Needs Assessment

PART I - REQUIREMENTS: TVA-TSP-18.303 / ANSI Z358.1

  • Emergency showers, eyewash, or other deluge systems shall be provided in areas where any of the following conditions exist:

  • Acid, caustic, or other hazardous chemicals used, stored, or handled (and the possibility of spillage)

  • Explain:

  • Add media

  • Airborne dust or contaminants may be presen.

  • Explain:

  • Chemical fumes that may cause eye or skin irritation are present.

  • Explain:

Emergency Shower / Eyewash

  • Is there a permanent or self-contained (portable) unit currently in the area?

  • Type

  • Type Recommended for this Area

  • If the answer above is "yes" complete the questions in Section Part II of this assessment.

Installation Requirements

PART II - EQUIPMENT / UNID

  • TYPE

  • MANUFACTURER:

  • MODEL:

  • General Condition of Unit:

  • REFERENCE: TVA-TSP-18.303 / ANSI Z358.1 / OSHA 29CFR1910 General Industry

DISTANCES

  • Travel distance to units are 10 seconds or 55 feet

  • Explain:

  • Add media

  • Travel distance at Battery Charging/Servicing Stations, within 25 feet.

  • Explain:

  • Add media

  • Exposure to highly corrosive chemicals - may require flushing units immediately adjacent (e.g., <10ft. To the hazard)

  • Explain:

  • Add media

OBSTRUCTIONS & ACCESSIBILITY

  • Unit is free from obstruction and accessible from two directions and located on the same level as the hazard?

  • Explain:

  • Add media

  • A clear and unobstructed 45-inch radius is maintained around unit?

  • Explain:

  • Add media

  • Unit water spray will not contact electrical apparatus or power outlets?

  • Explain:

  • Add media

  • NOTE: Electrical outlets within 45-inch radius around unit shall be de-energized.

INSTALLATION

  • Unit is marked with High Visibility Identification Signs?

  • Explain:

  • Add media

  • Actuating valves are easily accessible & manipulated?

  • Explain:

  • Add media

  • Combination unit components are capable of operating simultaneously by the same user?

  • Explain:

  • Add media

  • Drench hose flow delivers a controlled flow of flushing fluid at a velocity low enough to be non-injurious?

  • Explain:

  • Add media

  • Drench hose used as eyewash - eye/face wash meets performance requirements as specified in Section 5/6 of ANSI Z358.1?

  • Explain:

  • Add media

  • The unit is subject to freezing and freeze protection is provided?

  • Explain:

  • Add media

  • Shower head is installed between 82 to 96 inches above surface floor of user?

  • Explain:

  • Add media

  • Shower delivers minimum 20 gallons per minute and provides a column of water 20" wide at 60" above the surface floor of user?

  • Explain:

  • Add media

  • Pull valve handle is no more 69" above the surface flow of user?

  • Explain:

  • Add media

  • Flushing flow remains on without the use of the Operator's hands and operates within 1 second from OFF to ON?

  • Explain:

  • Add media

  • Flushing fluid nozzles of eyewash - eye/face wash are located between 33 to 45 inches above the from the floor and a minimum of 6 inches from the wall?

  • Explain:

  • Add media

  • Flushing fluid nozzles provide a controlled flow to both eyes simultaneously at a velocity low enough to be non-injurious?

  • Explain:

  • Add media

  • Eyewash ONLY delivers a minimum of .4 gallons per minute of water for 15 minutes?

  • Explain:

  • Add media

  • Eye/face wash delivers minimum 3 gallons per minute of water for 15 minutes?

  • Explain:

  • Add media

  • The flushing fluid of an eyewash - eye/face wash covers the areas between the interior & exterior lines of a gauge at some point less than 8" above the eyewash nozzles?

  • Explain:

  • Add media

  • Eyewash - eye/face wash Valve remains ON when operated without the continuous use of the operator's hands and go from ON to OFF in one second or less?

  • Explain:

  • Add media

INSPECTIONS

  • The unit has identification (inspection tag) verifying weekly activation of a permanently installed units?

  • Comment:

  • The FACILITY has a Weekly and Annual PM (Preventative Maintenance) procedure in place?

  • Comment: ( PM Numbers - frequency performed)

SIGNATURE

  • AUDITOR / TITLE:

  • Add signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.