Discharge F

  • CRAH 2-91 Alarms

  • CRAH 2-92

  • CRAH 2-92 Preferred Sources

  • CRAH 2-92 Discharge F

  • CRAH 2-92 Alarms

  • CRAH 2-93

  • CRAH 2-93 Preferred Sources

  • CRAH 2-93 Discharge F

  • CRAH 2-93 Alarms

  • CRAH 2-97

  • CRAH 2-97 Preferred Sources

  • CRAH 2-97 Discharge F

  • CRAH 2-97 Alarms

  • CRAH 2-98

  • CRAH 2-98 Discharge F

  • CRAH 2-98 Preferred Sources

  • CRAH 2-98 Alarms

  • CRAH 2-99

  • CRAH 2-99 Preferred Sources

  • CRAH 2-99 Discharge F

  • CRAH 2-99 Alarms

  • CRAH 2-103

  • CRAH 2-103 Preferred Sources

  • CRAH 2-103 Discharge F

  • CRAH 2-103 Alarms

  • CRAH 2-104

  • CRAH 2-104 Discharge F

  • CRAH 2-104 Preferred Sources

  • CRAH 2-104 Alarms

  • CRAH 2-105

  • CRAH 2-105 Discharge F

  • CRAH 2-105 Preferred Sources

  • CRAH 2-105 Alarms

Gallery 4B CRAH Units

  • CRAH 2-88

  • CRAH 2-88 Preferred Sources

  • CRAH 2-88 Discharge F

  • CRAH 2-88 Alarms

  • CRAH 2-89

  • CRAH 2-89 Preferred Sources

  • CRAH 2-89 Discharge F

  • CRAH 2-89 Alarms

  • CRAH 2-90

  • CRAH 2-90 Preferred Sources

  • CRAH 2-90 Discharge F

  • CRAH 2-90 Alarms

  • CRAH 2-94

  • CRAH 2-94 Preferred Sources

  • CRAH 2-94 Discharge F

  • CRAH 2-94 Alarms

  • CRAH 2-95

  • CRAH 2-95 Preferred Sources

  • CRAH 2-95 Discharge F

  • CRAH 2-95 Alarms

  • CRAH 2-96

  • CRAH 2-96 Preferred Sources

  • CRAH 2-96 Discharge F

  • CRAH 2-96 Alarms

  • CRAH 2-100

  • CRAH 2- 100 Preferred Sources

  • CRAH 2-100 Discharge F

  • CRAH 2-100 Alarms

  • CRAH 2-101

  • CRAH 2-101 Discharge F

  • CRAH 2-101 Preferred Sources

  • CRAH 2-101 Alarms

  • CRAH 2-102

  • CRAH 2-102 Preferred Sources

  • CRAH 2-102 Discharge F

  • CRAH 2-102 Alarms

  • CRAH 2-106

  • CRAH 2-106 Preferred Sources

  • CRAH 2-106 Discharge F

  • CRAH 2-106 Alarms

  • CRAH 2-107

  • CRAH 2-107 Discharge F

  • CRAH 2-107 Preferred Sources

  • CRAH 2-107 Alarms

  • CRAH 2-108

  • CRAH 2-108 Discharge F

  • CRAH 2-108 Preferred Sources

  • CRAH 2-108 Alarms

Gallery 4A UPS - 4A-1

  • UPS-4A-1 Status

  • PS-4A-1 Alarm

Gallery 4A UPS - 4B-1

  • UPS-4B-1 Status

  • PS-4A-B Alarm

UPS 4A 2 Board

  • Main

  • RB

  • BB

  • MOB

  • MIS

UPS 4B 2 Board

  • Main

  • RB

  • BB

  • MOB

  • MIS

2CP41A-1 Trip Unit

  • 2CP41A-1 Trip Unit AC Amps

  • 2CP41A-1 Trip Unit Alarms

2CP41A-1 2 Trip Unit

  • 2CP41A-2 Trip Unit AC Amps

  • 2CP41A-2 Trip Unit Alarms

2CP4B-1 Trip Unit

  • 2CP4B-1 Trip Unit AC Amps

  • 2CP4B-1 Trip Unit Alarms

2CP4B-1 2 Trip Unit

  • 2CP4B-2 Trip Unit AC Amps

  • 2CP4B-2 Trip Unit Alarms

Gallery A UPS-4A-3

  • Gallery A UPS-4A-3 Status

  • Gallery A UPS-4A-3 Alarm

Gallery B UPS-4A-3

  • Gallery B UPS-4A-3 Status

  • Gallery B UPS-4A-3 Alarm

UPS 4A 3 Board

  • Main

  • RB

  • BB

  • MOB

  • MIS

UPS 4B 3 Board

  • Main

  • RB

  • BB

  • MOB

  • MIS

2CP4A-31 Trip Unit

  • 2CP4A3-1 Trip Unit AC Amps

  • 2CP4A3-1 Trip Unit Alarms

2CP4A-3 2 Trip Unit

  • 2CP4A3-2 Trip Unit AC Amps

  • 2CP4A3-2 Trip Unit Alarms

2CP4B3-1 Trip Unit

  • 2CP4B3-1 Trip Unit AC Amps

  • 2CP4B3-1 Trip Unit Alarms

2CP4B3 2 Trip Unit

  • 2CP4B3 2 Trip Unit AC Amps

  • 2CP4B3 2 Trip Unit Alarms

UPS 4A 4 Board

  • Main

  • RB

  • BB

  • MOB

  • MIS

UPS 4B 4 Board

  • Main

  • RB

  • BB

  • MOB

  • MIS

2CP4A-4-1 Trip Unit

  • 2CP4A4-1 Trip Unit AC Amps

  • 2CP4A4-1 Trip Unit Alarms

2CP4A-4 2 Trip Unit

  • 2CP4A4-2 Trip Unit AC Amps

  • 2CP4A4-2 Trip Unit Alarms

2CP4B4-1 Trip Unit

  • 2CP4B4-1 Trip Unit AC Amps

  • 2CP4B4-1 Trip Unit Alarms

2CP4B4 2 Trip Unit

  • 2CP4B4 2 Trip Unit AC Amps

  • 2CP4B4 2 Trip Unit Alarms

POD 4A South

  • PDU-4A1-1 Alarms

  • PDU-4A1-2 Alarms

POD 4A North

  • PDU-4A1-1 Alarms

  • PDU-4A1-2 Alarms

POD 4B South

  • PDU-4A2-1 Alarms

POD 4B North

  • PDU-4B2-1 Alarms

POD 4C South

  • PDU-4A4-1 Alarms

  • PDU-4A3-2 Alarms

POD 4C North

  • PDU-4A3-2 Alarms

  • PDU-4A4-1 Alarms

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.