Title Page

  • Builder

  • Builder

  • Subdivision

  • Job #

  • Installer(s)

  • Inspected by:

  • Conducted on

Rough-in

  • Take Picture/Front Page Of Work Ticket Full Size

  • Take A Photo of Just the Equipment Stickers on the Work Ticket

Recordables

  • Are there any issues?

  • Recordable
  • Call Type

  • Problem

  • Notes about recordable

  • Pictures of recordable:

Equipment

  • Access Attic/Closet 23x30

  • Service Platform & Clearance (30"W) (24"W x 20'L)

  • Furnace Level/Hung as High as Possible

  • Coil Level 1/2" Grade to Drain Fittings/90% Furnaces 1/2"-MUST TAKE PICTURE WITH LEVEL ON IT-

  • Add media

  • Hangers Secured with Screws

  • Secondary Drain Pan Secured with Slope Towards PVC Termination-MUST TAKE PICTURE-

  • Add media

  • Drainage For 90% Equipment Install and Sealed Properly-MUST TAKE PICTURE-

  • Add media

  • Flue Vent Run Straight up Through Roof/Level/1" Clearance

  • PVC Vent Run Straight/Properly Sealed/90% Equipment

  • Roof Penetration is 24" away from valley or ridge

Refrigerant Lines

  • Soldered at Coil *No Mastic*-MUST TAKE PICTURE-

  • Add media

  • Insulated with Armaflex

  • Strapped every 5 feet

  • Spacer Block at Roof Line

  • Centered in Wall Cavity

  • Nail Plates Installed

  • Flashing at Wall Penetration/Installed Properly

  • Flashing at Celling Penetration/Installed Properly

  • Labeled Tonnage-outside-

  • Draft Stop in Walls

  • Wire run to Equipment and Secured-MUST TAKE PICTURE-

  • Add media

  • Line set Pressurize With Nitrogen to 300 Pounds-MUST TAKE PICTURE-

  • Add media

Drain Lines

  • "P" Trap Level *No Mastic at Coil Starter*-MUST TAKE PICTURE-

  • Add media

  • Pipe Run Straight-no bows-

  • Minimum 1/4" per Foot Slope

  • Strapped Every 4 Feet

  • Terminated Outside with Cap (primary)

  • Terminated over Window with Cap (secondary)

  • Nail Plates Installed

  • Draft Stop in Walls

  • Water Test

T-Tops/Caps

  • All Roof Components(T-Tops) secured together in Attic next to Equipment-MUST TAKE PICTURE-

  • Add media

  • Flue caps installed on flue pipes - MUST TAKE A PICTURE

  • Add media

Wiring

  • Thermostat Wire Installed 60" Off Floor-MUST TAKE PICTURE-

  • Add media

  • Blocked at Wall

  • Wire Run From T-stat Location to Equipment-MUST TAKE PICTURE-

  • Add media

  • Wire Connected and Run from Motorized Zone Dumper to Equipment/Secured-MUST TAKE PICTURE-

  • Add media

  • Wire Connected and Run from Fresh Air Motorized Dumper to T-stat Location -MUST TAKE PICTURE-

  • Add media

  • Wires Run from Temperature Sensors Location to T-stat Location-MUST TAKE PICTURE-

  • Add media

  • Wire Run( Jump Wire ) from T-stat Location to FRV Location-MUST TAKE PICTURE-

  • Add media

Ductwork/Flex

  • Plenums Secured, Sealed

  • Collars Sealed

  • Damper Disk Installed on all Collars/Equipment

  • Backdraft Dumper For FRESH AIR Installed Properly

  • Fresh Air Assembly (SONORAN VENT) Installed Properly-MUST TAKE A PICTURE -

  • Add media

  • Fresh air flex that is run through the roof is 24" away from any ridge or valley

  • BYPASS DAMPER Installed Properly/Correct Air Flow Direction/Arm-MUST TAKE PICTURE-

  • Add media

  • Flex Inner Liner Sealed/Panduit Straps

  • Outer Liner Panduit Straps

  • Hanging Strap Every 4 feet

  • Bends Un-restricted

  • Flex Runs Level

  • Duct Chases Draft Stop

  • Flex Clear of Roofline

  • Flex Free of Tears

  • S/A Ceiling Boxes Installed

  • R/A Boxes Installed

  • R/A Jump Ducts Installed Bedrooms

  • Flex Joint Spliced with Metal Pipe/Collar

Exhaust Fans

  • Exhaust Fans Installed Per Plan/Bath/Landry

  • Aluminum Flex Strapped Every 4 Feet

  • Terminated Through Roof Line With 4"KD Pipe/Secured With Metal Strap and 3 Screws

  • Fan termination through the roof is 24" away from any ridge or valley

  • Fan Damper Free to Close and Open

Vent Work

  • Dryer Vent Box Installed-MUST TAKE PICTURE-

  • Add media

  • Dryer Vent Box Framed by Other-MUST TAKE PICTURE-

  • Add media

  • Clean Cut Pipe in Box/Level/4" Long in D/Box

  • 25 Feet Max Length 4"

  • Strapped Every 4 Feet

  • Pipe Taped *No Screws* Dryers

  • Nail/Wall Plates Installed

  • Draft Stop

  • Terminated with T-Top/Wall Cap & Damper

  • Dry vent run through the roof is 24" away from any ridge or valley

  • Hood Vent Pipe/Wall Stack Level

  • 3 Screws per Joint/Mastic Sealed

  • Collar thru Wall for Sheetrock -2"

  • Terminated with T-Top/Wall Cap & Damper

  • Hood vent run through the roof is 24" away from any ridge or valley

  • Draft Stop

  • Proper Height & Location Hood Vent

Water Heater Flue Pipe

  • 1" Clearance from Combustibles

  • Strapped Every 4 Feet

  • Pipe Level

  • Water heater flue pipe penetration through the roof is 24" away from any valleys or ridges

  • Insulation Standoff Installed and Secured

  • 6" Below Ceiling

Other

  • Combustion Air Vents installed/12" From Floor/Ceiling

  • QUICK-FLASH Installed Properly(PVC,etc)

  • All Wall Caps Installed/Leveled/Dumpers Free/

Notes

  • Items corrected:

  • Notes:

  • Additional Pictures:

Finish

  • Signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.