Title Page

  • Site conducted

  • Conducted on

  • Prepared by

  • Location

Site Identification/Site – General Building

  • Photos showing the building or hut & compound as viewed from the site entrance plus a close-up of the grounds.

  • For in-building sites, pictures to capture the entire building and the entrance to the equipment room.

Room layout photos

  • Showing complete layout of the room and all the installed equipments.

Full Rack View Photo Requirement

  • The rack view photo should be clear and all the equipment added in the rack should be clearly visible with rack label.

  • GPS splitter<br>Combiners/Filters<br>Rack labelling<br>GPS receiver<br>Radio 2212<br>Radio 2217<br>RBS6601 box<br>H&S tray for DWDM<br>Fibre trays

Combiner Photo Requirement

  • Mandatory Requirements<br>➢ Location label should be clearly visible.<br>➢ Barcode should be clearly visible with<br>combiner type and barcode/serial number.<br>➢ Correct sector number to be noted on the<br>label.<br>➢ Feeder labels of combiner should be clearly<br>visible.<br>➢ Combiner (Type, Serial no, Revision, DOM,<br>Location) should also be captured in MITS<br>template.<br>➢ Combiner barcode photos also need to be<br>captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to<br>be captured in RFSR along with port<br>connectivity information.

  • Combiner Photo Requirement- Sector label<br>Mandatory Requirements<br>1- Sector number should be clearly visible in all combiner labels<br>2- The label must include combiner no., technology with sector information.<br>3- Ensure technologies mentioned on labels are correct as per RFSR.

Filter Photo Requirement

  • <br>Mandatory Requirements<br>➢ Location label should be clearly visible.<br>➢ Barcode should be clearly visible with filter type and barcode/serial number.<br>➢ Correct sector number to be noted on the label.<br>➢ Feeder labels of the filter should be clearly visible.<br>➢ Filter (Type, Serial no, Revision, DOM, Location) should also be captured in MITS template.<br>➢ Filter barcode photos also need to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR along with port connectivity information.

  • Filter Photo Requirement – Sector label<br>Mandatory Requirements:<br>1- Sector label should be clearly visible, for all the filters<br>2- Sector label should contain technology filter type, technology with the sector, and carrier information.<br>3- Ensure technologies mentioned on labels are correct as per RFSR.

GPS Equipment's

  • GPS Antenna<br>Surge Arrestor<br>Splitter<br>Receiver

  • GPS Antenna Photo Requirement:<br>Mandatory Requirements:<br>➢ Location of GPS antenna should be clearly visible<br>➢ Barcode label should be clearly visible stating GPS antenna type.<br>➢ Feeder labels of GPS antenna should be clearly visible.<br>➢ GPS antenna (Type, Serial no, Revision, DOM, Location) should also be captured in the MITS template and canrad data.<br>➢ GPS antenna barcode photos also need to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR.<br>➢ Correct GPS number location and height need to be mentioned in redline mark-up on E1/E2, S3, and site layout drawing.

  • GPS Surge Arrestor Photo Requirement:<br>Mandatory Requirements<br>➢ Location of GPS surge arrestor should be clearly visible<br>➢ Barcode label should be clearly visible stating GPS surge arrestor<br>type.<br>➢ Feeder labels of GPS antenna should be clearly visible.<br>➢ GPS surge arrestor (Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template and canrad data.<br>➢ GPS surge arrestor barcode photos also need to be captured in MITS<br>for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity need to be mentioned on RFSR.

  • GPS Splitter Photo Requirement<br>Mandatory Requirements<br>➢ Location of GPS splitter should be clearly visible<br>➢ Barcode label should be clearly visible stating GPS splitter type.<br>➢ Feeder labels of splitter should be clearly visible.<br>➢ Splitter (Type, Serial no, Revision, DOM, Location) should also be captured<br>in the MITS template.<br>➢ Splitter barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity need to be mentioned on RFSR

  • GPS Receiver Photo Requirement<br>Mandatory Requirements<br>➢ Location GPS receiver should be clearly visible<br>➢ Barcode label should be clearly visible stating GPS receiver type.<br>➢ Feeder labels of the receiver should be clearly visible.<br>➢ Receiver (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ Receiver barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Count of GPS receiver should be correct in RFSR and redline mark-up.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.

Radio 4480

  • Mandatory Requirements<br>➢ Location of Radio 4480 should be clearly visible.<br>➢ Correct sector label should be present on each radio.<br>➢ Feeder labels of the radio should be clearly visible.<br>➢ Radio 4480 (Type, Serial, Revision, DOM, Location)should also be<br>captured in the MITS template.<br>➢ 4480 Fan unit (Type, Serial, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ 4480 SFP(Type, Serial, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ Radio 4480, fan unit, SFP barcode photos also need to be captured<br>in MITS for backup purposes<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.

  • Radio 4480 Photo Requirement – Sector label<br>Mandatory Requirements<br>➢ Sector label should be clearly visible, for all the Radio 2212.<br>➢ Sector label should contain correct location, Radio no. , Radio type,<br>technology, sector, and cell information<br><br>Ensure technologies mentioned on labels<br>are correct as per RFSR

DCDU Photo Requirement

  • Mandatory Requirements<br>➢ Location of DCDU should be clearly visible.<br>➢ DCDU legend photo should be clearly visible with all details.<br>➢ DCDU (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ DCDU barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Provide cable tray (SXA1030769/1) serial no., DOM & Revision<br>associated with DCDU in MITS template and capture the barcode for<br>the same in MITS for backup purposes.<br>➢ DCDU CB and its ampere ratings should be clearly

  • DCDU Photo Requirement– DCDU legend close view<br>Mandatory Requirements<br>DCDU legend should contain:<br>DCDU location<br>CB information of power system from where DCDU is fed<br>Power rack location<br>Equipment that is getting supplied from DCDU<br>Equipment’s Location which is getting supply from DCDU<br>CB numbering

PDP Photo Requirement

  • Mandatory Requirements<br>➢ Location of PDP should be clearly visible.<br>➢ PDP legend photo should be clearly visible with all details.<br>➢ PDP (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ PDP barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ PDP CB and its ampere ratings should be clearly visible.

  • PDP Photo Requirement– PDP legend close view<br>Mandatory Requirements<br>PDP legend should contain:<br>PDP location<br>CB information of power system from where PDP is fed<br>Power rack location<br>Equipment that is getting supplied from PDP<br>Equipment’s Location which is getting supply from PDP<br>CB numbering

RBS 6601 Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of RBS6601<br>➢ Location of 6601 should be clearly visible.<br>➢ Close up photo of RBS6601<br>➢ FAN unit photo of RBS 6601<br>➢ Node label photo of RBS6601 with correct details.<br>➢ RBS6601 SUP (Type, Serial no, Revision, DOM, Location) should also<br>be captured in the MITS template.<br>➢ RBS6601 FAN unit (Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template.<br>➢ RBS6601 SUP and FAN unit barcode photos also need to be<br>captured in MITS for backup purposes.

  • RBS 6601 and XMU Label<br>Mandatory Requirements<br>➢ Node label of RBS6601 should be clearly visible.<br>➢ Node label of RBS 6601 should include the site name, node code,<br>node address manager ID, RBS 6601 location, and equipment<br>present in RBS 6601 with correct technologies<br>➢ For XMU added in 6601 node code should include enb ID, XMU no.,<br>technology and sector<br>Ensure technologies mentioned on labels are correct as per RFSR.

XMU /R503 Photo Requirement

  • Mandatory Requirements<br>➢ Location of XMU should be clearly visible.<br>➢ Close up photo of XMU showing all the ports with port no. visible<br>where SFPs are connected<br>➢ Node label photo of relevant RBS should include XMU details (XMU<br>and XMU no. mentioned along with sector information and<br>technology<br>➢ XMU/R503(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SFP (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ XMU and SFP barcode with the location mentioned on barcode<br>photos also need to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR<br>along with port connectivity information

DUW Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of DUW<br>➢ Location of DUW should be clearly visible.<br>➢ Close up photo of DUW showing DUW type, all the ports with port no.<br>where SFPs and DAC cables are connected.<br>➢ Node label photo of relevant RBS should include DUW details (node<br>code should include enb ID, DUW no., Technology and sector)<br>➢ DUW(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SFP & DAC cable(Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template.<br>➢ DUW, SFP & DAC cable barcode with the location mentioned on<br>barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR<br>along with port connectivity information

  • RBS 6601 and DUW Label<br>Mandatory Requirements<br>➢ Node label of RBS6601 should be clearly visible.<br>➢ Node label of RBS 6601 should include the site name, node code,<br>node address manager ID, RBS 6601 location, and equipment<br>present in RBS 6601with equipment name and no. mentioned<br>along with sector information and technology<br>➢ For DUW added in 6601 node code should include RBS ID, DUW<br>no., technology and sector<br>Ensure Technologies mentioned on labels are correct as per RFSR.

BB5216 Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of BB5216<br>➢ Location of BB5216 should be clearly visible.<br>➢ Close up photo of BB5216 showing BB5216 as marked in a photo, all<br>the ports with port no. where SFPs are connected.<br>➢ Node label photo of relevant RBS should include BB5216 details<br>(node code should include RBS ID, BB5216 no., technology and<br>sector)<br>➢ BB5216(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SFP (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ BB5216 & SFP barcode with the location mentioned on barcode<br>photos also need to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR<br>along with port connectivity information

  • RBS 6601 and BB5216 Photo Requirement– Node<br>label<br>Mandatory Requirements<br>➢ Node label of RBS6601 should be clearly visible.<br>➢ Node label of RBS 6601 should include the site name, node code,<br>node address manager ID, RBS 6601 location, and equipment<br>present in RBS 6601with equipment name and no. mentioned<br>along with sector information and correct technology.<br>➢ For BB5216 added in 6601 node code should include RBS ID,<br>BB5216 no., technology and sector<br>Ensure technologies mentioned labels are correct as per<br>RFSR.

RBS6202 (Rack View and Close up)

  • Mandatory Requirements<br>➢ Rack view photo should be clear and all the<br>equipment added in the rack should be clearly visible.<br>➢ Location label should be present and clearly visible.<br>➢ Open and close box photo of RBS6202 is required

  • Open Box Photo of RBS6202<br>Mandatory Requirements<br>➢ Open box photo of RBS6202<br>➢ All equipment installed in RBS6202 must be clearly visible.<br>➢ Equipment (BB5216/XMU/DUW) installed in RBS6202 all SFP ports<br>should be clearly visible, with port no.<br>➢ If any equipment is installed in Magazine 03(DU adapter unit), an open box<br>photo with a clear photo of ports with SFP connectivity should be provided<br>with port no.<br>➢ Node code photo is mandatory<br>➢ RBS6202 (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ PCF, SCU, PDU, FRU, RUS, PFU, DU adapter (Type, Serial no, Revision,<br>DOM, Location) should also be captured in the MITS template.<br>➢ RBS6202 unit barcode photos also need to be captured in MITS for backup<br>purposes.

  • RBS 6202 Photo Requirement– Node label<br>Site Name<br>Node Code<br>Node Manager Address ID<br>RBS type<br>Enb ID<br>Equipment<br>Equipment technology<br>Sectors<br>BBH Node code

DWDM (Open View and Closed View)

  • Mandatory Requirements<br>➢ DWDM cassettes (Type, Serial no., Revision, DOM, Location)<br>➢ Open and close view photos of DWDM<br>➢ Cassettes barcode photos also need to be captured in MITS for<br>backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.

  • DWDM Labelling when GCF(wwdm)-CRAN<br>andatory Requirements<br>➢ DWDM/WWDM (Type, Serial no., Revision,<br>DOM, Location) also need to be captured in<br>the MITS template.<br>➢ Open DWDM/WWDM photo is required<br>➢ DWDM/WWDM type should clearly be<br>visible from photos<br>➢ DWDM/WWDM barcode photos also need<br>to be captured in MITS for backup<br>purposes.

  • DWDM Type<br>DWDM/WWDM<br>Node label should<br>match with actual<br>photos(Positions<br>mentioned in Node<br>label should match<br>with photos<br>DWDM/WWDM<br>Node label

DWDM Labelling when no GCF(wwdm)-CRAN

  • Mandatory Requirements<br>➢ DWDM (Type, Serial no., Revision, DOM,<br>Location) also need to be captured in the<br>MITS template.<br>➢ Open DWDM photo is required<br>➢ DWDM type should clearly be visible from<br>photos<br>➢ DWDM barcode photos also need to be<br>captured in MITS for backup purp<br>Labeling standards should<br>be as per MOP and should<br>be site-specific.

  • DWDM Type<br>DWDM Node label<br>should match with<br>actual<br>photos(Positions<br>mentioned in Node<br>label should match<br>with photos<br>DWDM Node label

DWDM Labelling-HRAN

  • Mandatory Requirements<br>➢ DWDM/WWDM (Type, Serial no., Revision,<br>DOM, Location) also need to be captured in<br>the MITS template.<br>➢ Open DWDM/WWDM photo is required<br>➢ DWDM/WWDM type should clearly be<br>visible from photos<br>➢ DWDM/WWDM barcode photos also need<br>to be captured in MITS for backup<br>purposes.<br>Labeling standards should<br>be as per MOP and should<br>be site-specific.

  • DWDM Type<br>DWDM Node label<br>should match with<br>actual<br>photos(Positions<br>mentioned in Node<br>label should match<br>with photos<br>DWDM Node label

Router 6651 Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of 6651 router<br>➢ Location of 6651 router should be clearly visible.<br>➢ Close up photo of 6651 router<br>➢ Node label photo of 6651 router<br>➢ 6651 router (Type, Serial No, Revision, DOM, Location) should also be captured<br>in MITS template.<br>➢ 6651 router tray (Type, Serial No, Revision, DOM, Location) should also be<br>captured in MITS template.<br>➢ 6651 router fan unit (Type, Serial No, Revision, DOM, Location) should also be<br>captured in MITS template.<br>➢ 6651 SFP (Type, Serial No, Revision, DOM, Location) should also be captured<br>in MITS template.<br>➢ 6651 Blank panel SXK1253793/1 (Type, Serial No, Revision, DOM, Location)<br>should also be captured in MITS template.<br>➢ 6651 Router, tray, fan unit and SFP barcode Photos also need to be captured<br>in MITS for backup purpose.

  • SFP/Cable Associated with equipment's should be clearly visible with port No's<br>and should be in active green state.<br><br>Node Code requirements<br>Site Name<br>Router Type<br>Router Code<br>Location

  • Router Labels<br>Node Code requirements<br>Site Name<br>Router Type<br>Router Code<br>Location<br>GPON naming<br>GCF/WWDM Location<br>BBH Router Code<br>DWDM type<br>DWDM Location

6675 Router Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of 6675 cell site router<br>➢ Location of 6675 cell site router should be clearly visible.<br>➢ Close up photo of 6675 cell site router<br>➢ Node label photo of 6675 cell site router<br>➢ 6675 cell site router (Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template.<br>➢ 6675 cell site router SFP(Type, Serial no, Revision, DOM, Location)<br>should also be captured in the MITS template.<br>➢ 6675 Router fan unit (Type, Serial no, Revision, DOM, Location)<br>should also be captured in the MITS template.<br>➢ 6675 Router, fan unit and SFP unit barcode photos also need to be<br>captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.

  • Node Code requirements<br>Site Name<br>Router Type<br>Router Node Code<br>Location

BB6648 & RP6651 Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of BB6648/RP6651<br>➢ Location of BB6648/RP6651 should be clearly visible.<br>➢ Close up photo of BB6648/RP6651<br>➢ Node label photo of BB6648/RP6651.<br>➢ BB6648/RP6651 (Type, Serial no, Revision, DOM,<br>Location) should also be captured in the MITS template.<br>➢ BB6648/RP6651 fan unit (Type, Serial no, Revision,<br>DOM, Location) should also be captured in the MITS<br>template.<br>➢ BB6648/RP6651 and fan unit barcode photos also need<br>to be captured in MITS for backup purposes.<br>➢ Correct feeder no. type and lengths need to be captured<br>in RFSR and correct port connectivity needs to be<br>mentioned on RFSR.

  • BB6648 & RP6651 Node label Photo Requirement<br>Node Code requirements<br>Site Name<br>Node Code<br>Address id<br>Location<br>Baseband Type<br>Band Information<br>eNB ID/gNB id<br>Technology &<br>Sector Information

  • Ensure technologies mentioned on labels are correct as per RFSR.<br>BB6648 RP6651<br>All Label example templates MUST be modified to be site specific and correct- Remove WCDMA 850<br>and LTE/NR Bands as applicable

SIU Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of SIU<br>➢ Location of SIU should be clearly visible.<br>➢ Close up photo of SIU<br>➢ Node label photo of SIU<br>➢ SIU(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SFP installed at SIU in MTX(Type, Serial no, Revision, DOM, Location)<br>should also be captured in the MITS template.<br>➢ SIU and SFP barcode photos also need to be captured(SFP type,<br>Serial no. DOM should be clearly visible on photos) photos should be<br>uploaded in the MITS section.<br>Photo capturing SIU connections should match with MTX design.<br>Install SFP type as per design if any changes are required contact<br>designer and MTX design should be redlined accordingly and provided<br>to designer

  • Node Code requirements<br>Site Name<br>SIU Node Code<br>Location

Fibre tray Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of Tray<br>➢ Location of Tray should also be clearly visible.<br>➢ Tray any type of tray installed (Type, Serial No, Revision, DOM,<br>Location) should be captured in MITS template.<br>➢ If any fibre tray relocated need to mention the same in Redline markup S0-1 and E1 sheets and provide (Type, Serial No, Revision, DOM,<br>Location) in MITS section.<br>➢ Any fibre tray installed at site should be captured in redline mark-up<br>S0-1 and E1 sheets.

Patch Panel Photo Requirement

  • Mandatory Requirements<br>➢ Rack view photo of patch panel<br>➢ Location of patch panel should be clearly visible.<br>➢ Patch panel (Type, Serial no, Revision, DOM, Location) should be<br>captured in the MITS template.<br>➢ Patch panel(Type, Product code, Serial no, Revision, DOM, Location)<br>should be captured in the MITS template.<br>➢ Patch panel cassette (Type, Product code, Serial No, Revision, DOM,<br>Location) should also be captured in the MITS template.<br>➢ Patch barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ MPO cassettes associated with patch panel each cassette serial No.<br>should be captured in MITS template.

SPD Photo Requirement

  • Mandatory Requirements<br>➢ Close box photo of SPD<br>➢ Open box photo of SPD.<br>➢ SPD location photo<br>➢ SPD label photo<br>➢ SPD power label photo<br>➢ Clear view photo of all the CBs showing clear ampere rating and<br>manufacturer for each CB<br>➢ Clear view photo of feeder no. entering the SPD<br>➢ Padlock should be visible<br>➢ SPD(Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ SPD barcode photos also need to be captured in MITS for backup<br>purposes.<br>➢ Correct feeder no. type and lengths need to be captured in RFSR and<br>correct port connectivity needs to be mentioned on RFSR.

  • SPD Power Label<br>Mandatory Requirements<br>➢ Location on SPD power label should match with SPD location label<br>➢ PWR ID: actual power id of the respective power system to be<br>mentioned here, dummy power id should not be used.<br>➢ Location of the parent power system: respective power system<br>location from which SPD is getting supply.<br>➢ Location of Distribution fuse should match with power legend of the<br>respective power system

  • SPD Label<br>Mandatory Requirements<br>➢ CB of SPD(ON/OFF) and SPD label should match<br>➢ Feeder no. mentioned should match with feeder entry labels and<br>feeder entry labeling should be correct<br>➢ Cell names should be as per respective technologies associated with<br>CB<br>➢ Technology, equipment, port no. and antenna no. should be correct<br>and as per standards.<br>➢ The port numbers on the SPD label to be matched as per<br>XMU/BB6630/DWDM port connections. Both photos & SPD labels<br>need to have the same port connectivity.<br>➢ XMU-X, BB6630-X – should match with respective equipment node<br>label and its respective technologies.<br>➢ Here X represents numbering(1/2/3…)

Augmentation Box

  • Mandatory Points<br>➢ Augmentation box full view with<br>location label photo required.<br>➢ Augmentation box open photos<br>required<br>➢ Power ID legend photos<br>required.

Power System

  • Mandatory Requirements<br>➢ Full view photo of power system showing all the equipment's and<br>location label clearly visible<br>➢ Clear view photo of all the CBs showing clear ampere rating and<br>manufacturer for each CB<br>➢ Power rack and associated equipment<br>(Rectifiers/Convertors/Batteries/extension racks )-details to be<br>captured in SB template and barcode photos also need to be captured<br>in MITS for backup purposes.<br>➢ Power rack and associated equipment<br>(Rectifiers/Convertors/Batteries/extension racks(Type,<br>Manufacturing code, Serial no, Revision, DOM) should also be<br>captured in SB template.

  • Power Rack CB close view<br>Mandatory Requirements<br>➢ Clear view photo of all the CB’s showing clear ampere rating<br>and manufacturer for each CB and CB numbering

  • Power Rack Power legend<br>Mandatory Requirements<br>➢ Power legend and description of the same should be clearly visible.<br>➢ Power system CB ON/OFF status should match with the power legend<br>and E4 sheet of redline mark-up.<br>➢ All descriptions in the power legend should be correct.<br>➢ Equipment technologies/ type and Location should be correctly<br>mentioned.<br>➢ In case of Augmentation SPD is used on-site, information of the same is<br>to be captured in the power legend.<br>➢ Power legend description and E4 sheet CB description should match in<br>redline.<br>➢ Labelling standards should be as per MOP and should be site-specific.

Power Rack Batteries/Rectifiers/ Convertors

  • Mandatory Requirements<br>➢ Clear view photos of batteries, rectifiers, and convertors should be<br>provided.<br>➢ Battery type, rectifier, convertor, and monitor type should be visible<br>from photos.<br>➢ No of rectifier/convertor/monitor/batteries should match in redline<br>mark-up on S0-1, E1, and E4 sheets.<br>➢ Battery type, rectifier, convertor, and monitor type should match in<br>redline mark-up on S0-1, E1, and E4 sheets.<br>➢ Caution labels need to be fixed on blank plates of<br>rectifiers/convertors with maximum no. rectifiers/convertors<br>mentioned on labels in accordance with the FC drawing

Enatel DC/DC Converter

  • Mandatory Requirements<br>➢ Full view photo of power system showing all the equipment's and<br>location label clearly visible<br>➢ Clear view photo of all the CBs showing clear ampere rating and<br>manufacturer for each CB<br>➢ Clear view photo showing Convertor and monitor type and its<br>manufacturer and type.<br>➢ Power rack and associated equipment (Convertors/Monitor/rack )-<br>details to be captured in SB template and barcode photos also need<br>to be captured in MITS for backup purposes.<br>➢ Power rack and associated equipment (Convertors/Monitor<br>racks(Type, Manufacturing code, Serial no, Revision, DOM) should<br>also be captured in SB template.

  • Enatel DC/DC Converter<br>Mandatory Requirements<br>➢ Power legend and description of the same should<br>be clearly visible.<br>➢ Power system CB ON/OFF status should match<br>with the power legend and E4 sheet of redline<br>mark-up.<br>➢ Clear view photo of all the CB’s showing clear<br>ampere rating and manufacturer for each CB and<br>CB numbering<br>➢ All descriptions in the power legend should be<br>correct.<br>➢ Equipment technologies/ type and Location<br>should be correctly mentioned.<br>➢ In case of Augmentation SPD is used on-site,<br>information of the same is to be captured in the<br>power legend.<br>➢ Power legend description and E4 sheet CB<br>description should match in redline.<br>➢ Labelling standards should be as per MOP and<br>should be site-specific.<br>➢ Power ID legend photos required with all<br>details(Location/Power id/Location of parent<br>power system/Location of dist Fuse) should be<br>correct and as per standards

Distribution board

  • Mandatory Requirements<br>➢ Full view photo of distribution board<br>➢ Clear view photo of all the CBs showing clear ampere<br>rating and manufacturer for each CB<br>➢ Photo of distribution board label with the correct<br>description as per standards.

ESC

  • Mandatory Requirements<br>➢ Full rack view photo ESC showing ESC and rack location label.<br>➢ Close view photo of ESC with all ports cables/SFP clearly visible.<br>➢ Node label photo of ESC<br>➢ ESC entry in power legend of power system<br>➢ ESC (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.<br>➢ ESC SFP/cable (Type, Serial no, Revision, DOM, Location) should<br>also be captured in the MITS template.<br>➢ ESC needs to be markup in redlines in case of a new install.

OFDP Photo location label and open photo

  • Mandatory Requirements<br>➢ OFDP open photo<br>➢ OFDP close photos<br>➢ OFDP label<br>➢ OFDP (Type, Serial no, Revision, DOM, Location) should also be<br>captured in the MITS template.

Telstra DBORS Photo Guide (Donor End)

Full Rack view Photos

  • Mandatory Requirements<br>➢ Full rack view photo with location label<br>clearly visible.<br>➢ Equipment associated with remote end<br>(BB5216, BB6630, chasis) should be clearly<br>visible.

RBS 6601

  • Mandatory Requirements<br>➢ RBS6601 clear view photo with<br>subrack no. clearly visible<br>➢ BB5216 associated with a remote end<br>should be clearly visible with all SFP in<br>active state.<br>➢ Node label photo of BB5216 with<br>correct details.<br>➢ RBS6601 SUP (Type, Serial no,<br>Revision, DOM, Location) should also<br>be captured in the MITS template.<br>➢ RBS6601 fan unit (Type, Serial no,<br>Revision, DOM, Location) should also<br>be captured in the MITS template.<br>➢ RBS6601 SUP and fan unit barcode<br>photos also need to be captured in<br>MITS for backup purposes.

BB5216

  • Mandatory Requirements<br>➢ RBS6601 clear view photo with sub-rack<br>no. clearly visible<br>➢ BB5216 associated with a remote end<br>should be clearly visible with all SFP in<br>active state.<br>➢ Node label photo of relevant RBS should<br>include BB5216 details.<br>➢ BB5216(Type, Serial no, Revision, DOM,<br>Location) should also be captured in the<br>MITS template.<br>➢ SFP (Type, Serial no, Revision, DOM,<br>Location) should also be captured in the<br>MITS template.<br>➢ BB5216 & SFP barcode with the location<br>mentioned on barcode photos also need to<br>be captured in MITS for backup purposes.

BB6630

  • Mandatory Requirements<br>➢ Close up photo of BB6630 associated with<br>remote end, with subrack No., SFP ports<br>visible and all SFP in active state.<br>➢ Node label photo of BB6630<br>➢ BB6630(Type, Serial No, Revision, DOM,<br>Location) should also be captured in MITS<br>template.<br>➢ BB6630 fan unit (Type, Serial No, Revision,<br>DOM, Location) should also be captured in<br>MITS template.<br>➢ BB6630 and fan unit barcode Photos also<br>need to be captured in MITS for backup<br>purpose.<br>➢ SFP Labeling photos required on the SFP<br>patch cables to find out where our SFP’s are<br>plugged in.

DWDM

  • Mandatory Requirements<br>➢ Chasis clear view photo with<br>subrack no. and donor code should<br>be clearly visible<br>➢ Chasis (Type, Serial no., Revision, DOM,<br>Location)

DWDM / WWDM

  • Mandatory Requirements<br>➢ DWDM/WWDM clear view photo<br>➢ Positions at which DWDM/WWDM installed<br>➢ DWDM type should be clearly visible from photos<br>➢ Node label photo<br>➢ DWDM/WWDM (Type, Serial no., Revision, DOM, Location)<br>also need to be captured in the MITS template.<br>➢ DWDM/WWDM barcode photos also need to be captured in<br>MITS for backup purposes.

R6675

  • Mandatory Requirements<br>➢ R6675 clear view photos with sub-rack no.<br>clearly visible<br>➢ R6675 associated with remote end should be<br>clearly visible with all SFP in active state as per<br>MTX design.<br>➢ Node label photo of relevant RBS should<br>include R6675 details.<br>➢ R6675(Type, Serial no, Revision, DOM,<br>Location) should also be captured in the MITS<br>template.<br>➢ SFP (Type, Serial no, Revision, DOM, Location)<br>should also be captured in the MITS template.<br>➢ R6675 & SFP barcode with the location<br>mentioned on barcode photos also need to be<br>captured in MITS for backup purposes.<br>➢ R6675 naming convention should be correct<br>and router-id is mandatory to be mentioned on<br>naming convention

Fibre Tray

  • Mandatory Requirements<br>➢ Rack view photo of tray<br>➢ Sub rack no. should be clearly visible<br>➢ Tray (Type, Serial no, Revision, DOM, Location) should be<br>captured in the MITS template.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.