  • 1. Window Fit Factor

    Window Type: Fit: Factor:
    Casement Average 3.6
    Double Hung Average 2.2
    Loose 2.5
    Hinged Average 1.0
    Loose 5.4

  • 2. Rate of Infiltration (cfm / ft of crack)

  • [Average Wind Speed (mph) ✖️ 0.0263 ➖ 0.083] ✖️ Window Fit Factor = Infiltration Rate (cfm / ft of crack)

  • 3. Total Infiltration Rate (cfm)

  • Infiltration Rate (cfm / ft of crack) ✖️ Crack Length (ft / window) ✖️ Number of Windows ✖️ 0.001 = __________ Infiltration Rate (1,000 cfm)

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.