Site Identification/Site – General Building
-
Photos showing the building or hut & compound as viewed from the site entrance plus a close-up of the grounds.
-
For in-building sites, pictures to capture the entire building and the entrance to the equipment room.
Room layout photos
-
Showing complete layout of the room and all the installed equipments.
Full Rack View Photo Requirement
-
The rack view photo should be clear and all the equipment added in the rack should be clearly visible with rack label.
-
GPS splitter<br>Combiners/Filters<br>Rack labelling<br>GPS receiver<br>Radio 2212<br>Radio 2217<br>RBS6601 box<br>H&S tray for DWDM<br>Fibre trays
Combiner Photo Requirement
-
Mandatory Requirements<br>➢ Location label should be clearly visible.<br>➢ Barcode should be clearly visible with<br>combiner type and barcode/serial number.<br>➢ Correct sector number to be noted on the<br>label.<br>➢ Feeder labels of combiner should be clearly<br>visible.<br>➢ Combiner (Type, Serial no, Revision, DOM,<br>Location) should also be captured in MITS<br>template.<br>➢ Combiner barcode photos also need to be<br>captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to<br>be captured in RFSR along with port<br>connectivity information.
-
Combiner Photo Requirement- Sector label<br>Mandatory Requirements<br>1- Sector number should be clearly visible in all combiner labels<br>2- The label must include combiner no., technology with sector information.<br>3- Ensure technologies mentioned on labels are correct as per RFSR.
Filter Photo Requirement
-
<br>Mandatory Requirements<br>➢ Location label should be clearly visible.<br>➢ Barcode should be clearly visible with filter type and barcode/serial number.<br>➢ Correct sector number to be noted on the label.<br>➢ Feeder labels of the filter should be clearly visible.<br>➢ Filter (Type, Serial no, Revision, DOM, Location) should also be captured in MITS template.<br>➢ Filter barcode photos also need to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR along with port connectivity information.
-
Filter Photo Requirement – Sector label<br>Mandatory Requirements:<br>1- Sector label should be clearly visible, for all the filters<br>2- Sector label should contain technology filter type, technology with the sector, and carrier information.<br>3- Ensure technologies mentioned on labels are correct as per RFSR.
-
GPS Equipment's
-
GPS Antenna<br>Surge Arrestor<br>Splitter<br>Receiver
-
GPS Antenna Photo Requirement:<br>Mandatory Requirements:<br>➢ Location of GPS antenna should be clearly visible<br>➢ Barcode label should be clearly visible stating GPS antenna type.<br>➢ Feeder labels of GPS antenna should be clearly visible.<br>➢ GPS antenna (Type, Serial no, Revision, DOM, Location) should also be captured in the MITS template and canrad data.<br>➢ GPS antenna barcode photos also need to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR.<br>➢ Correct GPS number location and height need to be mentioned in redline mark-up on E1/E2, S3, and site layout drawing.
-
GPS Surge Arrestor Photo Requirement:<br>Mandatory Requirements<br>➢ Location of GPS surge arrestor should be clearly visible<br>➢ Barcode label should be clearly visible stating GPS surge arrestor<br>type.<br>➢ Feeder labels of GPS antenna should be clearly visible.<br>➢ GPS surge arrestor (Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template and canrad data.<br>➢ GPS surge arrestor barcode photos also need to be captured in MITS<br>for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity need to be mentioned on RFSR.
-
GPS Splitter Photo Requirement<br>Mandatory Requirements<br>➢ Location of GPS splitter should be clearly visible<br>➢ Barcode label should be clearly visible stating GPS splitter type.<br>➢ Feeder labels of splitter should be clearly visible.<br>➢ Splitter (Type, Serial no, Revision, DOM, Location) should also be captured<br>in the MITS template.<br>➢ Splitter barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity need to be mentioned on RFSR
-
GPS Receiver Photo Requirement<br>Mandatory Requirements<br>➢ Location GPS receiver should be clearly visible<br>➢ Barcode label should be clearly visible stating GPS receiver type.<br>➢ Feeder labels of the receiver should be clearly visible.<br>➢ Receiver (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ Receiver barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Count of GPS receiver should be correct in RFSR and redline mark-up.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.
Radio 4480
-
Mandatory Requirements<br>➢ Location of Radio 4480 should be clearly visible.<br>➢ Correct sector label should be present on each radio.<br>➢ Feeder labels of the radio should be clearly visible.<br>➢ Radio 4480 (Type, Serial, Revision, DOM, Location)should also be<br>captured in the MITS template.<br>➢ 4480 Fan unit (Type, Serial, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ 4480 SFP(Type, Serial, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ Radio 4480, fan unit, SFP barcode photos also need to be captured<br>in MITS for backup purposes<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.
-
Radio 4480 Photo Requirement – Sector label<br>Mandatory Requirements<br>➢ Sector label should be clearly visible, for all the Radio 2212.<br>➢ Sector label should contain correct location, Radio no. , Radio type,<br>technology, sector, and cell information<br><br>Ensure technologies mentioned on labels<br>are correct as per RFSR
-
DCDU Photo Requirement
-
Mandatory Requirements<br>➢ Location of DCDU should be clearly visible.<br>➢ DCDU legend photo should be clearly visible with all details.<br>➢ DCDU (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ DCDU barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Provide cable tray (SXA1030769/1) serial no., DOM & Revision<br>associated with DCDU in MITS template and capture the barcode for<br>the same in MITS for backup purposes.<br>➢ DCDU CB and its ampere ratings should be clearly
-
DCDU Photo Requirement– DCDU legend close view<br>Mandatory Requirements<br>DCDU legend should contain:<br>DCDU location<br>CB information of power system from where DCDU is fed<br>Power rack location<br>Equipment that is getting supplied from DCDU<br>Equipment’s Location which is getting supply from DCDU<br>CB numbering
-
PDP Photo Requirement
-
Mandatory Requirements<br>➢ Location of PDP should be clearly visible.<br>➢ PDP legend photo should be clearly visible with all details.<br>➢ PDP (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ PDP barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ PDP CB and its ampere ratings should be clearly visible.
-
PDP Photo Requirement– PDP legend close view<br>Mandatory Requirements<br>PDP legend should contain:<br>PDP location<br>CB information of power system from where PDP is fed<br>Power rack location<br>Equipment that is getting supplied from PDP<br>Equipment’s Location which is getting supply from PDP<br>CB numbering
-
RBS 6601 Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of RBS6601<br>➢ Location of 6601 should be clearly visible.<br>➢ Close up photo of RBS6601<br>➢ FAN unit photo of RBS 6601<br>➢ Node label photo of RBS6601 with correct details.<br>➢ RBS6601 SUP (Type, Serial no, Revision, DOM, Location) should also<br>be captured in the MITS template.<br>➢ RBS6601 FAN unit (Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template.<br>➢ RBS6601 SUP and FAN unit barcode photos also need to be<br>captured in MITS for backup purposes.
-
RBS 6601 and XMU Label<br>Mandatory Requirements<br>➢ Node label of RBS6601 should be clearly visible.<br>➢ Node label of RBS 6601 should include the site name, node code,<br>node address manager ID, RBS 6601 location, and equipment<br>present in RBS 6601 with correct technologies<br>➢ For XMU added in 6601 node code should include enb ID, XMU no.,<br>technology and sector<br>Ensure technologies mentioned on labels are correct as per RFSR.
-
XMU /R503 Photo Requirement
-
Mandatory Requirements<br>➢ Location of XMU should be clearly visible.<br>➢ Close up photo of XMU showing all the ports with port no. visible<br>where SFPs are connected<br>➢ Node label photo of relevant RBS should include XMU details (XMU<br>and XMU no. mentioned along with sector information and<br>technology<br>➢ XMU/R503(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SFP (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ XMU and SFP barcode with the location mentioned on barcode<br>photos also need to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR<br>along with port connectivity information
-
DUW Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of DUW<br>➢ Location of DUW should be clearly visible.<br>➢ Close up photo of DUW showing DUW type, all the ports with port no.<br>where SFPs and DAC cables are connected.<br>➢ Node label photo of relevant RBS should include DUW details (node<br>code should include enb ID, DUW no., Technology and sector)<br>➢ DUW(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SFP & DAC cable(Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template.<br>➢ DUW, SFP & DAC cable barcode with the location mentioned on<br>barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR<br>along with port connectivity information
-
RBS 6601 and DUW Label<br>Mandatory Requirements<br>➢ Node label of RBS6601 should be clearly visible.<br>➢ Node label of RBS 6601 should include the site name, node code,<br>node address manager ID, RBS 6601 location, and equipment<br>present in RBS 6601with equipment name and no. mentioned<br>along with sector information and technology<br>➢ For DUW added in 6601 node code should include RBS ID, DUW<br>no., technology and sector<br>Ensure Technologies mentioned on labels are correct as per RFSR.
-
BB5216 Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of BB5216<br>➢ Location of BB5216 should be clearly visible.<br>➢ Close up photo of BB5216 showing BB5216 as marked in a photo, all<br>the ports with port no. where SFPs are connected.<br>➢ Node label photo of relevant RBS should include BB5216 details<br>(node code should include RBS ID, BB5216 no., technology and<br>sector)<br>➢ BB5216(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SFP (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ BB5216 & SFP barcode with the location mentioned on barcode<br>photos also need to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR<br>along with port connectivity information
-
RBS 6601 and BB5216 Photo Requirement– Node<br>label<br>Mandatory Requirements<br>➢ Node label of RBS6601 should be clearly visible.<br>➢ Node label of RBS 6601 should include the site name, node code,<br>node address manager ID, RBS 6601 location, and equipment<br>present in RBS 6601with equipment name and no. mentioned<br>along with sector information and correct technology.<br>➢ For BB5216 added in 6601 node code should include RBS ID,<br>BB5216 no., technology and sector<br>Ensure technologies mentioned labels are correct as per<br>RFSR.
-
RBS6202 (Rack View and Close up)
-
Mandatory Requirements<br>➢ Rack view photo should be clear and all the<br>equipment added in the rack should be clearly visible.<br>➢ Location label should be present and clearly visible.<br>➢ Open and close box photo of RBS6202 is required
-
Open Box Photo of RBS6202<br>Mandatory Requirements<br>➢ Open box photo of RBS6202<br>➢ All equipment installed in RBS6202 must be clearly visible.<br>➢ Equipment (BB5216/XMU/DUW) installed in RBS6202 all SFP ports<br>should be clearly visible, with port no.<br>➢ If any equipment is installed in Magazine 03(DU adapter unit), an open box<br>photo with a clear photo of ports with SFP connectivity should be provided<br>with port no.<br>➢ Node code photo is mandatory<br>➢ RBS6202 (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ PCF, SCU, PDU, FRU, RUS, PFU, DU adapter (Type, Serial no, Revision,<br>DOM, Location) should also be captured in the MITS template.<br>➢ RBS6202 unit barcode photos also need to be captured in MITS for backup<br>purposes.
-
RBS 6202 Photo Requirement– Node label<br>Site Name<br>Node Code<br>Node Manager Address ID<br>RBS type<br>Enb ID<br>Equipment<br>Equipment technology<br>Sectors<br>BBH Node code
-
DWDM (Open View and Closed View)
-
Mandatory Requirements<br>➢ DWDM cassettes (Type, Serial no., Revision, DOM, Location)<br>➢ Open and close view photos of DWDM<br>➢ Cassettes barcode photos also need to be captured in MITS for<br>backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.
-
DWDM Labelling when GCF(wwdm)-CRAN<br>andatory Requirements<br>➢ DWDM/WWDM (Type, Serial no., Revision,<br>DOM, Location) also need to be captured in<br>the MITS template.<br>➢ Open DWDM/WWDM photo is required<br>➢ DWDM/WWDM type should clearly be<br>visible from photos<br>➢ DWDM/WWDM barcode photos also need<br>to be captured in MITS for backup<br>purposes.
-
DWDM Type<br>DWDM/WWDM<br>Node label should<br>match with actual<br>photos(Positions<br>mentioned in Node<br>label should match<br>with photos<br>DWDM/WWDM<br>Node label
-
DWDM Labelling when no GCF(wwdm)-CRAN
-
Mandatory Requirements<br>➢ DWDM (Type, Serial no., Revision, DOM,<br>Location) also need to be captured in the<br>MITS template.<br>➢ Open DWDM photo is required<br>➢ DWDM type should clearly be visible from<br>photos<br>➢ DWDM barcode photos also need to be<br>captured in MITS for backup purp<br>Labeling standards should<br>be as per MOP and should<br>be site-specific.
-
DWDM Type<br>DWDM Node label<br>should match with<br>actual<br>photos(Positions<br>mentioned in Node<br>label should match<br>with photos<br>DWDM Node label
-
DWDM Labelling-HRAN
-
Mandatory Requirements<br>➢ DWDM/WWDM (Type, Serial no., Revision,<br>DOM, Location) also need to be captured in<br>the MITS template.<br>➢ Open DWDM/WWDM photo is required<br>➢ DWDM/WWDM type should clearly be<br>visible from photos<br>➢ DWDM/WWDM barcode photos also need<br>to be captured in MITS for backup<br>purposes.<br>Labeling standards should<br>be as per MOP and should<br>be site-specific.
-
DWDM Type<br>DWDM Node label<br>should match with<br>actual<br>photos(Positions<br>mentioned in Node<br>label should match<br>with photos<br>DWDM Node label
-
Router 6651 Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of 6651 router<br>➢ Location of 6651 router should be clearly visible.<br>➢ Close up photo of 6651 router<br>➢ Node label photo of 6651 router<br>➢ 6651 router (Type, Serial No, Revision, DOM, Location) should also be captured<br>in MITS template.<br>➢ 6651 router tray (Type, Serial No, Revision, DOM, Location) should also be<br>captured in MITS template.<br>➢ 6651 router fan unit (Type, Serial No, Revision, DOM, Location) should also be<br>captured in MITS template.<br>➢ 6651 SFP (Type, Serial No, Revision, DOM, Location) should also be captured<br>in MITS template.<br>➢ 6651 Blank panel SXK1253793/1 (Type, Serial No, Revision, DOM, Location)<br>should also be captured in MITS template.<br>➢ 6651 Router, tray, fan unit and SFP barcode Photos also need to be captured<br>in MITS for backup purpose.
-
SFP/Cable Associated with equipment's should be clearly visible with port No's<br>and should be in active green state.<br><br>Node Code requirements<br>Site Name<br>Router Type<br>Router Code<br>Location
-
Router Labels<br>Node Code requirements<br>Site Name<br>Router Type<br>Router Code<br>Location<br>GPON naming<br>GCF/WWDM Location<br>BBH Router Code<br>DWDM type<br>DWDM Location
-
6675 Router Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of 6675 cell site router<br>➢ Location of 6675 cell site router should be clearly visible.<br>➢ Close up photo of 6675 cell site router<br>➢ Node label photo of 6675 cell site router<br>➢ 6675 cell site router (Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template.<br>➢ 6675 cell site router SFP(Type, Serial no, Revision, DOM, Location)<br>should also be captured in the MITS template.<br>➢ 6675 Router fan unit (Type, Serial no, Revision, DOM, Location)<br>should also be captured in the MITS template.<br>➢ 6675 Router, fan unit and SFP unit barcode photos also need to be<br>captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.
-
Node Code requirements<br>Site Name<br>Router Type<br>Router Node Code<br>Location
-
BB6648 & RP6651 Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of BB6648/RP6651<br>➢ Location of BB6648/RP6651 should be clearly visible.<br>➢ Close up photo of BB6648/RP6651<br>➢ Node label photo of BB6648/RP6651.<br>➢ BB6648/RP6651 (Type, Serial no, Revision, DOM,<br>Location) should also be captured in the MITS template.<br>➢ BB6648/RP6651 fan unit (Type, Serial no, Revision,<br>DOM, Location) should also be captured in the MITS<br>template.<br>➢ BB6648/RP6651 and fan unit barcode photos also need<br>to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured<br>in RFSR and correct port connectivity needs to be<br>mentioned on RFSR.
-
BB6648 & RP6651 Node label Photo Requirement<br>Node Code requirements<br>Site Name<br>Node Code<br>Address id<br>Location<br>Baseband Type<br>Band Information<br>eNB ID/gNB id<br>Technology &<br>Sector Information
-
Ensure technologies mentioned on labels are correct as per RFSR.<br>BB6648 RP6651<br>All Label example templates MUST be modified to be site specific and correct- Remove WCDMA 850<br>and LTE/NR Bands as applicable
-
SIU Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of SIU<br>➢ Location of SIU should be clearly visible.<br>➢ Close up photo of SIU<br>➢ Node label photo of SIU<br>➢ SIU(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SFP installed at SIU in MTX(Type, Serial no, Revision, DOM, Location)<br>should also be captured in the MITS template.<br>➢ SIU and SFP barcode photos also need to be captured(SFP type,<br>Serial no. DOM should be clearly visible on photos) photos should be<br>uploaded in the MITS section.<br>Photo capturing SIU connections should match with MTX design.<br>Install SFP type as per design if any changes are required contact<br>designer and MTX design should be redlined accordingly and provided<br>to designer
-
Node Code requirements<br>Site Name<br>SIU Node Code<br>Location
-
Fibre tray Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of Tray<br>➢ Location of Tray should also be clearly visible.<br>➢ Tray any type of tray installed (Type, Serial No, Revision, DOM,<br>Location) should be captured in MITS template.<br>➢ If any fibre tray relocated need to mention the same in Redline markup S0-1 and E1 sheets and provide (Type, Serial No, Revision, DOM,<br>Location) in MITS section.<br>➢ Any fibre tray installed at site should be captured in redline mark-up<br>S0-1 and E1 sheets.
-
Patch Panel Photo Requirement
-
Mandatory Requirements<br>➢ Rack view photo of patch panel<br>➢ Location of patch panel should be clearly visible.<br>➢ Patch panel (Type, Serial no, Revision, DOM, Location) should be<br>captured in the MITS template.<br>➢ Patch panel(Type, Product code, Serial no, Revision, DOM, Location)<br>should be captured in the MITS template.<br>➢ Patch panel cassette (Type, Product code, Serial No, Revision, DOM,<br>Location) should also be captured in the MITS template.<br>➢ Patch barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ MPO cassettes associated with patch panel each cassette serial No.<br>should be captured in MITS template.
-
SPD Photo Requirement
-
Mandatory Requirements<br>➢ Close box photo of SPD<br>➢ Open box photo of SPD.<br>➢ SPD location photo<br>➢ SPD label photo<br>➢ SPD power label photo<br>➢ Clear view photo of all the CBs showing clear ampere rating and<br>manufacturer for each CB<br>➢ Clear view photo of feeder no. entering the SPD<br>➢ Padlock should be visible<br>➢ SPD(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SPD barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.
-
SPD Power Label<br>Mandatory Requirements<br>➢ Location on SPD power label should match with SPD location label<br>➢ PWR ID: actual power id of the respective power system to be<br>mentioned here, dummy power id should not be used.<br>➢ Location of the parent power system: respective power system<br>location from which SPD is getting supply.<br>➢ Location of Distribution fuse should match with power legend of the<br>respective power system
-
SPD Label<br>Mandatory Requirements<br>➢ CB of SPD(ON/OFF) and SPD label should match<br>➢ Feeder no. mentioned should match with feeder entry labels and<br>feeder entry labeling should be correct<br>➢ Cell names should be as per respective technologies associated with<br>CB<br>➢ Technology, equipment, port no. and antenna no. should be correct<br>and as per standards.<br>➢ The port numbers on the SPD label to be matched as per<br>XMU/BB6630/DWDM port connections. Both photos & SPD labels<br>need to have the same port connectivity.<br>➢ XMU-X, BB6630-X – should match with respective equipment node<br>label and its respective technologies.<br>➢ Here X represents numbering(1/2/3…)
-
Augmentation Box
-
Mandatory Points<br>➢ Augmentation box full view with<br>location label photo required.<br>➢ Augmentation box open photos<br>required<br>➢ Power ID legend photos<br>required.
-
Power System
-
Mandatory Requirements<br>➢ Full view photo of power system showing all the equipment's and<br>location label clearly visible<br>➢ Clear view photo of all the CBs showing clear ampere rating and<br>manufacturer for each CB<br>➢ Power rack and associated equipment<br>(Rectifiers/Convertors/Batteries/extension racks )-details to be<br>captured in SB template and barcode photos also need to be captured<br>in MITS for backup purposes.<br>➢ Power rack and associated equipment<br>(Rectifiers/Convertors/Batteries/extension racks(Type,<br>Manufacturing code, Serial no, Revision, DOM) should also be<br>captured in SB template.
-
Power Rack CB close view<br>Mandatory Requirements<br>➢ Clear view photo of all the CB’s showing clear ampere rating<br>and manufacturer for each CB and CB numbering
-
Power Rack Power legend<br>Mandatory Requirements<br>➢ Power legend and description of the same should be clearly visible.<br>➢ Power system CB ON/OFF status should match with the power legend<br>and E4 sheet of redline mark-up.<br>➢ All descriptions in the power legend should be correct.<br>➢ Equipment technologies/ type and Location should be correctly<br>mentioned.<br>➢ In case of Augmentation SPD is used on-site, information of the same is<br>to be captured in the power legend.<br>➢ Power legend description and E4 sheet CB description should match in<br>redline.<br>➢ Labelling standards should be as per MOP and should be site-specific.
-
Power Rack Batteries/Rectifiers/ Convertors
-
Mandatory Requirements<br>➢ Clear view photos of batteries, rectifiers, and convertors should be<br>provided.<br>➢ Battery type, rectifier, convertor, and monitor type should be visible<br>from photos.<br>➢ No of rectifier/convertor/monitor/batteries should match in redline<br>mark-up on S0-1, E1, and E4 sheets.<br>➢ Battery type, rectifier, convertor, and monitor type should match in<br>redline mark-up on S0-1, E1, and E4 sheets.<br>➢ Caution labels need to be fixed on blank plates of<br>rectifiers/convertors with maximum no. rectifiers/convertors<br>mentioned on labels in accordance with the FC drawing
-
Enatel DC/DC Converter
-
Mandatory Requirements<br>➢ Full view photo of power system showing all the equipment's and<br>location label clearly visible<br>➢ Clear view photo of all the CBs showing clear ampere rating and<br>manufacturer for each CB<br>➢ Clear view photo showing Convertor and monitor type and its<br>manufacturer and type.<br>➢ Power rack and associated equipment (Convertors/Monitor/rack )-<br>details to be captured in SB template and barcode photos also need<br>to be captured in MITS for backup purposes.<br>➢ Power rack and associated equipment (Convertors/Monitor<br>racks(Type, Manufacturing code, Serial no, Revision, DOM) should<br>also be captured in SB template.
-
Enatel DC/DC Converter<br>Mandatory Requirements<br>➢ Power legend and description of the same should<br>be clearly visible.<br>➢ Power system CB ON/OFF status should match<br>with the power legend and E4 sheet of redline<br>mark-up.<br>➢ Clear view photo of all the CB’s showing clear<br>ampere rating and manufacturer for each CB and<br>CB numbering<br>➢ All descriptions in the power legend should be<br>correct.<br>➢ Equipment technologies/ type and Location<br>should be correctly mentioned.<br>➢ In case of Augmentation SPD is used on-site,<br>information of the same is to be captured in the<br>power legend.<br>➢ Power legend description and E4 sheet CB<br>description should match in redline.<br>➢ Labelling standards should be as per MOP and<br>should be site-specific.<br>➢ Power ID legend photos required with all<br>details(Location/Power id/Location of parent<br>power system/Location of dist Fuse) should be<br>correct and as per standards
-
Distribution board
-
Mandatory Requirements<br>➢ Full view photo of distribution board<br>➢ Clear view photo of all the CBs showing clear ampere<br>rating and manufacturer for each CB<br>➢ Photo of distribution board label with the correct<br>description as per standards.
ESC
-
Mandatory Requirements<br>➢ Full rack view photo ESC showing ESC and rack location label.<br>➢ Close view photo of ESC with all ports cables/SFP clearly visible.<br>➢ Node label photo of ESC<br>➢ ESC entry in power legend of power system<br>➢ ESC (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ ESC SFP/cable (Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template.<br>➢ ESC needs to be markup in redlines in case of a new install.
-
OFDP Photo location label and open photo
-
Mandatory Requirements<br>➢ OFDP open photo<br>➢ OFDP close photos<br>➢ OFDP label<br>➢ OFDP (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.
-
Telstra DBORS Photo Guide (Donor End)
Full Rack view Photos
-
Mandatory Requirements<br>➢ Full rack view photo with location label<br>clearly visible.<br>➢ Equipment associated with remote end<br>(BB5216, BB6630, chasis) should be clearly<br>visible.
-
RBS 6601
-
Mandatory Requirements<br>➢ RBS6601 clear view photo with<br>subrack no. clearly visible<br>➢ BB5216 associated with a remote end<br>should be clearly visible with all SFP in<br>active state.<br>➢ Node label photo of BB5216 with<br>correct details.<br>➢ RBS6601 SUP (Type, Serial no,<br>Revision, DOM, Location) should also<br>be captured in the MITS template.<br>➢ RBS6601 fan unit (Type, Serial no,<br>Revision, DOM, Location) should also<br>be captured in the MITS template.<br>➢ RBS6601 SUP and fan unit barcode<br>photos also need to be captured in<br>MITS for backup purposes.
-
BB5216
-
Mandatory Requirements<br>➢ RBS6601 clear view photo with sub-rack<br>no. clearly visible<br>➢ BB5216 associated with a remote end<br>should be clearly visible with all SFP in<br>active state.<br>➢ Node label photo of relevant RBS should<br>include BB5216 details.<br>➢ BB5216(Type, Serial no, Revision, DOM,<br>Location) should also be captured in the<br>MITS template.<br>➢ SFP (Type, Serial no, Revision, DOM,<br>Location) should also be captured in the<br>MITS template.<br>➢ BB5216 & SFP barcode with the location<br>mentioned on barcode photos also need to<br>be captured in MITS for backup purposes.
-
BB6630
-
Mandatory Requirements<br>➢ Close up photo of BB6630 associated with<br>remote end, with subrack No., SFP ports<br>visible and all SFP in active state.<br>➢ Node label photo of BB6630<br>➢ BB6630(Type, Serial No, Revision, DOM,<br>Location) should also be captured in MITS<br>template.<br>➢ BB6630 fan unit (Type, Serial No, Revision,<br>DOM, Location) should also be captured in<br>MITS template.<br>➢ BB6630 and fan unit barcode Photos also<br>need to be captured in MITS for backup<br>purpose.<br>➢ SFP Labeling photos required on the SFP<br>patch cables to find out where our SFP’s are<br>plugged in.
-
DWDM
-
Mandatory Requirements<br>➢ Chasis clear view photo with<br>subrack no. and donor code should<br>be clearly visible<br>➢ Chasis (Type, Serial no., Revision, DOM,<br>Location)
-
DWDM / WWDM
-
Mandatory Requirements<br>➢ DWDM/WWDM clear view photo<br>➢ Positions at which DWDM/WWDM installed<br>➢ DWDM type should be clearly visible from photos<br>➢ Node label photo<br>➢ DWDM/WWDM (Type, Serial no., Revision, DOM, Location)<br>also need to be captured in the MITS template.<br>➢ DWDM/WWDM barcode photos also need to be captured in<br>MITS for backup purposes.
-
R6675
-
Mandatory Requirements<br>➢ R6675 clear view photos with sub-rack no.<br>clearly visible<br>➢ R6675 associated with remote end should be<br>clearly visible with all SFP in active state as per<br>MTX design.<br>➢ Node label photo of relevant RBS should<br>include R6675 details.<br>➢ R6675(Type, Serial no, Revision, DOM,<br>Location) should also be captured in the MITS<br>template.<br>➢ SFP (Type, Serial no, Revision, DOM, Location)<br>should also be captured in the MITS template.<br>➢ R6675 & SFP barcode with the location<br>mentioned on barcode photos also need to be<br>captured in MITS for backup purposes.<br>➢ R6675 naming convention should be correct<br>and router-id is mandatory to be mentioned on<br>naming convention
-
Fibre Tray
-
Mandatory Requirements<br>➢ Rack view photo of tray<br>➢ Sub rack no. should be clearly visible<br>➢ Tray (Type, Serial no, Revision, DOM, Location) should be<br>captured in the MITS template.
-