1. Make-Up Water Requirements
Steam Produced (lb/hr)➖Condensate = Make-Up Water Rate (lb/hr) -
Make-Up Water Rate (lb/hr) =
-
2. Blowdown Requirements
[Solids in Make-Up Water (ppm)✖️Make-Up Water Rate (lb/hr)]➗[ASME Solids Limit (ppm) ➖Solids in Make-Up Water (ppm)] = Boiler Blowdown Rate (lb/hr) -
Boiler Blowdown Rate (lb/hr) =
-
ASME Recommended Limits for Solids in Boiler Water
-
Boiler Steam Pressure (psig) Total Dissolved Solids (ppm)
0 - 300 3,500
301 - 450 3,000
451 - 600 2,500
601 - 750 2,000
751 - 900 1,500
901 - 1,000 1,200