Title Page

  • Site conducted

  • Conducted on

  • Prepared by

  • Location

Battery System

  • Check condition of environment, and remove or create action to remove hazardous materials if any exist

  • Check condition of battery inverter including: secure termination of battery and AC cabling N / A / E; comms cabling; two wire auto start; glands secured so no points of entry for vermin or insects;

  • Check voltage of battery supply at battery inverter and at battery bank

  • Check DC wiring from Battery inverter, through DC isolator, to battery bank. Including terminals, general condition, entry points, mechanically secured

  • Update Firmware - battery inverter

  • Update Firmware - battery BMS

  • Check the fallback function, turn on the PV supplies. Unplug the RS485 lead (RJ45) in the SP PRO.<br>Check that each of the connected grid inverter’s output drops to zero after 10 seconds.

  • Confirm signage in place compliant with AS5139 / AS4509 including - ES, Isc (sum if multiple parallel banks), Voltage, Danger, relevant hazard signs, DC isolator, “battery” for cabling, shutdown procedure (adjacent to PCE), system location noted at Switchboard.

  • Checklist as per 5139:

  • Confirm compliance with AS5139 checklist and note any exceptions

Solar System

  • Site: clean, no debris on or under array

  • PV modules: DC isolators have good integrity; integrity of glands for isolator; no fractures, browning corrosion of panels; no moisture penetration of panels; Conduit has good mechanical integrity and fixings; integrity of glands for isolators

  • Wiring: good mechanical integrity; integrity of penetrations; integrity of earthing system; wiring secured to frame system and not lying on roof.

  • System tests results: Voltage Open Circuit; Isolation device operates correctly; Power production matches array size, orientation, tilt, weather and age of system;

  • Check mounting system: feet secure; rails secure; panels secure; wiring secured to array mounting structure where necessary.

  • Clean solar panels and remove any debris

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.