Title Page

  • Site conducted

  • Conducted on

  • Prepared by

Container Inspection

  • 1. Container Appearance Inspection: Make sure no damage or rust

  • 2. PCS exhaust duct Inspection: Make sure fixation stability

  • 3. PCS room door lock Inspection: Make sure that PCS escape lock can open smoothly

  • 4. Battery room door lock Inspection: Make sure that battery room pull rod lock can open

  • 5. Container Nameplate Inspection: Make sure container nameplate fix tightly

  • 6. Seal rubber gasket around container doors inspection: Make sure no damage, fix tightly

  • 7. Fireproof door between PCS room and Battery room Inspection: Make sure Fireproof door open/close smoothly

  • 8. Container internal cleaning: make sure no rubbish and no mud

  • 9.HMI Current Alarm Inspection: make sure no current alarm

  • 10.SPD in main power circuit Inspection: make sure SPD willow colour is not red

  • 11.HMI display Inspection: make sure HMI time correct, HMI running no delay, status indicator normal

PCS Inspection

  • 12.PCS Fan Inspection: make sure no abnormal noise when PCS fan is running

  • 13.PCS Dustproof Screen Inspection: Make sure PCS dustproof screen clean

  • 14.HMI history alarm Inspection: If some frequent fault occur, take photos about history alarm and feedback to BYD

  • 15.PCS Scram Button Inspection: test PCS scram button and make sure it work normally

  • 16.PCS Control Switcher Inspection: test PCS Control Switcher and make sure it work normally

  • 17.PCS AC/DC Breaker Inspection: make sure breaker open/close smoothly

  • 18.PCS Pre-charge Boards Inspections

  • 19.PCS AC Cables Inspections

  • 20.PCS DC Cables Inspections

PDC Inspection

  • 21.SPD in auxiliary power circuit Inspection: make sure SPD willow colour is not red

  • 22. UPS Inspection: General: inspect the UPS system, batteries and accessories. Cooling: check fans for operation. Connections: check and adjust all electrical connections (AC and DC). Functional: check all functions operate correctly

Battery &BMS Inspection

  • 23.Battery Appearance Inspection: make sure battery no shape-change and no leakage

  • 24.Battery Shelf Inspection: make sure battery shelf no shape-change.

  • 25.SOC calculation Inspection: charge/Discharge in manual mode and make sure SOC increase/decrease collectly.<br>

  • 26.Battery power cable and communcation cable Inspection: make sure cables no damage

  • 27. BMS Box DC Breaker Inspection: make sure breaker open/close smoothly

Fire Extinguish System

  • 28.The fire device outside container Inspection: No damage,no rubbish coverage

  • 29. Fire Controller Panel Inspection: The screen should shown "All normal".

  • 30. Fire Cylinder Pressure Inspection: One big cylinder in battery room and two small cylinders in PCS room.Make sure that the pointer in green area.

  • 31. Fire Manual/Auto Switcher: The Fire Manual/Auto Switcher should turn smoothly.

Lighting Inspection

  • 32.General Lighting Inspection

System Inspection

  • 33. Emerency Lighting Inspection: make sure emerency lighting can work without AC power.

  • 34. Air-condition Appearance Inspection: no damage, fix steadily

  • 35. Inspect condensate pipe to make sure no leakage.

Air-Condition Inspection

  • 36. Inspect the temperature setting if correct.

  • 37. Remove dust on the air entrance of air-condition indoor

  • 38. Remove dust on the radiator of air-condition outdoor unit.

  • HVAC 1 can run normally

  • HVAC 2 can run normally

  • HVAC 3 can run normally

  • HVAC 4 can run normally

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.