Title Page
-
Client's Name
-
Prepared by
-
Date and Time
-
Audit Location
- "Add Door"
-
ASSET NUMBER
-
LEVEL
-
LOCATION
-
TEST EVIDENCE AVAILABLE
- 1+ Certified door, certified installation, full maintenance records available.
- 1+ Certified door, certified installation, no maintenance records available.
- 1 Certified door.
- 2 Door with Project Specific Assessment from Warringtonfire.
- 2 Door with assessment and supporting records.
- 2 Door with test evidence and supporting records.
- 3 Door with manufacturer identifier.
- 4+ Flush door, no records (installed after 1987).
- 4 Joinery door no records.
- 4 Joinery door no records (installed before 1987).
- 4 Steel door no records
- NA
-
DOOR FUNCTION
- Single door/single action
- Single door/double action
- Double door/single action
- Double door/double action
- Single fire exit
- Double fire exit
-
INTENDED RATING
- FD30
- FD30S
- FD60
- FD60s
- FD90
- FD90s
- FD120
- FD120s
- NA
-
CONSTRUCTION
- Aluminum
- Glass
- Timber
- Steel
- Timber Steel Clad
- Glass Aluminium Frame
- Glass Steel Frame
SUPPORTING STRUCTURE
-
The supporting structure is suitable?
INSTALLATION
-
Has the installation been carried out correctly?
FRAME
-
The frame is suitable and in good condition?
- Pass
- Unable to verify - further investigation required
- Requires attention - The frame is unsuitable
- Requires attention - The frame is damaged beyond repair
- Requires attention - The frame is damaged and requires repairing
- Requires attention - The frame is twisted and/or out of square
- Requires attention - The frame has been incorrectly installed
- Requires attention- The frame has been incorrectly modified
- NA
OVERPANEL/SIDE PANEL
-
The overpanel/side panel is suitable and in good condition?
- Pass
- Unable to verify - further investigation required
- Requires attention - The over/side panel is unsuitable
- Requires attention - The over/side panel is damaged beyond repair
- Requires attention - The over/side panel is damaged and requires repairing
- Requires attention - The over/side panel is twisted and/or out of square
- Requires attention - The over/side panel has been incorrectly installed
- Requires attention- The over/side panel has been incorrectly modified
- N/A
FIRE STOPPING
-
There is sufficient fire stopping behind the frame?
ARCHITRAVE
-
The architrave is suitable and in good condition?
- Pass
- Unable to verify - Further investigation required
- Requires attention - The architrave is unsuitable
- Requires attention - The architrave is damaged beyond repair
- Requires attention - The architrave is damaged and requires repairing
- Requires attention - The architrave has been incorrectly installed
- Requires attention - The architrave is missing
- NA
DOOR STOPS
-
The doors stops are suitable and in good condition?
- Pass
- Unable to verify - further investigation required
- Requires attention – The stop beads are unsuitable
- Requires attention - The stop beads are damaged beyond repair
- Requires attention - The stop beads are damaged and require repairing
- Requires attention - The stop beads are incorrectly fitted
- Requires attention – The stop beads are missing
- Requires attention- The stop beads have been incorrectly modified
- NA
DOOR LEAF
-
There door leaf is suitable and free from damage?
- Pass
- Nominal fire door - The door has the characteristics of a fire resisting door however there is no evidence to support this
- Unable to verify - further investigation required
- Requires attention - Door leaf is unsuitable
- Requires attention - Door leaf is damaged beyond repair
- Requires attention - Door leaf is damaged and requires repairing
- Requires attention - Door leaf is twisted and/or out of square
- Requires attention- The door leaf has been incorrectly modified
- Requires attention - Door leaf has been incorrectly installed
- Requires attention - Door leaf is missing
- NA
GAPS AROUND THE DOOR
-
The gaps around the door are between 2 and 4mm and the smoke seals are making contact?
GAP UNDER THE DOOR
-
There gap under the door is no greater than 10mm or 3mm for doors that require smoke control?
THRESHOLD SEAL
-
Threshold seal is present, and working?
INTUMESCENT SEALS
-
The smoke seals are present, suitable and undamaged?
- Pass
- Unable to verify - further investigation required
- Requires attention – The seals are unsuitable
- Requires attention - The seals are damaged
- Requires attention - The seals are missing
- Requires attention - The seals have been incorrectly installed
- NA
HINGES/PIVOTS
-
3 hinges are present, certified and in good condition?
- Pass
- Unable to verify - further investigation required
- Requires attention - Hinges/Pivots are unsuitable
- Requires attention - Hinges/Pivots are worn and need replacing
- Requires attention - Hinges/Pivots have been incorrectly installed
- Requires attention - Missing or loose fixings
- Requires attention - Missing intumescent hinge pads
- NA
GLAZING SYSTEM
-
The glazing system is suitable and in good condition?
- Pass
- Unable to verify - further investigation required
- Requires attention - Glazing system is unsuitable
- Requires attention - Glazing system is damaged beyond repair
- Requires attention - Glazing system has been incorrectly installed
- Requires attention - Glass is missing
- NA
DOOR CLOSER
-
Door closer is present, working and in good condition?
- Pass
- Unable to verify - further investigation required
- Requires attention - Closer is unsuitable
- Requires attention - Closer is damaged beyond repair
- Requires attention - Closer is missing
- Requires attention - Closer has been incorrectly installed
- Requires attention - Closer requires adjustment
- Requires attention - Missing or loose fixings
- NA
OPERATION
-
Door closes correctly from any angle and latches where required?
- Pass
- Unable to verify - further investigation required
- Requires attention - The door is being wedged open
- Requires attention - The door is being obstructed
- Requires attention - The door has dropped or has swollen and is catching on the floor
- Requires attention - There is a high spot in the floor preventing the door from closing
- Requires attention - The door is not closing fully into frame
- NA
HOLD OPEN DEVICE
-
Hold open device operates correctly?
LOCKSET/LATCH/HARDWARE
-
Hardware is present, suitable, operates correctly and is in good condition?
- Pass
- Unable to verify - further investigation required
- Requires attention - Lockset/Hardware is unsuitable
- Requires attention - Lockset/Hardware is damaged
- Requires attention - Lockset/Hardware is missing
- Requires attention - Lockset/Hardware has been incorrectly installed
- Requires attention - Lockset/Hardware is loose or requires a ease and adjust
- NA
SIGNAGE
-
Door is correctly signed?
- Pass
- Unable to verify - further investigation required
- Requires attention - Signs damaged
- Requires attention - Signs missing
- Requires attention - Incorrectly fitted signs
- NA
AIR TRANSFER GRILLE
-
Air transfer grill is suitable and correctly fitted?
- Pass
- Unable to verify - further investigation required
- Requires attention - Air transfer grille is unsuitable
- Requires attention - Air transfer grille is damaged
- Requires attention - Air transfer grille is missing
- Requires attention - Air transfer grille has been incorrectly fitted
- NA
EMERGENCY EXIT DEVICE
-
Emergency exit device is present and working?
- Pass
- Unable to verify - further investigation required
- Requires attention - Hardware is unsuitable
- Requires attention - Hardware is damaged
- Requires attention - Hardware is missing
- Requires attention - Hardware has been incorrectly installed
- Requires attention - Hardware is difficult to operate
- Requires attention - The door or pathway is obstructed
- Requires attention - Hardware does not conform with current regs
- NA
OVERALL CONDITION AND SUITABILITY OF DOOR
-
PASS/FAIL
- Pass
- Fail
- N/A
- Unable to inspect
- Further investigation required
- No Access
REMEDIAL WORKS REQUIRED FOR SINGLE DOOR
-
Remedial works required to rectify issues with door.
- ART-01a - Partial repair of lipping.
- ART-01b - Full repair to closing edge.
- ART-01c - Full repair to hanging edge.
- ART-02a - Repair voids.
- ART-03a - Repair frame joints.
- ART-03b - Resize frame.
- ART-04a - Realign door.
- ART-04b - Relip closing edge of door.
- ART-04c - Relip frame closing edge.
- ART-04d - Relip frame top edge.
- ART-04e - Relip bottom edge of door.
- ART-05a - Adjust door closer.
- ART-05b - Replace door closer.
- ART-05c - Fit new door closer.
- ART-06 - Realign door and stops.
- ART-07 - Moisture ingress. Area must be dried.
- ART-08 - Replace hinges.
- ART-09 - Realign frame.
- ART-11 - Replace intumescent/smoke seals.
- ART-12a - Realign hardware/keep
- ART-12b - Replace hardware
- ART-13a - Refix hinges.
- ART-13b - Patch repair frame.
- ART-14a - Replace glass.
- ART-14b - Replace glazing beads.
- ART-15 - Hinge recess repair.
- ART-16a - Replace architrave.
- ART-16b - Fire stopping requires improvement.
- ART-17 - Replace door leaf.
- ART-18 - Replace doorset.
- ART-19a - Fit new 'fire door keep shut' sign.
- ART-19b - Fit 2no. new 'fire door keep shut' signs.
- ART-19c - Fit new 'fire door keep locked' sign.
- ART-19d - Fit 1no. new 'automatic fire door keep clear' signs.
- ART-19e - Fit 1no. new 'fire exit keep clear' sign.
- ART-19f - Fit 1no. new 'push bar to openr' sign.
- ART-20 - Replace door frame.
- ART-22 - Fit drop down seal or threshold.
- ART-24 - General Operational Adjustment
- ART-25a - Panic bar replacement.
- ART-25b - Panic bar repair.
- ART-25c - Emergency exit hardware requires attention
- ART-26 - Repair not listed. See comments
- We recommend consultation with customer to determine best course of action.
COMMENTS
NOTES
-
- The fire performance of the overall door-set system cannot be confirmed as evidence of fire performance was not available.
- The fire performance of the overall door-set system cannot be confirmed as evidence of performance was only available for part of the door-set
- A thorough visual examination has been undertaken on the door-set however the internal construction of the door leaf could not be confirmed.
- The density of the timber components was not confirmed against the minimum specification for density in the documentation.
- The details of the vision panel could not be confirmed.
- 7. It was apparent that a new door had been installed into an existing frame. The installation of a new door with associated ironmongery and intumescent/smoke seals into an existing frame may not be suitable in providing the required fire separation as the condition and quality/density of the frame and supporting construction could not be confirmed.
- The door-set only displayed a reference to a fire test and/or assessment and it was not evident that the door-set was of third party independent certification scheme.
- It was not possible to remove door hardware to verify that the correct intumescent gaskets had been installed between the hardware components and the door / door frame.
PHOTOS
-
Add media
Completion and Sign-Off
-
Inspector's Name and Signature