Central Inverter
- Inverter
-
Name Plate, Make and Model
-
Add media
-
Mounted Square On Pad<br>
-
Add media
-
Lamacoids Installed As Per SLD
-
Add media
AC Side of Inverter
-
AC Conductors Installed As Per SLD
-
Wire Size As Per SLD
-
Include picture of wire size
-
Wire Phased Correctly
-
Add media
-
Conduits Sealed
-
Add media
-
Lugs Rubber Taped
-
Add media
-
Torqued and Marked
-
Add media
-
Grounds Torqued and Marked<br>
-
Add media
-
Are Cavities Clean and Free of Debris
-
Add media
-
Safety Guards Installed ,Gland Plates In
-
Add media
DC Side of Inverter
-
DC Conductors Installed As Per SLD<br>
-
Wire Size As Per SLD
-
Include picture of wire size
-
Wire Phased Correctly
-
Add media
-
Conduits Sealed
-
Add media
-
Lugs Rubber Taped
-
Add media
-
Torqued and Marked
-
Add media
-
Grounds Torqued and Marked <br>
-
Add media
-
Are Cavities Clean and Free of Debris<br>
-
Add media
-
Safety Guards Installed, Gland Plates In
-
Add media
Monitoring
-
Are Conduits Run to Cavities On Inverter
-
Add media
-
Are Wires Pulled To Cavity in Inverter
-
Add media
-
Are Communication Wires Terminated
-
Add media
Page Complete
-
Add signature
Inverter pad
-
Cement Work Done to RESCo Standards
-
Add media
-
Picture of Ground Plate With Ground Wire Attached
-
Add media
-
Fence Installed to RESCo Standards
-
Add media
-
Fence Welded
-
Add media
-
Fence Bonded
-
Add media
-
Locks and U Bolt Installed
-
Add media
-
Signage Installed
-
Add media
-
Lock Box On Fence
-
Add media
-
All Strut Galv Sprayed and Secure
-
Add media
Cable Tray
-
Installed Securely
-
Add media
-
Bonded every 50 Feet, Back to Recombiner
-
Add media
-
Cable Space Maintained <br>
-
Add media
-
Cables Secured
-
Add media
-
Cover Installed Correctly
-
Add media
Pipe Work
-
Pipe Supported Properly to Code
-
Add media
-
All Connectors Installed Tightly With Sealing Rings
-
Add media
-
LB'S Drilled / Drain Hole
-
Add media
-
Pipe or Uni Strut Galv Sprayed
-
Add media
Page Complete
-
Add signature
String Inverters
- String Inverter
-
Ground Bushing Present for Metalic Conduit
-
Add media
-
Clean and Free of Debris
-
Add media
DC Side of Inverters
-
DC Conductors Installed As Per SLD
-
Add media
-
Wire Size As Per SLD
-
Add media
-
Correct Polarity and Phase
-
Add media
-
Conduits Sealed
-
Add media
-
Ground Bushings Present On Metallic Conduit <br>
-
Add media
-
Terminations Torqued and Marked
-
Add media
-
Grounds Torqued and Marked
-
Add media
-
Cavities Clean and Free of Debris
-
Add media
-
Safety Guards Installed
-
Add media
-
Name Plate ,Make and Model
-
Add media
-
Mounted Secure and Square
-
Add media
-
Lamacoids As Per SLD
-
Add media
AC Side of Inverter
-
All Conductors Installed As Per SLD
-
Add media
-
Wire Size As Per SLD
-
Add media
-
Wire Phased Correctly
-
Add media
-
Conduits Sealed
-
Add media
-
Lugs Torqued and Marked
-
Add media
-
Grounds Torqued and Marked
-
Add media
-
Knockouts Sealed
-
Add media
Page Complete
-
Add signature
Micro inverters/ Power Optimizers
-
Bonded and Grounded As Per SLD
-
Add media
-
Serial Number Map Complete
-
Add media
-
Monitoring Installation Complete
-
Add media
Page Complete
-
Add signature
Disconnects
- Disconnects
-
Lamacoids Installed As Per SLD
-
Add media
-
Conductors Installed As Per SLD
-
Add media
-
Wires Phased Correctly
-
Add media
-
DC Wiring Done Correctly<br>
-
Add media
-
Lugs Torqued and Marked
-
Add media
-
Fuses Installed As Per SLD
-
Add media
-
Neutral Block Installed, Bonded if Needed
-
Add media
-
Clean and Free of Debris
-
Add media
-
Drain Hole if Needed
-
Add media
Page Complete
-
Add signature
Metering and Monitoring
-
Are Monitoring Enclosures Installed
-
Add media
-
All Pipe work Complete , including Chase to Roof Top, and Inverters
-
Add media
-
Communication Wire Pulled
-
Add media
-
Weather Station Built and Ballasted
-
Add media
-
All Sensors Installed
-
Add media
-
All Sensor Wires Terminated
-
Add media
-
Communication Wires Terminated
-
Add media
-
Meter Installed
-
Include Picture of Complete Enclosure and Face Plate and Serial Number of Meter
-
120 On Pad with Plug
-
Add media
-
Metering Phone Line Installed
-
Add media
-
Monitoring Internet Connection (hardline) Installed and Tested
-
Add media
-
Pre-Commissioning Forms Completed
Page Complete
-
Add signature
Transformer
-
Make, Model, Name Plate
-
Add media
-
Lamacoids Installed by SLD
-
Add media
-
Taps Are Free From Any Modifications and Have Adequate Space Between Them
-
Add media
-
Terminations Are Rubber Taped
-
Add media
-
Clean and Free of Debris
-
Add media
Primary
-
Conductors Installed As Per SLD
-
Conductor Size As Per SLD
-
Include picture of wire size
-
Lugs Torqued and Marked
-
Add media
-
XO Grounded, By Us or By Factory
-
Add media
-
Transformer Chassis Grounded
-
Add media
-
Conduits Sealed
-
Add media
Secondary
-
Conductors Installed As Per SLD
-
Conductor Size As Per SLD<br>
-
Include picture of wire size
-
Lugs Torqued and Marked
-
Add media
-
Conduits Sealed
-
Add media
Page Complete
-
Add signature
Recombiner
- Recombiner
-
Make, Model, Name Plate
-
Add media
-
Lamicoids Installed As Per SLD
-
Add media
-
Recombiner Secured to the Pad
-
Add media
-
Conductors Installed As Per SLD
-
Add media
-
Teck Installed Correctly, Conductor Size As Per SLD
-
Add media
-
Conductors Size As Per SLD, From Recombiner to Inverter
-
Add media
-
Conductors Phased Correctly<br>
-
Add media
-
Teck Cables Labeled As Per SLD, to Correct Breaker
-
Add media
-
Breakers Installed As Per SLD
-
Add media
-
Teck Connectors Installed Correctly, and Sealed
-
Add media
-
Ground Installed and Torqued
-
Add media
-
Rubber Taped on Lugs
-
Add media
-
Lugs Torqued and Marked
-
Add media
-
Conduits Sealed, Gland Plate Installed
-
Add media
-
Clean and Free of Debris
-
Add media
Page Complete
-
Add signature
Electrical Room
-
Clean and Free of Debris
-
Add media
-
All Lamacoids Installed As Per SLD
-
Add media
-
All Pipe or Teck Runs Secured Correctly
-
Add media
-
Overall Photo Of Completed Work
-
Add media
Page Complete
-
Add signature
Main Switch / Shutdown
-
Make, Model, Name Plate<br>
-
Add media
-
Lamacoids Installed As Per SLD
-
Add media
-
Shut Down Complete<br>
-
Include All Shut Down Pictures
-
Lugs Torqued and Marked
-
Add media
-
Size Of Main Breaker
-
Add media
DG1
-
Clean and Free of Debris
-
Add media
-
Shutdown Lock Installed
-
Add media
-
Installed As Per SLD
-
Add media
-
Conductor Size As Per SLD
-
Add media
-
Neutral Block Installed and Bonded
-
Add media
-
Ground Bushings
-
Add media
-
Lugs Torqued and Marked
-
Add media
-
Lamacoids Installed As Per SLD
-
Add media
Page Complete
-
Add signature
Combiner boxes
- Combiner Box
-
Add media
-
Secured To Rack or Durablock<br>
-
Add media
-
Lamacoid As Per SLD
-
Add media
-
Expansion Joints Installed for Wire Management With Sealing Rings
-
Add media
-
Teck Connectors Seated Correctly With Sealing Rings
-
Add media
-
Teck and Pipe Supported Correctly
-
Add media
-
Feeders Installed Correctly and Phased
-
Add media
-
All Fuses Installed and Open
-
Add media
-
All Home Runs Connected
-
Lugs Torqued and Marked
-
Add media
-
Bonding Conductor Installed ,Torqued and Fastened to Array
-
Add media
-
Conduits Entering Are Sealed
-
Add media
-
Clean and Free of Debris
-
Add media
-
PV Wire Installed Neatly, As Per SLD and Labeled Correctly
-
Add media
-
Make and Model, Serial Number<br>
-
Add media
-
Combiner Installed As Per SLD and Location
Page Complete
-
Add signature
Cable Tray / Wire trough / Wire Basket
Cable Tray
-
Installed Securely, Fasten to Durablock
-
Add media
-
Bonded Every 50 Feet<br>Bonded to Recombiner
-
Add media
-
Cable Space Maintained
-
Add media
-
Covers Installed Correctly
-
Add media
Wire Trough
-
Expansion Joints On Non Continues Runs
-
Add media
-
Installed Securely, fasten to Durablock, Fasten to Array<br>
-
Add media
-
Lapp Connectors Installed Securely
-
Add media
-
Bonded to Corresponding Combiner Box
-
Add media
-
End Caps Installed
-
Add media
-
Covers and Latches Installed Screws All Installed With Gaskets
-
Add media
Wire Basket
-
Installed Securely, Fasten to Durablock, Fasten to Array
-
Add media
-
Every Piece Bonded
-
Add media
-
PV Wire Protected Leaving Basket
-
Add media
-
Covers Installed Correctly
-
Add media
Page Complete
-
Add signature
Array / Racking
-
Array Installed Straight and Square
-
Add media
-
General Pictures of the Array
-
Add media
-
Installed As Per Drawing <br>
-
Add media
-
Ballasted As Per Drawing
-
Add media
-
All Roof Protection Is Installed As Per Drawing
-
Add media
-
Module Type and Name Plate<br>
-
Add media
-
Hardware Torqued and Marked As Per Specs
-
Add media
-
Pv Wire Size, Wire Type and Connector Type
-
Add media
-
Pv Dressed Under Modules
-
Add media
-
Pvc Jumpers North to South Fastened to Racking
-
Add media
-
Home Runs Labeled Correctly
-
Add media
-
Teck Cables Dressed Under Modules
-
Add media
-
Array is Bonded
-
Add media
-
Clean and Free of Debris <br>
-
Add media
Page Complete
-
Add signature
Over All Site Conditions
Roof top
-
Any Signs of Degranulation
-
Any Left Behind Material, Safety Devices
-
Drain Flags Installed
-
Clean and Free of Debris
-
All Stone Spread Out Evenly
Site Services
-
Site trailer
-
Port-a-jon
-
Seacan
-
Bin or Dumpster
-
Safety Fence
-
Landscaping or Property Damage
-
Clean and Free of Debris
Page Complete
-
Add signature