Controlled, low velocity flow completely rinses eyes and face and is not injurious to user. (Section 6.1.1)
-
Water flow is sufficiently high to allow user to hold eyes open while rinsing. (Section 6.1.7)
-
Spray heads are protected from airborne contaminants. Covers are removed by water flow. (Section 6.1.3)
-
Unit delivers at least 3.0 gallons (11.4 liters) of water per minute for 15 minutes. (Section 6.1.6, 6.4.5)
-
Water flow pattern is positioned between 33" (83.8 cm) and 53" (134.6 cm) from the floor and at least 6" (15.3 cm) from the wall or nearest obstruction. (Section 6.4.4)
-
Hands-free stay-open valve activates in one second or less. (Section 6.1.4, 6.2)
-
Valve actuator is easy to locate and readily accessible to user. (Section 6.2)
-
Unit washes both eyes simultaneously. Water flow covers area indicated on Guardian test gauge at no more than 8" above spray heads. (Section 6.1.8)
-
Location: Install eye/face wash unit within 10 seconds (approximately 55 feet) of hazard, on the same level as hazard and with unobstructed travel path.
-
Identification: Identify eye/face wash location with highly visible sign. Area around eye/face wash unit shall be well-lit. (Section 6.4.3)
-
Water Temperature: Water delivered by eye/face wash shall be tepid (60-100°F). (Section 6.4.6; B6)
-
Training: Instruct all employees in the location and proper use of eye/face wash units. (Section 6.5.4)