Title Page
-
Audit Title
-
Client / Site
-
Date on site
-
Prepared by
-
Site address
Project Details
-
Customer Contact name
-
Customer contact phone
-
Customer Email
-
Add location
-
Work Order Number
-
Commissioning details
-
FSE involved
EVlink Information
-
Description
-
Model Number
-
Serial Number
-
Firmware version
-
Firmware Build
Test Equipment Used
-
1. Laptop
-
2. EV Simulator Tool
-
3. Fluke multi-meter
-
4. Sparkymate
Commissioning
-
Sign in / H&S
-
Documentation completion: SENZ HIRA and customer sign in.
-
Established work area, equipment setup and isolations where required.
-
Visual checks
-
Visual check of charger externals for damage/wear.
-
Visual check of internal hardware.
Uploads
-
Upload customer configuration parameters.
-
Upload customer maintenance logs.
-
Firmware revision check
Tests - Socket #1
-
Check cable integrity
-
a. Visual Cable Check
-
b. Electrical Cable Check (Earth Continuity less than 1 Ohm)
-
c. Insulation Resistance Check Earth to Red phase (greater than 1 MOhm)
-
d. Insulation Resistance Check Earth to White phase (greater than 1 MOhm)
-
e. Insulation Resistance Check Earth to Blue phase (greater than 1 MOhm)
-
f. Insulation Resistance Check Earth to Neutral (greater than 1 MOhm)
-
Trip the Power Auxiliary Breaker (welded contactor test) to test under voltage release
-
Test RCD charger using Schneider Electric Vehicle Simulation Tool
-
Confirm RCD tripping time is less than 300 milliseconds @ 30 mA – Red Phase
-
Confirm RCD tripping time is less than 300 milliseconds @ 30 mA – White Phase
-
Confirm RCD tripping time is less than 300 milliseconds @ 30 mA – Blue Phase
-
Test earth continuity monitoring with EV Simulation Tool
-
Function test with Schneider Electric vehicle simulation tool.
-
Function test charger using a customer supplied vehicle (if applicable/vehicle readily available).
Tests - Socket #2
-
Check cable integrity
-
a. Visual Cable Check
-
b. Electrical Cable Check (Earth Continuity less than 1 Ohm)
-
c. Insulation Resistance Check Earth to Red phase (greater than 1 MOhm)
-
d. Insulation Resistance Check Earth to White phase (greater than 1 MOhm)
-
e. Insulation Resistance Check Earth to Blue phase (greater than 1 MOhm)
-
f. Insulation Resistance Check Earth to Neutral (greater than 1 MOhm)
-
Trip the Power Auxiliary Breaker (welded contactor test) to test under voltage release
-
Test RCD charger using Schneider Electric Vehicle Simulation Tool
-
Confirm RCD tripping time is less than 300 milliseconds @ 30 mA – Red Phase
-
Confirm RCD tripping time is less than 300 milliseconds @ 30 mA – White Phase
-
Confirm RCD tripping time is less than 300 milliseconds @ 30 mA – Blue Phase
-
Test earth continuity monitoring with EV Simulation Tool
-
Function test with Schneider Electric vehicle simulation tool.
-
Function test charger using a customer supplied vehicle (if applicable/vehicle readily available).
Record
-
Record the Type of Socket #1 RCD and confirm compliance (Type B)
-
Record the Type of Socket #2 RCD and confirm compliance (Type B)
-
Verify/Record the Rating of Socket #1 RCD is compliant (current rating in Amps and Sensitivity in mA)
-
Verify/Record the Rating of Socket #2 RCD is compliant (current rating in Amps and Sensitivity in mA)
-
Record supply circuit breaker rating – Socket #1 (Amps)
-
Record supply circuit breaker rating – Socket #2 - result below (Amps)
-
Verify the correct Rating of all overcurrent protection
Completion
-
Record assessment/inspection on the Electrical and Gas High Risk Database
-
Attach Schneider Electric service/inspection tag.
-
Removed isolations where required and cleared site appropriately.
-
Report completion.
Findings
-
List all the Findings (click "Add Finding")
Finding
-
Add media
Conclusions
-
List all the Conclusions (click "Add Conclusion")
Conclusion
Recommendations
-
List all the Recommendations (click "Add Recommendation")
Recommendation
Completion
-
Sign off
-
For further information and maintenance offers, please contact our Services sales team on 0800 652 999.