Information
-
job no
-
Client
-
Site
-
Conducted on
-
Prepared by
-
Location
-
Engineer on site
-
The installation is in accordance with the specification and any changes have been agreed with the customer in writing
-
All cables into door panel clearly marked
-
Is the door panel secured properly to prevent water ingress
-
Door panel
-
Door panel manufacturer and model number including camera unit / digital keypad any other parts
-
Has the audio on the panel been set to suit the environment it being used ( sound level)
-
What calling mode is the system
-
Has a functional panel been installed and have all buttons been programed and tested
-
Is the panel audio or audio/video
-
What type of lock has been installed
-
Lock manufacturer and part number
-
Is the lock a fail safe or fail secure lock
-
Has a MOV or diode been installed on the lock
-
Has the lock been checked for correct operations
-
Has the lock been installed by SCCI
-
Lock
-
Cables are segregated and suitably supported in riser and central equipment cabinet
-
Field wiring is labelled and adequately terminated in all devices/controllers.
-
Manufacturer and model no of power supply equipment and control equipment and any switch units
-
State location of central equipment and junction box within building
-
Central equipment
-
Do you require a door key to access central equipment
-
What type of key is required
-
What access equipment do you require
- steps
- ladders
- hop up
-
Control equipment / rise cabling
-
Manufacturer and model of handset and back plate
-
Handsets have been installed correctly and addressed
-
Have the following functional test been performed (door release/speech/audio)
-
If no to the above question give details
-
Picture of handset installed with flat number on written card for less then 20 handsets
-
Mains connection is permanently connected and NOT by plug and socket
-
Is the mains supply a 3A unswitched fuse connection unit
-
All reader, keypad and egress button have been checked for correct operation and response time
-
Reader/PTE/BGU
-
The operation of each door has been checked for correct operation under fire/emergency conditions.
-
At least 5 tags have been issued and checked for correct operation
-
Has the system got a CPS installed
-
Is the CPS in full working order
paper work
-
The customer has been shown how to operate the system and full training has been offered.
-
System training has been given to
-
Signature
-
User manual and schematic drawing printouts are available to the operator.
-
Service telephone label complete with contract number is located appropriately
-
Have all the cables in the riser been clipped or tied and made good
-
All surplus materials and equipment have been cleared from the site.
-
The customer premises have been left in a tidy condition.
-
Is the system in full operation condition
-
Have any major joint have been made if yes list locations
-
Notes or comments
-
I confirm that the installation is complete as recorded above and the system has passed its acceptance test (any items which are not complete has been recorded )