Title Page
-
Document No.
-
Client/ Site
-
Location
Checmical Safety, Storage & Hazardous Materials
-
Flammable/combustible liquids not stored/kept near exits (IFC 5704.3.3.3)
-
Quantities >10 gals stored in cabinets (IFC 5704.3.4.4)
-
No basement storage unless sprinklered (IFC 5704.3.5.1)
-
Storage exceeds Maximum Allowable Quantities (IFC Table 5003.1.1)
-
Compressed gas cylinder security (IFC 5303.5)
-
704 Label accurate/current (IFC 5003.5)
-
Proper separation of incompatible chemicals (IFC 5003.9.8)
-
Shelving equipped with restraints from falling (IFC 5003.9.9)
-
Sash closed when fume hood unattended (recognized standard)
-
Compressed gas cylinders secured with chain at least .25" (recognized standard)
-
All chemicals properly labeled (recognized standard)
-
All chemicals dated when first opened (recognized standard)
-
Chemicals shall not be stored in fume hood (recognized standard)
Construction Features & Fire Resistance
-
Fire rated construction present/maintained (IFC 703.1)
-
Rated fire doors operational & not blocked (IFC 703.2)
Exiting & Egress
-
Exits, aisles and corridors free of obstructions (IFC 1030.3)
-
Adequate number of exits (IFC 1004.1.1, 1015, 1021, 1104.24)
-
Exit signage present & operable (IFC 1011, 1104.3)
-
Emergency lighting present & operational (IFC 1006, 1104.5)
-
Exit corridors rated (IFC 1018.1, 1104.17)
-
Vertical openings of 2 or more stories shall be protected (IFC 1103.4)
-
Vertical openings of 3-5 stories protected with sprinklers (IFC 1103.4.2)
Electrical
-
Electrical hazards (IFC 605.1, 605.6)
-
Electrical appliances, fixtures, cords in good condition (IFC 605.7)
-
Multiplug adapters per NFPA 70 (IFC 605.4)
-
Extension cords not a substitute for permanent wiring (IFC 605.9)
-
36" clearance for electrical panels (IFC 605.3)
-
GFCI outlets near water source (IFC 605.1)
Elevator Machine Room
-
Free of storage (ASME A17.1)
-
Portable fire extinguisher at least 2A:10B:C (ASME A17.1)
Kitchen Extinguishing & Suppression Systems
-
Kitchen hood system fuel shutoff (IFC 904.11.2)
-
Kitchen hood suppression system maintained (IFC 609.3, 904.11.6)
Occupant Load
-
Occupant load exceeded (IFC 1004, Table 1015.1)
Portable Fire Extinguishers
-
Readily accessible, not obstructed (IFC 906.5, 906.6)
-
Travel distance not exceeded (IFC 906.1, 906.3)
-
Tested/inspected annually (IFC 901.6.1)
-
Extinguishers must be mounted (IFC 906.7)
Sprinker Systems
-
Controls are readily accessible (IFC 509.2)
-
Wrench & spare sprinklers available (IFC 903.3.1)
Storage
-
Storage neat & orderly (IFC 315.3)
-
Combustibles prohibited in mechanical/electrical rooms (IFC 315.3.3)
-
Attic storage prohibited if unprotected (IFC 315.3.4)
-
Concealed space storage prohibited if unprotected (IFC 315.3.4)
-
Storage maintained, <2" ceiling unsprinkled, <18" sprinkled ((IFC 315.3.1)
Sign off
-
Signature