Information
-
Document No.
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
ALCOHOL BASED HAND RUB ABHR (K-211)
-
Corridors are at least 6 feet wide
-
Dispensers are installed at least 4 feet apart
-
Dispensers are not installed over or adjacent to an ignition source such as electrical switches and/or outlets
-
Where hallways are carpeted, the building is 100% sprinkled
-
Dispensers do not exceed a capacity of 1.2 liters
-
Not more than 10 gallons in a single smoke compartment
CONSTRUCTION / RENOVATIONS
-
Has any modification of more than 50% or 4,500 sq ft of the smoke compartment been done
-
Has any modification of less than 50% or 4,500 sq ft of the smoke compartment been done
-
Have any major LSC systems been replaced in the last 5 years (fire alarm, sprinkler system, generator, etc)
CORRIDOR WALLS / FIRE WALLS / SMOKE WALLS K-11, K-17, K-21, K-25, K-27, K-39
-
Corridors are separated from use areas by walls that form a barrier to limit the transfer of smoke and, for existing construction, required to have a fire resistance rating of 30 minutes.
-
Smoke Barrier / Fire Walls are constructed from outside wall to outside wall or other smoke/fire barrier and from floor to roof/floor deck above
-
Penetrations are sealed with rated materials. (No expanding foam unless fire rated)
-
Only products rated by UL and FM are used for penetrations
-
Fire rated ceiling tiles are replaced with fire rated ceiling tiles.
CORRIDOR WIDTH / MEANS OF EGRESS K-39, K-72, K-73
-
MONITOR CORRIDORS SERVING AS EXIT ACCESS TO ENSURE THAT THEY ARE CLEAR AND UNOBSTRUCTED
-
Linen carts, soiled utility carts, wheelchairs and lifts are not stored in hallways. (Isolation carts and crash carts are permissible in the corridors)
-
Furniture and plants are not placed in the hallway that may impede evacuation.
-
Decorations are not combustable and are flame resistant (review interior finish documents for flame spread documentation) <br>NOTE: Combustible decorations, such as photographs and paintings, in limited quantities that do not pose a fire hazard of fire development or spread is not present)
-
Linen carts, soiled utility carts, wheelchairs and lifts are considered stored if not in use for over 30 minutes in a corridor. <br>(When appropriate staff is around and using something, it is to be considered being in use)
-
"Stop Signs" attached to exit doors do not obstruct egress or cover door hardware.
DOORS K-18, K-21, K-25, K-27, K-28, K-29, K-38
-
INSPECT DOORS TO ENSURE THAT:
-
Self Closing and Automatic devices are installed properly and are functioning
-
Smoke Doors and Doors opening into the corridor close properly and resist the passage of smoke
-
Gasket material used to correct door gaps is of a rated material (weather stripping is not allowed or rated)
-
Doors in corridors close freely, unobstructed and latch positively in the door frame. Doors open freely with door hardware
-
Door latches open with one motion
-
Doors protecting a hazardous area are self closing and latch positively in the door frame
-
Smoke barrier doors that swing in the same direction are required to have a coordinator to ensure doors close properly which allows one door to close first preventing the doors from hitting. (Astragal coordinator)
-
Magnetically locked or delay egress locking arrangements
-
Doors release appropriately
-
No more than one delayed egress locked door in the path of egress travel
-
Randomly selected staff are aware of how to bypass magnetically locked or delay egress locking arrangements
-
Doors do not reactivate if the fire alarm system is placed in silent mode. (Fire alarm must be reset for doors to relock)
-
Doors with magnetic locking devices without the delayed egress function shall unlock upon activation of the complete fire alarm system.
-
Self closing door hold opens
-
Doors in exit corridors, stairwell enclosures, horizontal exits, smoke barriers and hazardous areas are only held open by a device that automatically closes the door upon activation of fire alarm and/or local smoke detector and/or automatic sprinkler system
-
Exit doors or exit access doors are not painted/disguised in a manner that obstructs the use of the door
ELECTRICAL (K-106, K-145, K-146, K-147)
-
Power strips are not in use in resident rooms
-
Medical equipment including the residet bed are not plugged in a power strip
-
Includes iv, tube feeding pumps, oxygen concentrators, etc...
-
Power strips are not used in typically wet locations
-
Hair dryers, refridgerators are not plugged into power strips
-
Heat producing appliances are not plugged into power strips
-
Appliances used for cooling are not plugged in to power strips
-
Maintain 3 foot clearance around all electrical panels
-
All electrical equipment is in good repair
-
Electrical cords and plugs do not have frayed or exposed wires
-
Electrical outlets have appropriate cover plates
-
Light switches have appropriate cover plates
-
Junction boxes have appropriate cover plates
EMERGENCY LIGHTING (K-45, K-46)
-
Emergency battery lighting is tested for 30 seconds every month
-
Monthly testing information is maintained on a log
-
Emergency battery lighting is tested for 1.5 hours annually
-
Annual testing information is maintained on a log
-
Exterior emergency lighting is either battery powered or generator supplied
-
Exterior emergency lights have either two lamps in one fixture or two fixtures
-
Exit discharge emergency lighting functions for a minimum of 1.5 hours
-
Rooms that exceed 1,000 sq ft in area have illuminated exit signs
-
Exit signs in rooms that exceed 1,000 sq ft in area provided emergency power for 1.5 hours
EXITS (K-38, K-47, K-72)
-
Exit and directional signage properly provide direction for egress path
-
Exit signs provide continuious illumination
-
Exit signs area serviced by emergency power and appropriately tested with documentation
-
Exit access are readily accessable at all times and the means of egress is free of obstructions or impedments to full instant use
-
Exit discharges outside the building have a hard surface to the public way
-
Exit discharges outside the building are usable in inclement weather (snow, rain) without impediments
-
Exit discharges outside of the building are illuminated along the path or egress to the public way
-
Doors leading to courtyards that DO NOT provide egress to the public way are appropriately marked "NO EXIT"
FIRE ALARM SYSTEM (K-51, K-52, K-54, K-60, K-107)
-
Fire alarm system is maintained in accordance with NFPA 72, National Fire Alarm Code, 1999 Edition
-
Fire alarm testing and maintenance records are available for inspection
-
Fire alarm panel is installed in a supervised location
-
Annual fire alarm testing documentation is complete, accurate and documents test results for all initiating devices
-
Annual fire alarm testing documentation is complete, accurate and documents test results for all supervisory devices
-
Verify that the fire alarm system is connected to the sprinkler system
-
There is documentation that indicated that the fire alarm activates if the sprinkler system is activated
-
Date fire alarm last checked and necessary maintenance provided
-
Name of licensed contractor providing inspection / service
-
If Michigan, is contractor Act 144 certified and documentation of contractors certification is available at the community
FIRE DRILLS (K-50)
-
There is a plan in place for the protection of all persons in the event of fire
-
Fire drills are conducted, One drill, per shift, per quarter (drills at shift change count as ONE drill)
-
Fire drill records include documentation that transmission of an alarm was sent to the monitoring station
-
Third shift fire drills
-
QUARTER 1
-
QUARTER 2
-
QUARTER 3
-
QUARTER 4
-
First shift fire drills
-
QUARTER 1
-
QUARTER 2
-
QUARTER 3
-
QUARTER 4
-
Second shift fire drills
-
QUARTER 1
-
QUARTER 2
-
QUARTER 3
-
QUARTER 4
-
Fire drill records contain the following information
-
Differing times for drills on each shift (at least 2 hour variation)
-
Varying conditions of drills (a drill conducted at meal time is a varying condition)
-
Differing days of the week, including weekends
-
Involvment of all departments
-
Documented observations of staff responses
-
Documentation of equipment function (release of locked or delayed egress doors, magnetic hold opens, etc…)
-
Documentation of the time the monitoring agency received the alarm notification
-
Fire drills are compliant (Held quarterly, per shift, at unexpected times and under varying conditions
FIRE EXTINGUISHERS (K-64)
-
Portable fire extinguishers are inspected monthly
-
By facility staff
-
By outside vendor
-
Portable fire extinguishers are maintained annually
-
Dry chemical extinguishers have the chemicals changed every six (6) years
-
Hydrostatic testing of vessels every twelve (12) years
-
Hydrostatic testing of CO2 vessels every five (5) years
-
Extinguishers do not exceed a gross weight of 40 lbs
-
Extinguishers exceed a gross weight of 40 lbs are not mounted more than five (5) feet above the floor at the top of the extinguisher
-
Extinguishers having a gross weight of more than 40 lbs are installed so that the top of the extinguisher does not exceed 3.5 feet above the floor
-
No extinguisher shall be mounted more than 4 inches from the bottom of the extinguisher to the floor
FIRE SAFETY PLAN (K-48)
-
Last date reviewed
-
The fire safety plan includes the following items:
-
Use of alarms
-
Transmission of alarms to forces (fire department)
-
Response to alarms
-
Isolation of fire
-
Evacuation of the immediate area
-
Evacuation of the smoke compartment
-
Preperation of floors and building for evacuation
-
Extinguishment of fire
FIRE WATCH AND SYSTEMS IMPAIRMENT
-
The community has a policy for impairment of the automatic sprinkler system and/or fire alarm system if it is unavailable more than 4 hours in any continuious 24 hour period
-
The community has a policy on approved fire watch
-
Approved fire watch must include the following elements:
-
Involves at least one person with fire watch responsibility beyond normal staffing assignment(s)
-
Individuals in fire watch are trained in fire prevention and in occupant and fire department notification of fire
-
Notification of local forces of the impariment
-
Notification of the AHJ (Authority having jurisdiction) of the community
-
Notification of any other licensing authority having jurisdiction
-
Addresses separate situations in which the sprinkler system and/or fire alarm system is out of service for more that 4 hours in any 24 hours
-
A log is available to document and review fire watch
GENERATORS (K-105, K-108, K-144)
-
Generator(s) are inspected weekly
-
Generator(s) are exercised under load for 30 minute per month (Startup and cool down time are not part of the 30 minutes)
-
Under operating temperature conditions at least 30% of the EPS nameplate rating
-
Loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer
-
DIESEL GENERATORS, that do not meet the above requirments are exercised monthly with the available EPS load
-
DIESEL GENERATORS, that do not meet the above requirments are load banked tested annually
-
Inspection records include all of the following:
-
Date of inspection
-
Time of inspection
-
Generators general condition (leaks, hoses, fuel supply, oil, belts, battery, cooling system transfer switch)
-
Start and End times of the load test including start-up time and cool down time
-
Generator output readings during load test
-
Signature of individual conducting the inspection, testing and/or repairs
-
Battery powered emergency lighting is available at generator set location inside building
-
Verify battery powered emergency lighting is check monthly for 30 seconds and annually for 1.5 hours
-
Is there at least a 90 minute fuel supply
-
Contingency plan in place and written agreement for the resupplying of fuel in an emergency situation
-
Remote generator annunciator panel is attended in a area staffed 24/7, 7 days per week
-
EPS transer switch activates and provides power within 10 seconds to critical branch circuits
-
Natural Gas generators must comply with the following:
-
There is a letter of reliability on file in the community from their natural gas provider that contains the following:
-
Description supporting the reasonable reliability assertion
-
Statement that the fuel source is reliable
-
Statement of the low likelihood of an interruption
-
Description supporting the low interruption assertion
-
Signature from technical personnel
HAZARDOUS AREAS (K-29)
-
Hazardous areas have a solid wood core door with automatic self closing device
-
hazardous areas doors latch positively
-
Mechanical rooms are clean and orderly
-
Mechanical rooms are not used for combustable storage
-
Clearance of 3 feet is maintained around all heat producing equipment such as a gas furnace
HEATING, VENTILATION, AIR CONDITIONING and COOLING. (HVAC) (K-67, K-68, K-104)
-
Fire dampers are inspected every two years to ensure no rusting or blockage, noting hinges and other moving parts
-
Fire dampers fuseable links are changed and damper exercised every 4 years
-
Fire dampers are cleaned and lubricated as necessary and documentated
HOOD SUPPRESSION SYSTEM (K-69)
-
Hood is inspected and documentation that the hood, ducts and suppression system nozzles are free of grease and dirt buildup
-
Hood suppression system is maintained and inspected in accordance with NFPA 96
-
Fuel sources are automatically disconnected when the extinguishing system is activated
-
Hood suppression system activator is located in the path of egress
-
Activation of the hood suppression system initiates the communitys alarm system
-
The hood suppression system is UL 300 compliant
-
Dining services staff are versed in activation of the hood suppression system
-
Is deep fryer at least 16 inches from stove
-
If fryer is less that 16" away from stove, then a eight (8) inch shield is installed on the tallest appliance
INTERIOR FINISH, FURNISHINGS & DECORATIONS (K-14, K-15, K-16, K-72, K-73, K-74, K-130)
-
Finishes meet Class A, B or C ratings in sprinklered buildings
-
The community has documentation of flame spread and smoke ratings of all their interior finishes
-
Curtains have labels or tags indicating non flammability rating
-
Records are maintained of any community treated fire resistance materials
-
Combustable decorations are flame retardant (Photographs, paintings, etc…)
-
Decorations are not hung from fire sprinker heads and/or pipes
-
Highly flammable decorations are not used in the community (Hay bales, straw, fine tinsel, live christmas trees, etc…)
LAUNDRY / TRASH (K-29, K-75)
-
Soiled linen and trash are stored in rooms protected as hazardous areas
-
Soiled linen and trash are stored in room doors have automatic closers and positively latch
-
Linen containers in hallways or other areas do not exceed a combined 32 gallon capacity in a 64 sq ft area. Approx 8' x 8'
OXYGEN STORAGE (K-76, K-77, K-141, K-143)
-
Storage areas are secured against unauthorized entry
-
Storage area doors are equipped with self closing devices
-
Storage area doors are positive latching
-
Oxygen cylinders are seperated from combustible materials by a minimum distance of five (5) feet of the storage area is protected by an automatic sprinkler system
-
Cylinder and container storage locations meet temperature limitations (Cylinders are protected from reaching temperatures that could exceed 130 degrees ferinheit)
-
Storage area electrical wall fixtures are installed in fixed locations not less than 5 feet above the floor to protect from physical damage
-
Cylinders are protected to prevent damage to cylinders, valve, regulators or safety devices
-
Cylinders are not stored near elevators or locations where heavy objects could strike or fall on the cylinder
-
Freestanding cylinders are properly chained or supported in an appropriate cylinder stand or cart
-
Full and empty cylinders are are stored seperately
-
Community ensures that smoking, open flames, electrical heating elements and other sources of ignition do not occur in storage locations
-
Smoking, open flames, electrical heating elements and other sources of ignition do not occur within 20 feet of an outside storage location
-
Oxygen storage areas are properly identified (CAUTION - OXIDIZING GAS(ES) STORED WITHIN - NO SMOKING)
OXYGEN (TRANSFERRING LIQUID OXYGEN) (K-143)
-
Liquid oxygen is transferred in an area separated away from resident sleeping rooms
-
Liquid oxygen is transferred in an area seperated by 1-hour fire resistive construction
-
Liquid oxygen is transferred in an area seperated by 1-hour fire resistive construction has a door rating of 3/4 hour fire rating
-
Liquid oxygen transfering area is mechanically ventilated
-
Liquid oxygen transfering area has either a concrete or ceramic tile floor
-
Liquid oxygen transferring area is posted with signage indicating oxygen transfering is occuring and smoking is prohibited in the immediate area
PORTABLE SPACE HEATERS (K-70)
-
There are no portable space heaters used in resident sleeping areas
SMOKE DETECTORS (K-53, K-54)
-
Smoke detectors are tested annually to ensure each detector is operative and produces intended results
-
Smoke detector sensitivity is checked within one year of installation and every 2 years after that
-
Date of last sensitivity testing
-
Records are available showing the past two sensitivity testing by a qualified firm
-
Testing company name
-
Smoke detector sensitivity testing shows the exact response of each detector as it relates to the manufactures sensitive rating for that model detector
-
Smoke detectors are maintain and calibrated in accordance with NFPA 72
-
Smoke detectors are not placed within three (3) feet of a direct airflow supply or return air vent
-
Single station smoke detectors (Battery operated)
-
Inspected and tested monthly according to manufacturers instructions
-
Replace batteries according to manufacturers instructions (at least yearly)
-
Inspection and testing is documented and available
SMOKING REGULATIONS (K-66)
-
Metal containers with self closing cover devices which ashtrays can be emptied area available and used
-
Required Oxygen in Use - NO SMOKING signage is posted on all exterior doors
-
Community enforces its no smoking regulation
-
There are no cigarette butts visible on the ground or in areas where smoking is prohibited
SPRINKLER SYSTEMS (K-56, K-58, K-61, K-62)
-
The sprinkler system is inspected and maintained according to NFPA 25
-
Inspection records for the past 12 months are available for inspection
-
Inspection recommendations have been addressed from previous inspections
-
There are no gaps in celing and/or tiles adjacent to sprinkler heads (escussions are used)
-
High pile storage is a minimum of 18" below and away from sprinkler heads
-
Cubicle curtains are installed to prevent interference with the sprinkler system
-
There are at least two (2) replacement sprinkler heads for each type of sprinkler head used in the facility
-
There is a sprinkler head wrench kept with the spare sprinkler heads
-
Each compartment has the same type of sprinkler head in use
-
Sprinkler heads are clean, dust free and clear of paint or other obstructions
-
Note source of water supply for sprinkler system
-
Date sprinkler system last checked and necessary maintenance provided
-
If Michigan, is contractor Act 144 certified and documentation of contractors certification is available at the community
-
Gauges have been replaced or calibrated once every five (5) years
-
Date performed
WAIVERS
-
Record any waivers and expiration dates
SIGNATURES
-
SIGNATURE OF TSLC HOME OFFICE STAFF COMPLETING AUDIT