Title Page

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Location
  • Prepared by

Site Information

  • Address
  • Site number of phases

  • CoES number

  • Meter location

  • Please specify

  • Meter number/s

  • Meter
  • Meter number

  • Number of phases

Array

  • PV array Open Circuit Voltage (Voc)

  • PV array Short Circuit Current (Isc)

  • Bonding earth correctly installed using purposely designed clamps.

  • Bonding earth protected against corrosion

  • Bonding earth continuity <0.5Ω

  • PV array cabling protected against external influences

  • PV array cabling secured using only Stainless Steel cable ties or clips.

  • Roof cable penetration using approved means. (Dektite etc)

  • Array/s isolator correctly rated for current and voltage, correctly wired, IP rating and UV protection.

  • PV array isolator labelled "PV ARRAY D.C. ISOLATOR".

  • All junction boxes labelled " WARNING HAZARDOUS DC VOLTAGE"

  • Array cable in HD conduit for entire length

  • Array cable conduit labelled "SOLAR DC" at intervals no greater 2 metres.

Inverter/s

  • String Inverter

  • Inverter
  • Array isolator correctly rated for current and voltage, correctly wired, IP rating and UV protection.

  • PV array isolator labelled "PV ARRAY D.C. ISOLATOR".

  • Array isolators labelled "WARNING: MULTIPLE D.C. SOURCES TURN OFF ALL TO EQUIPMENT" if required.

  • Shut down procedure containing the wording "WARNING: P.V. ARRAY D.C. ISOLATORS DO NOT DE-ENERGISE THE P.V. ARRAY OR ARRAY CABLING" permanently attached adjacent to the inverter. (AS/NZS 5033 - 2014 Clause 5.5.2)

  • Inverter location, fixing, height, UV and IP ratings.

  • Inverter protective earthing resistance.

  • A.C. isolator located near the inverter correctly rated, installed and wired. (If required)

  • A.C. wiring correct polarity, current rating, fault loop impedance and mechanical protection.

  • Inverter anti islanding requirements.

  • Make

  • Model

  • kW Rating

  • Serial Number

  • Location

Switchboard

  • Solar Supply Main Switch for rating, circuit arrangement and labelling.

  • Normal Supply Main Switch labelled.

  • No R.C.D's between inverter and grid supply.

  • Select inverter type.

  • Solar Neutral labelled.

  • D.C. Voltage, D.C. Current and Array Location label attached to the Main Switchboard.

  • "WARNING: DUAL SUPPLY" label attached to the Main Switchboard, the switchboard that the inverter is connected to and any intermediate switchboard.

  • "WARNING: DUAL SUPPLY" "Green" label attached to the Main Switchboard, the switchboard that the inverter is connected to, any intermediate switchboard and all fire indicator panels.

  • Inverter location label at the Main Switchboard. (If required)

  • P.V. Label attached to the Main Switchboard.

  • Consumers terminals labelled "WARNING: DUAL SUPPLY".

  • Sign

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.