Visual Inspection
Approved plans on location:
Piping and joints are uncovered:
Size of piping same as indicated on approved plans:
Type of piping and bedding material same as indicated on approved plans:
Piping follows same path and direction as indicated on approved plans:
Depth of piping is same as indicated on approved plans:
Thrust blocks at each change of direction:
Poly wrap of any ductile piping:
Terminates no more than 5 feet inside the building:
Terminates no more than 1 foot above finished floor:
Visual Inspection Status:
Utility Crossings / Encasement Inspection
Piping placed in separate trench:
Encasement provided at utility crossings within 10 feet:
Utility Crossing / Encasement Inspection Status:
Hydrostatic Test
Underground fire line must hold a minimum of 200 psi for 2 hours.
Start pressure (psi):
Pressure pump to be disconnected after underground fire line is pressurized to 200 psi.
End pressure (psi):
Pressure relieved and gauge returns to zero psi:
Hydrostatic Test Status:
Underground Line Flush
Flow through minimum of a 4 inch hose or pipe:
Hose or pipe restrained:
Observe flush until clear of all debris:
Underground Fire Line Flush Status:
Final Acceptance Test
As built drawings for any changes made:
Test certificate completed and copy provided:
Final Acceptance Test Status:
Inspection Status
Comments:
Visual Inspection:
Utility Crossing / Encasement Inspection:
Hydrostatic Test:
Underground Fire Line Flush:
Final Inspection:
- A. Hargrove - 840
- B. Patrick - 841
- P. Ayres - 842
- K. Clark - 843
Inspection Status:
Acknowledgement of Receipt
Persons who shall violate a provision of this code or shall fail to comply with any requirements thereof or who shall erect, install, alter, repair, or do work in violation of the approved construction documents or directive of the fire code official, or of a permit or certification used under provisions of this code, shall be guilty of a Class C Misdemeanor, punishable by a fine of not more than $2,000.00 dollars, or by imprisonment not to exceed 180 days, or both such fine and imprisonment. Each day that a violation continues after due notice has been served shall be deemed a separate offense.