Title Page
-
Site conducted
-
Site Address
-
Report By
-
Date
Transport & Lifting
-
Transport - All components were correctly loaded and fastened as per transportation document, report any damage.
-
Photographs Required
-
Photographs Required
-
All components weights specified on nameplates are correct as per freight layout/craning & excavation document
-
Has crane operator been advised of the changes to component weights
-
Is a spreader bar being used for lifting of components
-
Photographs required
-
Have you notified the Construction Manager for approval to proceed prior to commencing any lifts
-
Site instruction , approval form (document # HS-Site-006) has been signed by Client
-
Crane lifts commenced
Pump Station Components
-
All components have been checked for cracking. Is there any evidence of cracking.
-
Photographs required
-
Details:
-
Epoxy coating has been applied correctly to all surfaces as per IFC Civil/Mechanical drawings. The application is free from pin<br>holes and air bubbles etc.
-
Photographs required
-
Photographs Required
-
Details
-
HDPE liner installed as specified on the IFC Civil/Mechanical drawings.
-
HDPE liner is not damaged and is free from any air bubbles, sctaches or tears
-
Photographs Required
-
Photographs Required
-
Details
-
Increment Core Hole & Conduits – Positions and dimensions identified, inlets and rising mains as per <br>drawings supplied
-
Photographs required
-
Photographs Required
-
Details
-
Inlet Stub – Check installation matches drawing, bolt holes, level etc.
-
Photographs required
-
Photographs Required
-
Details
-
Has Knivegate Valve been fitted to inlet pipe prior to lowering segment into the ground
-
Has knive gate been fully closed
-
Photographs required
-
Have bolts been torqued
-
Photographs required of witness markings
-
Has a blind flange or plug been fitted to inlet stub to prevent flooding of pump station
-
Photograph required
-
Cover Slab checked and there are no evident cracks. Surface finish is of acceptable standard
-
Photograph required
-
Photographs Required
-
Deatils
-
Cover Slab – Check lid orientation alignment is correct and all lids are easily opened
-
Photo Required
-
Photographs Required
-
Details
-
Cover Slab – Locking mechanisms are correctly aligned and padlocks can be easily applied
-
Photo Required
-
Photographs Required
-
Details
-
Cover Slab – Lid sealing strips have been correctly installed
-
Photo Required
-
Photographs Required
-
Details
-
Cover Slab – Check I/O spindle orientation is correct.
-
Photograph required
-
Photographs Required
-
Details
-
Cover Slab – Check conduit entry mains power core hole position.
-
Photograph required
-
Cover Slab – Check positions of educt vent / vent core hole / bolt patterns.
-
Photograph required
Valve Pit Components
-
Is there a separate valve pit to be installed?
-
All components have been checked for cracking. Is there any evidence of cracking.
-
Photo Required
-
Photographs Required
-
Epoxy coating has been applied correctly to all surfaces as per IFC Civil/Mechanical drawings. The application is free from pin<br>holes and air bubbles etc.
-
Photo Required
-
Photographs Required
-
Details
-
Core Hole & Conduits – Positions and dimensions identified as being correct with drawing supplied
-
Photograph required
-
Photographs Required
-
Deatils
-
Cover Slab checked and there are no evident cracks. Surface finish is of acceptable standard
-
Photograph required
-
Photographs Required
-
Details
-
Cover Slab – Check lid orientation alignment is correct and all lids are easily opened
-
Photograph required
-
Photographs Required
-
Details
-
Cover Slab – Locking mechanisms are correctly aligned and padlocks can be easily applied
-
Photograph required
-
Photographs Required
-
Details
-
Cover Slab – Lid sealing strips have been correctly installed
-
Photograph required
-
Photographs Required
-
Details
Flow Meter Pit Components
-
Is there a flow meter pit to be installed?
-
All components have been checked for cracking. There is no evidence of cracking.
-
Photograph required
-
Details
-
Epoxy coating has been applied correctly to all surfaces as per IFC Civil/Mechanical drawings. The application is free from pin<br>holes and air bubbles etc.
-
Photograph required
-
Photographs Required
-
Details
-
Core Hole & Conduits – Positions and dimensions identified as being correct with drawing supplied
-
Photograph required
-
Photographs Required
-
Details
-
Cover Slab checked and there are no evident cracks. Surface finish is of acceptable standard
-
Photograph required
-
Photographs Required
-
Details
-
Cover Slab – Check lid orientation alignment is correct.
-
Photo Required
-
Photographs Required
-
Details
Civil Installation
-
Excavation – for pump station correctly prepared in accordance with IFC Civil/Mechanical drawings backfill requirements<br>, Craning and excavation document.
-
Photograph required
-
Photograph required
-
Details:
-
Excavation Base – compacted and finished to RL depth in accordance with IFC Civil/Mechanical drawings backfill requirements<br>, Craning and excavation document. Check with civil contractor
-
Photograph required
-
Photographs required
-
Details
-
Base Unit – Installed with orientation to suit gravity inlet-sewer and rising main
-
Photograph required
-
Photograph required
-
Details:
-
Base unit installation procedure – adhered to by Civil Contractor in accordance with specifications,and is level
-
Photograph required
-
Photograph required
-
Details:
-
Base Unit diameter
-
Top and the 45 degree rebates have been sprayed with aerosol primer prior to applying mastic
-
Photograph required
-
Base Component - 2 runs to top rebate and 1 run to 45 degree rebate of mastic has been applied
-
Photograph required
-
Underneath side of all increments being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Top of all increments being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Increments - 2 runs to top rebate and 1 run to 45 degree rebate of mastic has been applied
-
Photograph required
-
Increments – Installed correctly as per IFC Civil/Mechanical drawings (with civil contractor) ensure level before installing<br>next increment
-
Photograph required
-
Top of last increment/intergal valve chamber being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
3 runs of mastic has been applied to top face of last increment/intergal valve chamber
-
Photograph required
-
Underneath side of coverslab being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Coverslab has been placed minium of 10mm proud of internal walls to ensure pump claw does not clash
-
Photograph required
-
Top & 45 degree rebates has been sprayed with aerosol primer prior to applying mastic
-
Photograph required
-
Base Component - 2 runs to top rebate and 1 run to 45 degree rebate of mastic has been applied
-
Photograph required
-
Underneath side of all increments being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Top of all increments being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Increments - 1run to top rebate and 1 run to 45 degree rebate of mastic has been applied
-
Photograph required
-
Increments – Installed correctly as per IFC Civil/Mechanical drawings (with civil contractor) ensure level before installing<br>next increment
-
Photograph required
-
Top of last increment/intergal valve chamber being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
3 runs of mastic has been applied to top face of last increment/intergal valve chamber
-
Photograph required
-
Underneath side of coverslab being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Coverslab has been placed minium of 10mm proud of internal walls to ensure pump claw does not clash
-
Photograph required
-
Top & 45 degree rebates has been sprayed with aerosol primer prior to applying mastic
-
Photograph required
-
Base Component - 1 run to top rebate and 1 run to 45 degree rebate of mastic has been applied
-
Photograph required
-
Underneath side of all increments being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Top of all increments being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Increments - 1 run to top rebate and 1 run to 45 degree rebate of mastic has been applied
-
Photograph required
-
Increments – Installed correctly as per IFC Civil/Mechanical drawings (with civil contractor) ensure level before installing<br>next increment
-
Photograph required
-
Top of last increment/intergal valve chamber being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
3 runs of mastic has been applied to top face of last increment/intergal valve chamber
-
Photograph required
-
Underneath side of coverslab being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
Coverslab has been placed minium of 10mm proud of internal walls to ensure pump claw does not clash
-
Photograph required
-
Is gator wrapping of increments joins required ? Check IFC Civil /Mechanical drawings for requirements
-
How many joints have been Gator wrapped
-
Gator Wrap - Ensure surfaces are clean - free from debri and Aerosol primer has been applied
-
Photograph required
-
Gator wrap has been placed as per manufacturers instructions.
-
Photograph required
-
Megapoxy has been applied to all below ground lifting lugs
-
Photographs required
-
Is a separate valve pit being installed
-
Excavation – Correctly prepared in accordance with IFC Civil/Mechanical drawings backfill requirements<br>, Craning and excavation document.
-
Photograph required
-
Photographs Required
-
Details
-
Excavation Base – compacted and finished to RL depth in accordance with IFC Civil/Mechanical drawings backfill requirements<br>, Craning and excavation document. Check with civil contractor
-
Photograph required
-
Photographs Required
-
Details
-
Top of valve pit being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
2 runs of mastic applied to top of valve pit
-
Photograph required
-
Coverslab placed as per IFC Civil/Mechanical drawings and is correctly aligned with pump station coverslab
-
Photograph required
-
Photographs Required
-
Details
-
Megapoxy has been applied to all below ground lifting lugs
-
Photographs required
-
Is a flow meter pit being installed
-
Excavation – Correctly prepared in accordance with IFC Civil/Mechanical drawings backfill requirements<br>, Craning and excavation document.
-
Photograph required
-
Photographs Required
-
Details
-
Excavation Base – compacted and finished to RL depth in accordance with IFC Civil/Mechanical drawings backfill requirements<br>, Craning and excavation document. Check with civil contractor
-
Photograph required
-
Photograph Required
-
Details
-
Top of valve pit being placed is free from dirt , mud etc. and has been sprayed with aerosol primer
-
Photograph required
-
2 runs of mastic applied to top of flow meter pit
-
Photograph required
-
Coverslab placed as per IFC Civil/Mechanical drawings and is correctly aligned with pump station /valve pit coverslabs
-
Photograph required
-
Photographs Required
-
Details
-
Megapoxy has been applied to all below ground lifting lugs
-
Photographs Required
-
All access lids have been locked with Aquatec padlocks
-
Photographs Required
Signatures
-
Add all additional photos here:
-
Have the drawings been red pen marked up ?
-
Notes/Comments:
-
Aquatec Representative:
-
Signature:
-
Date: