Title Page
-
Site conducted
-
Conducted on
-
Prepared by
Container Inspection
-
1. Container Appearance Inspection: Make sure no damage or rust
-
2. PCS exhaust duct Inspection: Make sure fixation stability
-
3. PCS room door lock Inspection: Make sure that PCS escape lock can open smoothly
-
4. Battery room door lock Inspection: Make sure that battery room pull rod lock can open
-
5. Container Nameplate Inspection: Make sure container nameplate fix tightly
-
6. Seal rubber gasket around container doors inspection: Make sure no damage, fix tightly
-
7. Fireproof door between PCS room and Battery room Inspection: Make sure Fireproof door open/close smoothly
-
8. Container internal cleaning: make sure no rubbish and no mud
-
9.HMI Current Alarm Inspection: make sure no current alarm
-
10.SPD in main power circuit Inspection: make sure SPD willow colour is not red
-
11.HMI display Inspection: make sure HMI time correct, HMI running no delay, status indicator normal
PCS Inspection
-
12.PCS Fan Inspection: make sure no abnormal noise when PCS fan is running
-
13.PCS Dustproof Screen Inspection: Make sure PCS dustproof screen clean
-
14.HMI history alarm Inspection: If some frequent fault occur, take photos about history alarm and feedback to BYD
-
15.PCS Scram Button Inspection: test PCS scram button and make sure it work normally
-
16.PCS Control Switcher Inspection: test PCS Control Switcher and make sure it work normally
-
17.PCS AC/DC Breaker Inspection: make sure breaker open/close smoothly
-
18.PCS Pre-charge Boards Inspections
-
19.PCS AC Cables Inspections
-
20.PCS DC Cables Inspections
PDC Inspection
-
21.SPD in auxiliary power circuit Inspection: make sure SPD willow colour is not red
-
22. UPS Inspection: General: inspect the UPS system, batteries and accessories. Cooling: check fans for operation. Connections: check and adjust all electrical connections (AC and DC). Functional: check all functions operate correctly
Battery &BMS Inspection
-
23.Battery Appearance Inspection: make sure battery no shape-change and no leakage
-
24.Battery Shelf Inspection: make sure battery shelf no shape-change.
-
25.SOC calculation Inspection: charge/Discharge in manual mode and make sure SOC increase/decrease collectly.<br>
-
26.Battery power cable and communcation cable Inspection: make sure cables no damage
-
27. BMS Box DC Breaker Inspection: make sure breaker open/close smoothly
Fire Extinguish System
-
28.The fire device outside container Inspection: No damage,no rubbish coverage
-
29. Fire Controller Panel Inspection: The screen should shown "All normal".
-
30. Fire Cylinder Pressure Inspection: One big cylinder in battery room and two small cylinders in PCS room.Make sure that the pointer in green area.
-
31. Fire Manual/Auto Switcher: The Fire Manual/Auto Switcher should turn smoothly.
Lighting Inspection
-
32.General Lighting Inspection
System Inspection
-
33. Emerency Lighting Inspection: make sure emerency lighting can work without AC power.
-
34. Air-condition Appearance Inspection: no damage, fix steadily
-
35. Inspect condensate pipe to make sure no leakage.
Air-Condition Inspection
-
36. Inspect the temperature setting if correct.
-
37. Remove dust on the air entrance of air-condition indoor
-
38. Remove dust on the radiator of air-condition outdoor unit.
-
HVAC 1 can run normally
-
HVAC 2 can run normally
-
HVAC 3 can run normally
-
HVAC 4 can run normally