Information
-
EVR Number:
-
Client:
-
Site:
-
Project Number :
-
Prepared on:
-
Location:
-
Prepared by:
-
Prepared by Signature:
Introduction
-
This Electrical Validation Report (EVR) is an overview of the existing electrical installation carried out by RMS LTD. It has been carried out in-line with BS7671:Amendment 3 20015
Please note that the items listed within this report are as noted at the time of inspection. -
The attached report presents findings of a visual and intrusive survey of the electrical Installation at:
-
Excluded from this report:
- Circuits Outside of Scope
- Supply Characteristics/Intake (Origin)
- Supply Characteristics/Intake (Origin) Outside of Scope
- Earthing & Bonding
- Earthing & Bonding Outside of Scope
- Switch Gear & Metering
- Switch Gear & Metering Outside of Scope
- Sub-Mains
- Sub-Mains Outside of Scope
- Distribution Boards
- Distribution Boards Outside of Scope
- Small Power System
- Small Power System Outside of Scope
- Lighting System
- Lighting System Outside of Scope
- DATA System
- DATA System Outside of Scope
- Fire Alarm System
- Fire Alarm System Outside of Scope
- Security Alarm System
- Security Alarm System Outside of Scope
- AV System
- AV System Outside of Scope
- PA System
- PA System Outside of Scope
- Electrical Risers
- Electrical Risers Outside of Scope
- Lift Motor Room
- Lift Motor Room Outside of Scope
- Plant Room
- Plant Room Outside of Scope
- Containment
- Containment Outside of Scope
- High Level/Ceiling Survey
- High Level/Ceiling Survey Outside of Scope
- Low Level/Floor Survey
- Low Level/Floor Survey Outside of Scope
-
Inspection start date:
-
This report provides a representation of the condition of the electrical installation on the following floors/areas:
Summary
-
Summary includes:
- Supply Characteristics/Intake (Origin)
- Earthing & Bonding
- Switch Gear & Metering
- Sub-Mains
- Distribution Boards
- Small Power System
- Lighting System
- DATA System
- Fire Alarm System
- Door Entry System
- Security Alarm System
- AV System
- PA System
- Electrical Riser
- Lift Motor Room
- Plant Room
- Containment
- High Level/Ceiling Survey
- Low Level/Floor Survey
- Recommendations
-
SUPPLY CHARACTERISTICS/INTAKE (ORIGIN)
-
SUPPLY CHARACTERISTICS/INTAKE (ORIGIN) SUMMARY
-
Add Photo
-
EARTHING & BONDING SUMMARY
-
EARTHING & BONDING SUMMARY
-
Add Photo
-
SWITCH GEAR & METERING SUMMARY
-
SWITCH GEAR & METERING SUMMARY
-
Add Photo
-
SUB-MAINS SUMMARY
-
SUB-MAINS SUMMARY
-
Add Photo
-
DISTRIBUTION BOARD SUMMARY
-
DISTRIBUTION BOARD SUMMARY
-
Add Photo
-
SMALL POWER SYSTEM SUMMARY
-
SMALL POWER SYSTEM SUMMARY
-
Add Photo
-
LIGHTING SYSTEM SUMMARY
-
LIGHTING SYSTEM SUMMARY
-
Add Photo
-
DATA SYSTEM SUMMARY
-
DATA SYSTEM SUMMARY
-
Add Photo
-
FIRE ALARM SYSTEM SUMMARY
-
FIRE ALARM SYSTEM SUMMARY
-
Add Photo
-
DOOR ENTRY SYSTEM SUMMARY
-
DOOR ENTRY SYSTEM SUMMARY
-
Add Photo
-
SECURITY ALARM SYSTEM SUMMARY
-
SECURITY ALARM SYSTEM SUMMARY
-
Add Photo
-
AV SYSTEM SUMMARY
-
AV SYSTEM SUMMARY
-
Add Photo
-
PA SYSTEM SUMMARY
-
PA SYSTEM SUMMARY
-
Add Photo
-
ELECTRICAL RISER SUMMARY
-
PA SYSTEM SUMMARY
-
Add Photo
-
LIFT MOTOR ROOM SUMMARY
-
LIFT MOTOR ROOM SUMMARY
-
Add Photo
-
PLANT ROOM SUMMARY
-
PLANT ROOM SUMMARY
-
Add Photo
-
CONTAINMENT SUMMARY
-
CONTAINMENT SUMMARY
-
Add Photo
-
HIGH LEVEL/CEILING SURVEY SUMMARY
-
HIGH LEVEL/CEILING SUMMARY
-
Add Photo
-
LOW LEVEL/FLOOR SURVEY SUMMARY
-
LOW LEVEL/FLOOR SURVEY SUMMARY
-
Add Photo
-
LOW LEVEL/FLOOR SURVEY SUMMARY
-
LOW LEVEL/FLOOR SURVEY SUMMARY
-
Add Photo
-
RECOMMENDATIONS
Supply Characteristics/Intake (Origin)
-
Incoming Supply Characteristic/Intake (Origin) Surveyed:
-
Nature of supply parameters by:
- Enquiry
- Measurement
- Calculation
- TBC
-
Incoming Supply Cable Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Incoming Supply Cable Size:
-
Incoming Supply Cable Conductor Material:
-
Incoming Supply Conductor Material:
-
Incoming Supply Voltage:
- TBC
- 400v
- 230v
- LIMITATION
- AGREED LIMITATION
- OTHER
-
Incoming Supply Voltage:
-
Ze Reading Recorded:
-
Ze Reading recorded or Reason for being unable to record a result:
-
Is Existing Certificate Available?
-
Existing Certificate No:
-
Photo of Certificate
-
Main Switch/Fuse type:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Main Switch/Fuse Type:
-
Main Switch/Fuse No. of poles:
-
Main Switch/Fuse Voltage Rating:
- TBC
- 400v
- 230v
- LIMITATION
- AGREED LIMITATION
- OTHER
-
Main Switch/Fuse Voltage Rating:
-
Main Switch/Fuse Current Rating:
- TBC
- LIMITATION
- OTHER
- 60A
- 63A
- 80A
- 100A
- 125A
- 200A
- 400A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
-
Main Switch/Fuse Current Rating
-
Main Switch/Fuse Short Circuit Capacity:
-
Condition of Service Cables:
-
Reason For Unsatisfactory Condition:
-
Photo of Unsatisfactory Service Cables:
-
Condition of Service head:
-
Reason For Unsatisfactory Condition:
-
Photo of Unsatisfactory Service head:
-
Condition of Meter tails:
-
Reason For Unsatisfactory Condition:
-
Photo of Unsatisfactory Meter tails:
-
Condition of Metering equipment:
-
Reason For Unsatisfactory Condition:
-
Photo of Unsatisfactory Metering equipment:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
Earthing and Bonding
-
Main Earthing and Bonding Surveyed:
-
Earthing System:
- TN-C-S (PME)
- TN-S
- TN-C-S
- TT
- IT
- LIMITATION
- OTHER
-
Main Earthing Conductor Material:
-
Main Earthing Conductor Material:
-
Main Earthing Conductor Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Main Earthing Conductor Size:
-
Main Protective Bonding Conductors:
- Water Installation Pipe
- Oil Installation Pipe
- Gas Installation Pipe
- Structural Steel
- Lightning Protection
- OTHER
-
Water Installation Pipe Conductor Material:
-
Conductor Material:
-
Water Installation Pipe Conductor Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Conductor Size:
-
Oil Installation Pipe Conductor Material:
-
Conductor Material:
-
Oil Installation Pipe Conductor Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Conductor Size:
-
Gas Installation Pipe Conductor Material:
-
Conductor Material:
-
Gas Installation Pipe Conductor Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Conductor Size:
-
Structural Steel Conductor Material:
-
Conductor Material:
-
Structural Steel Conductor Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Conductor Size:
-
Lightning Protection Conductor Material:
-
Conductor Material:
-
Lightning Protection Conductor Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Conductor Size:
Main Protective Bonding Conductor
-
Main Protective Bonding Conductor
-
Conductor Material:
-
Conductor Material:
-
Conductor Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Conductor Size:
-
EQUIPOTENTIAL PROTECTIVE BONDING CONDUCTORS:
EQUIPOTENTIAL PROTECTIVE BONDING CONDUCTOR
-
EQUIPOTENTIAL PROTECTIVE BONDING CONDUCTOR
-
Conductor Material:
-
Conductor Material:
-
Conductor Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Conductor Size:
-
Condition Of Main Earthing Conductor (Cable, Crimps, Earthing Bar/Bolts)
-
Reason for Un-Satisfactory Condition:
-
Photo of Un-Satisfactory Main Earthing Conductor:
-
Condition Of Main Protective Bonding Conductors (Cable, Crimps, Earthing Bar/Bolts, Clamps)
Un-Satisfactory Main Protective Bonding Conductor
-
Reason for Un-Satisfactory Condition:
-
Photo of Un-Satisfactory Main Protective Bonding Conductor:
-
Condition Of EQUIPOTENTIAL PROTECTIVE BONDING CONDUCTORS (Cable, Crimps, Earthing Bar/Bolts, Clamps)
Unsatisfactory Equipotential Protective Bonding Conductor:
-
Reason for Un-Satisfactory Condition:
-
Photo of Un-Satisfactory Equipotential Protective Bonding Conductor:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
Mains Distribution Panels, Switch Gear, Metering & Sub-Mains
- Mains Distribution Panels, Switch Gear, Metering & Sub Mains Survey:
-
Main Distribution Panel Surveyed:
-
Panel Designation:
-
Panel Location:
-
Panel Manufacturer:
-
Panel Model:
-
Panel Mounting:
-
Incoming Panel Over Current Protective Device/Switch:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Over Current Protective Device:
-
Number of Poles:
-
Rating Amps:
- TBC
- 6A
- 10A
- 15A
- 16A
- 20A
- 25A
- 30A
- 32A
- 40A
- 50A
- 60A
- 63A
- 75A
- 100A
- 125A
- 135A
- 150A
- 160A
- 175A
- 185A
- 200A
- 225A
- 250A
- 300A
- 315A
- 320A
- 400A
- 450A
- 500A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
- OTHER
-
Rating Amps:
-
Type No.
-
Short Circuit Capacity:
-
Short Circuit Capacity:
-
Number of Ways in Panel:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Number of Ways in Panel Being Used:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Over Current Protective Device used in Panel:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Over Current Protective Device:
-
Number of Ways in Panel Spare:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Over Current Protective Device:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Over Current Protective Device:
-
Rating Amps:
- TBC
- 6A
- 10A
- 15A
- 16A
- 20A
- 25A
- 30A
- 32A
- 40A
- 50A
- 60A
- 63A
- 75A
- 100A
- 125A
- 135A
- 150A
- 160A
- 175A
- 185A
- 200A
- 225A
- 250A
- 300A
- 315A
- 320A
- 400A
- 450A
- 500A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
- OTHER
-
Rating Amps:
-
Type No.
-
Short Circuit Capacity:
-
Short Circuit Capacity:
-
Number of Spares with Main Switches Installed:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Condition Of Panel:
-
Reason For Un-Satisfactory Condition:
-
Photo of Un-Satisfactory Panel:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Metering Surveyed:
-
Number of Meters:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Number of Meters Surveyed:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Meter Manufacturer:
-
Mater Model:
-
Condition Of Meter:
-
Reason For Un-Satisfactory Condition:
-
Photo of Un-Satisfactory Meter:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Switch Gear Surveyed:
-
Switch Gear Manufacturer:
-
Switch Gear Model:
-
Switch Gear Designation:
-
Switch Gear Fused or Un-fused:
-
Switch Gear Rating:
- TBC
- LIMITATION
- OTHER
- 60A
- 63A
- 80A
- 100A
- 125A
- 200A
- 400A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
-
Switch Gear Rating Amps:
-
Switch Gear Fuse Rating:
- TBC
- LIMITATION
- OTHER
- 60A
- 63A
- 80A
- 100A
- 125A
- 200A
- 400A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
-
Switch Gear Fuse Rating Amps:
-
Type of Switch Fuse:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Type of Switch Fuse:
-
Condition Of
-
Reason For Un-Satisfactory Condition:
-
Photo of Un-Satisfactory
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Sub Mains Surveyed:
-
Number of Sub Mains within Panel/ Switch Gear:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Number of Sub Mains Surveyed:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Number of Sub Mains Tested:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Previous Test Certificates Available:
-
Picture of Test Certificates:
-
Sub Main Information:
Sub Main
-
Designation:
-
Load Connection Location:
-
Over Current Protective Device:
-
Over Current Protective Device:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Over Current Protective Device:
-
Rating Amps:
- TBC
- 6A
- 10A
- 15A
- 16A
- 20A
- 25A
- 30A
- 32A
- 40A
- 50A
- 60A
- 63A
- 75A
- 100A
- 125A
- 135A
- 150A
- 160A
- 175A
- 185A
- 200A
- 225A
- 250A
- 300A
- 315A
- 320A
- 400A
- 450A
- 500A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
- OTHER
-
Over Current Protective Device:
-
Type No.
-
Short Circuit Capacity:
-
Over Current Protective Device:
-
Supply connection Location:
-
Age of Cable in Years:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- 29
- 30
- 31
- 32
- 33
- 34
- 35
- 36
- 37
- 38
- 39
- 40
- OTHER
-
Cable Size:
- 16mm
- 25mm
- 35mm
- 50mm
- 70mm
- 95mm
- 120mm
- 150mm
- 185
- 240mm
- 300mm
- 400
- 500
- 630
- Non Varifiable
- Other
-
Cable Size
-
Number of Cores:
-
Cable Type:
- A. Thermoplastic Insulated/Sheathed Cable
- B. Thermoplastic Cable in Metallic Conduit
- C. Thermoplastic Cable in Non-Metallic Conduit
- D. Thermoplastic Cable in Metallic Trunking
- E. Thermoplastic Cable in Non-Metallic Trunking
- F. Thermoplastic/SWA Cables
- G. Thermosetting/SWA Cable
- H.Mineral Insulated Cable
- OTHER
-
Cable Type
-
Installation Reference Method:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Installation Reference Method:
Distribution Boards
-
Distribution Boards Surveyed
-
How Many Distribution Boards are Installed?
- None
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
-
Distribution Board
DB
-
DB Location:
-
DB Designation:
-
DB Manufacturer:
-
Add media
-
DB Model:
-
Add media
-
DB Number of Phases:
-
DB Main Switch Type:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Add media
-
Main Switch Number of Poles:
-
Main Switch Current Rating:
- TBC
- 6A
- 10A
- 15A
- 16A
- 20A
- 25A
- 30A
- 32A
- 40A
- 50A
- 60A
- 63A
- 75A
- 100A
- 125A
- 135A
- 150A
- 160A
- 175A
- 185A
- 200A
- 225A
- 250A
- 300A
- 315A
- 320A
- 400A
- 450A
- 500A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
- OTHER
-
Main Switch Voltage Rating:
- TBC
- 240V
- 400V
- 415V
- 630V
- 660V
-
Is DB Condition Satisfactory:
-
Summary of DB Defects:
-
Photo of Defects
-
Is DB Circuit Schedule Present and Up to Date:
-
Photo of Circuit Schedule:
-
Is there Adequate Protective Devices Installed:
-
Photo of RCD/RCBO
-
Photo of MCB
-
Existing Circuits Installed:
-
Is an up to Date Test Certificate Available:
-
Photo of Relevant Test Certificate:
-
Are any of the Existing Circuits outside of the contract area affected by works to be carried out
-
Existing Circuits outside of the contract Area affected by works to be carried out:
-
Photo of Circuits outside
-
Is any of the Existing circuits Unknown:
-
Information raised about Existing Unknown Circuits:
-
Add media
-
Tests Results Recorded:
-
Photo of test Results:
-
Test Results/Additional Information:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Additional Photos:
Add Additional Photos:
-
Additional Photos:
Small Power System
-
Small Power System Surveyed:
-
Small Power Circuits Surveyed:
-
Circuit Designation:
-
Circuit Description:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
R1/L & RN/N Size:
-
R2/CPC Size
-
Over Current Protective Device:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Over Current Protective Device Amp Rating:
- TBC
- 6A
- 10A
- 15A
- 16A
- 20A
- 25A
- 30A
- 32A
- 40A
- 50A
- 60A
- 63A
- 75A
- 100A
- 125A
- 135A
- 150A
- 160A
- 175A
- 185A
- 200A
- 225A
- 250A
- 300A
- 315A
- 320A
- 400A
- 450A
- 500A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
- OTHER
-
Number of Points Served:
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Small Power Accessories surveyed:
-
Fitting Manufacturer:
-
Fitting type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
Lighting System
-
Lighting System Surveyed:
-
Lighting Circuits Surveyed:
-
Circuit Designation:
-
Circuit Description:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
R1/L & RN/N Size:
-
R2/CPC Size
-
Over Current Protective Device:
- BS 5419 Isolator
- BS EN 60947-3 Isolator
- BS EN 60947-2 ACB
- BS EN 60947-2 MCCB
- BS EN 60947-2 MCB Type B
- BS EN 60947-2 MCB Type C
- BS EN 60947-2 MCB Type D
- BS 3871 MCB Type 1
- BS 3871 MCB Type 2
- BS 3871 MCB Type 3
- BS 3871 MCB Type 4
- BS EN 60898 MCB Type B
- BS EN 60898 MCB Type C
- BS EN 60898 MCB Type D
- BS 1361 HBC Domestic Type 1
- BS 1361 HBC Domestic Type 2
- BS 3036 Fuse Re-Wirable (semi enclosed)
- BS 88 Fuse HRC gG (General)
- BS 4293 RCD
- BS EN 61008 RCD
- BS EN 61009 RCD/RCBO Type B
- BS EN 61009 RCD/RCBO Type C
- BS EN 61009 RCD/RCBO Type D
- Other
-
Over Current Protective Device Amp Rating:
- TBC
- 6A
- 10A
- 15A
- 16A
- 20A
- 25A
- 30A
- 32A
- 40A
- 50A
- 60A
- 63A
- 75A
- 100A
- 125A
- 135A
- 150A
- 160A
- 175A
- 185A
- 200A
- 225A
- 250A
- 300A
- 315A
- 320A
- 400A
- 450A
- 500A
- 630A
- 800A
- 1000A
- 1250A
- 1600A
- 2000A
- 2500A
- 3200A
- OTHER
-
Number of Points Served:
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Light Fittings surveyed:
-
Fitting Manufacturer:
-
Fitting type:
-
Lamp Type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Lighting Control System Surveyed:
-
Lighting Control System Installed:
-
Lighting Control System Accessory:
-
Accessory Manufacturer:
-
Accessory type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
DATA System
-
DATA System Surveyed:
-
DATA Server Surveyed:
-
DATA Server Installed:
-
DATA Server Accessory:
-
Accessory Manufacturer:
-
Accessory type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
DATA Circuits Surveyed:
-
Circuit Designation:
-
Circuit Description:
-
Type of Wiring:
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
DATA Accessories surveyed:
-
Fitting Manufacturer:
-
Fitting type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
Fire Alarm System
-
Fire Alarm System Surveyed:
-
Fire Alarm Panel Surveyed:
-
Fire Alarm Panel Installed:
-
Fire Alarm Panel:
-
Fire Alarm Panel Manufacturer:
-
Fire Alarm Panel type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
-
Fire Alarm Current Maintainer:
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Fire Alarm Circuits Surveyed:
-
Circuit Designation:
-
Circuit Description:
-
Type of Wiring:
-
Size of Wiring:
-
Number of points Served:
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Fire Alarm Accessories surveyed:
-
Fitting Manufacturer:
-
Fitting type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
Security Alarm System
-
Security Alarm System Surveyed:
-
Security Alarm Panel Surveyed:
-
Security Alarm Panel Installed:
-
Security Alarm Panel:
-
Security Alarm Panel Manufacturer:
-
Security Alarm Panel type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
-
Security Alarm Current Maintainer:
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Security Alarm Circuits Surveyed:
-
Circuit Designation:
-
Circuit Description:
-
Type of Wiring:
-
Size of Wiring:
-
Number of points Served:
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Security Alarm Accessories surveyed:
-
Fitting Manufacturer:
-
Fitting type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
Door Entry System
-
Door Entry System Surveyed:
-
Door Entry Panel Surveyed:
-
Door Entry Panel Installed:
-
Door Entry Panel:
-
Door Entry Panel Manufacturer:
-
Door Entry Panel type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
-
Door Entry System Current Maintainer:
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Door Entry System Circuits Surveyed:
-
Circuit Designation:
-
Circuit Description:
-
Type of Wiring:
-
Size of Wiring:
-
Number of points Served:
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
Door Entry Accessories surveyed:
-
Fitting Manufacturer:
-
Fitting type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
AV System
-
AV System Surveyed:
-
AV System Panel Surveyed:
-
AV System Panel Installed:
-
AV System Panel:
-
AV System Panel Manufacturer:
-
AV System Panel type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
-
Door Entry System Current Maintainer:
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
AV System Circuits Surveyed:
-
Circuit Designation:
-
Circuit Description:
-
Type of Wiring:
-
Size of Wiring:
-
Number of points Served:
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
AV Accessories surveyed:
-
Fitting Manufacturer:
-
Fitting type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
PA System
-
PA System Surveyed:
-
PA System Panel Surveyed:
-
PA System Panel Installed:
-
PA System Panel:
-
PA System Panel Manufacturer:
-
PA System Panel type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
-
PA System Current Maintainer:
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
PA System Circuits Surveyed:
-
Circuit Designation:
-
Circuit Description:
-
Type of Wiring:
-
Size of Wiring:
-
Number of points Served:
-
Is Condition Satisfactory:
-
Reason for Unsatisfactory Condition:
Photo:
-
Insert Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Additional Information:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
-
PA Accessories surveyed:
-
Fitting Manufacturer:
-
Fitting type:
-
Number installed:
-
Location Installed:
-
Type of Wiring:
- A. Installed in Conduit in Thermally insulating wall
- B. Enclosed in Conduit or Trunking or in a Wall
- C. Clipped Direct
- D. Direct in the ground or in ducting
- E. Free Air/perforated cable tray (multi-core cable)
- F. Free Air/perforated cable tray (single-core cable)
- G. Free Air/Flat spaced by one cable diameter
- OTHER
-
Attach photo
-
Is Condition Satisfactory:
Photo:
-
Insert Photo:
-
Reason for Unsatisfactory Condition:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Photo:
-
Existing Testing/Commissioning Certificate available;
-
Photo of Certificate:
-
Additional Information:
-
Test Results Recorded:
-
Photo:
-
Test Results/Additional Information:
Electrical Risers
-
Electrical Risers Surveyed:
-
Details
LOCATION
-
Location:
-
Number of Distribution Boards Installed:
-
Other equipment installed
-
Details:
-
Photo
-
Additional Details ?
-
Additional Details
Item
-
Designation:
-
Purpose:
-
Observation:
-
Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Add media
Lift Motor Room
-
Lift Motor Room Surveyed:
-
Details
LOCATION
-
Location:
-
Lift Manufacturer:
-
Current Lift Maintainer:
Photo:
-
Photo:
-
Relevant Information:
-
Other equipment installed
-
Details:
-
Photo
-
Additional Details ?
-
Additional Details
Item
-
Designation:
-
Purpose:
-
Observation:
-
Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Add media
Plant Room
-
Plant Room Surveyed:
-
Details
LOCATION
-
Location:
-
Plant Manufacturer:
-
Current Plant Maintainer:
Photo:
-
Photo:
-
Relevant Information:
-
Other equipment installed
-
Details:
-
Photo
-
Additional Details ?
-
Additional Details
Item
-
Designation:
-
Purpose:
-
Observation:
-
Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Add media
Containment
-
Containment Surveyed:
Containment:
-
Containment Type:
-
Location of Installation:
-
Containment Manufacturer:
-
Containment Size:
-
Approximate length Installed:
-
Containment Purpose:
-
Method of Support:
Photo:
-
Photo:
-
Is Condition Satisfactory:
-
Reason For Unsatisfactory Condition:
Photo:
-
Photo:
-
Additional Comments or Observations:
-
Additional Comments or Observations:
-
Existing Record Drawings/Tech Subs Available:
-
Add media
-
Additional Information:
High Level/Ceiling Survey
-
High Level/Ceiling Surveyed:
Add Survey:
-
Area Surveyed:
-
Ceiling Type/Material:
-
Ceiling Accessible:
Add Photo:
-
Photo:
-
Additional Information:
-
Measurement From Finished Floor Level to Ceiling Underside:
-
Measurement From Ceiling to Slab:
-
Void Areas over 600mm to be aware of:
Photo of Area:
-
Add media
-
Additional Information:
-
Additional Comments or Observations:
Add Photo:
-
Photo:
-
Additional Comments or Observations:
Low Level/Floor Survey
-
Low Level/Floor Surveyed:
Add Survey:
-
Area Surveyed:
-
Floor Type/Material:
-
Floor Accessible:
Add Photo:
-
Photo:
-
Additional Information:
-
Measurement From Finished Floor Level to Ceiling Underside:
-
Measurement From Slab to Finished Floor Level:
-
Void Areas over 600mm to be aware of:
Photo of Area:
-
Add media
-
Additional Information:
-
Additional Comments or Observations:
Add Photo:
-
Photo:
-
Additional Comments or Observations:
Recommendations
-
RECOMMENDATIONS
-
Recommendations
Item
-
Recommendations: