Suction

RFPT

  • Have you called Wal-mart control to make them aware of your visit?

  • Call them.

Suction

  • Suction Groups

  • Suction Group
  • Rack suction pressure setpoint (psig)

  • Suction pressure deadband

  • Is the suction temperature stable?

  • Piping Deviation

  • Is the suction pressure stable?

  • Piping Deviation

  • Does the high and low suction suction alarm have a 15 min delay?

  • Control Deviation

  • Temporarily reduce suction alarm delay from 15 minutes to 15 seconds.

  • High suction pressure alarm (psig)

  • Override the suction pressure above the high suction pressure alarm setpoint

  • Does high suction alarm generate in the controller?

  • Control Deviation

  • Low suction pressure alarm (psig)

  • Override the suction pressure below the low suction pressure alarm setpoint

  • Does low suction alarm generate in the controller?

  • Control Deviation

  • Reset suction alarm delay back to 15 minutes.

Compressors

Compressor information

  • Compressors

  • Compressor
  • Model Number

  • Does this compressor match the submittal?

  • Equipment Deviation

  • Does the compressor have an unloader?

  • What type of unloader?

  • Does the compressor toggle switch work?

  • Equipment Deviation

  • Override the compressor and/or its unloader off through the BAS controller

  • Does the compressor/unloader turn off?

  • Control Deviation

  • Compressor Oil reservoir level

  • Oil reservoir level

  • Piping Deviation

Compressor staging

  • Suction Groups

  • Suction Group
  • Compressor staging and capacities

  • Stage
  • Which compressors are called for in this stage? (Novar Only)

  • Capacity (MBH)

  • Compressor staging up delay.

  • Compressor staging down delay.

  • Override the suction pressure above the suction target deadband.

  • Do compressors stage completely up?

  • Control Deviation

  • Override the suction pressure below the suction target deadband.

  • Do compressors stage completely down?

  • Control Deviation

Suction Float

Float circuits

  • Suction Groups

  • Suction Group
  • Who is the BAS provider?

  • Is there a float circuit and if so, does it match your plans?

  • Override float circuit temperature input below its target deadband.

  • Does the suction target float up?

  • Control Deviation

  • If system has already floated up, override float circuit temperature input above its target temperature.

  • Does the suction target float down?

  • Control Deviation

  • Are there 2 float circuits and if so, do they match the plans?

  • Control Deviation

  • Control Deviation

Subcooler

Subcooler

  • What is the target subcooled liquid temperature?

  • Does Subcooler liquid temp appear stable around 50degF?

  • Piping Deviation

  • Is Subcooler stage 1 cut in/cut out set to 55/45?

  • Control Deviation

  • What is the time delay?

  • What is the duration?

  • Is Subcooler stage 2 cut in/cut out set to 58/48?

  • Control Deviation

  • What is the time delay?

  • What is the duration?

  • Is Subcooler stage 3 cut in/cut out set to 60/50?

  • Control Deviation

  • What is the time delay?

  • What is the duration?

  • Is Subcooler LPR cut in/cut out set to 55/60?

  • Control Deviation

  • What is the time delay?

  • What is the duration?

  • Override the subcooled liquid temp below 45 degF.

  • Do all subcooler supply solenoid valves de-energize/close?

  • Piping Deviation

  • Does the LPR bypass solenoid energize/close?

  • Piping Deviation

  • Override the subcooled liquid temp to 56 degF.

  • Does subcooler stage 1 supply solenoid valve energize/open?

  • Piping Deviation

  • Override the subcooled liquid temp to 59 degF.

  • Does subcooler stage 1 supply solenoid valve de-energize/close?

  • Piping Deviation

  • Does subcooler stage 2 supply solenoid valve energize/open?

  • Piping Deviation

  • Override the subcooled liquid temp to 61 degF.

  • Does subcooler stage 1 supply solenoid valve energize/open?

  • Piping Deviation

  • Does subcooler stage 2 supply solenoid valve energize/open?

  • Piping Deviation

  • Does the LPR bypass solenoid de-energize/open?

  • Piping Deviation

  • Override the subcooled liquid temp to 54 degF.

  • Is subcooler stage 1 supply solenoid valve energize/open?

  • Piping Deviation

  • Is subcooler stage 2 supply solenoid valve energize/open?

  • Piping Deviation

  • Does the LPR bypass solenoid energize/close?

  • Piping Deviation

  • Override the subcooled liquid temp to 49 degF.

  • Does subcooler stage 1 supply solenoid valve de-energize/close?

  • Piping Deviation

  • Does subcooler stage 2 supply solenoid valve energize/open?

  • Piping Deviation

  • Override the subcooled liquid temp to 47degF.

  • Does subcooler stage 1 supply solenoid valve energize/open?

  • Piping Deviation

  • Does subcooler stage 2 supply solenoid valve de-energize/close?

  • Piping Deviation

  • Override the subcooled liquid temp below 45 degF.

  • Do all subcooler supply solenoid valves de-energize/close?

  • Piping Deviation

  • Does the LPR bypass solenoid energize/close?

  • Piping Deviation

  • Does Subcooler liquid temp appear stable around 75degF?

  • Piping Deviation

  • Is Subcooler stage 1 cut in/cut out set to 80/70degF?

  • Control Deviation

  • What is the time delay?

  • What is the duration?

  • Is Subcooler stage 2 cut in/cut out set to 83/73degF?

  • Control Deviation

  • What is the time delay?

  • What is the duration?

  • Is Subcooler stage 3 cut in/cut out set to 85/75 degF

  • Control Deviation

  • What is the time delay?

  • What is the duration?

  • Is Subcooler LPR cut in/cut out set to 80/85degF?

  • Control Deviation

  • What is the time delay?

  • What is the duration?

  • Override the subcooled liquid temp below 70 degF.

  • Do all subcooler supply solenoid valves de-energize/close?

  • Piping Deviation

  • Does the LPR bypass solenoid energize/close?

  • Piping Deviation

  • Override the subcooled liquid temp to 81degF.

  • Does subcooler stage 1 supply solenoid valve energize/open?

  • Piping Deviation

  • Override the subcooled liquid temp to 84degF.

  • Does subcooler stage 1 supply solenoid valve de-energize/close?

  • Piping Deviation

  • Does subcooler stage 2 supply solenoid valve energize/open?

  • Piping Deviation

  • Override the subcooled liquid temp to 86degF.

  • Does subcooler stage 1 supply solenoid valve energize/open?

  • Piping Deviation

  • Does subcooler stage 2 supply solenoid valve energize/open?

  • Piping Deviation

  • Does the LPR bypass solenoid de-energize/open?

  • Piping Deviation

  • Override the subcooled liquid temp to 79degF.

  • Is subcooler stage 1 supply solenoid valve energize/open?

  • Piping Deviation

  • Is subcooler stage 2 supply solenoid valve energize/open?

  • Piping Deviation

  • Does the LPR bypass solenoid energize/close?

  • Piping Deviation

  • Override the subcooled liquid temp to 74degF.

  • Does subcooler stage 1 supply solenoid valve de-energize/close?

  • Piping Deviation

  • Does subcooler stage 2 supply solenoid valve energize/open?

  • Piping Deviation

  • Override the subcooled liquid temp to 72degF.

  • Does subcooler stage 1 supply solenoid valve energize/open?

  • Piping Deviation

  • Does subcooler stage 2 supply solenoid valve de-energize/close?

  • Piping Deviation

  • Override the subcooled liquid temp below 70degF

  • Do all subcooler supply solenoid valves de-energize/close?

  • Piping Deviation

  • Does the LPR bypass solenoid energize/close?

  • Piping Deviation

  • Override the subcooled liquid temp below 70degF.

  • Do all subcooler supply solenoid valves de-energize/close?

  • Piping Deviation

  • Does the LPR bypass solenoid energize/close?

  • Piping Deviation

Surge Valve/Receiver Bypass Valve

Surge Valve/Receiver Bypass

  • What is the surge valve/receiver bypass cut in?

  • What is the surge valve/receiver bypass cut out?

  • What is the time delay?

  • What is the duration?

  • Override the drop leg temperature to below the cut in setpoint.

  • Does the surge valve/receiver bypass solenoid energize/open?

  • Piping Deviation

  • Override the drop leg temperature to above the cut out setpoint.

  • Does the surge valve/receiver bypass solenoid de-energize/close?

  • Piping Deviation

Discharge

Discharge

  • Is VFD bypass set to enable at 275 psig?

  • Control Deviation

  • Is VFD bypass set to disable at 325 psig?

  • Control Deviation

  • Override discharge pressure to 326 psig.

  • Does the VFD go into bypass (all fans should be at full speed)?

  • Control Deviation

  • Does the controller generate an alert indicating VFD bypass?

  • Control Deviation

  • Override discharge pressure below 275 psig.

  • Does VFD bypass discontinue?

  • Control Deviation

  • Is high discharge lockout set to 375 psig?

  • Override discharge pressure above 375 psig.

  • Do compressors shutdown and condenser go into VFD bypass?

  • Control Deviation

  • Does the controller generate an alarm indicating high discharge lockout?

  • Control Deviation

Condenser

Current Conditions

  • Current outside air temperature on the controller

  • Current outside air temperature on the VFD

  • Current drop leg temperature on the controller

  • Current saturated condensing temperature (drop leg) on the VFD

  • Refrigerant type

Condenser

  • What type of condenser is in operation?

  • Model Number

  • Is the condenser clean?

  • Piping Deviation

  • Verify the condenser fans are rotating the proper direction?

  • Piping Deviation

  • Is it an Emerson or Danfoss VFD?

  • Pr 61 - Pressure feedback pressure

  • Pr 62 - Extrapolated temperature based off feedback pressure?

  • Pr 63 - Ambient temperature sensor feedback?

  • Is Pr 66 in pressure or TD control mode?

  • Piping Deviation

  • Is Pr 67, condenser TD, set to 150 or 15 degF?

  • Piping Deviation

  • Is Pr 68, the minimum reference temperature, set to 80 degF?

  • Piping Deviation

  • Is Pr 18.27, maximum reference temperature, set to 2250?

  • Piping Deviation

  • Is the condenser TD set 19 degF?

  • Piping Deviation

  • Is the max TD reference 114degF?

  • Piping Deviation

  • Is the min TD reference 77degF?

  • Piping Deviation

  • When condenser TD is raised, do the fans react by slowing down?

  • Piping Deviation

  • When condenser TD is lowered, do the fans ramp up to compensate?

  • Piping Deviation

  • Pump cut in

  • Pump cut out

  • Does the pump cut in at its set point?

  • Does the pump cut out at its set point?

  • Model Number

  • Is the condenser clean?

  • Piping Deviation

  • Is it an Emerson or Danfoss VFD?

  • Pr 61 - Pressure feedback pressure

  • Pr 62 - Extrapolated temperature based off feedback pressure?

  • Pr 63 - Ambient temperature sensor feedback?

  • Is Pr 66 in pressure or TD control mode?

  • Piping Deviation

  • Is Pr 67, condenser TD, set to 150 or 15 degF?

  • Piping Deviation

  • Is Pr 68, the minimum reference temperature, set to 80 degF?

  • Piping Deviation

  • Is Pr 18.27, maximum reference temperature, set to 2250?

  • Piping Deviation

  • Is the condenser TD set 19 degF?

  • Piping Deviation

  • Is the max TD reference 114degF?

  • Piping Deviation

  • Is the min TD reference 77degF?

  • Piping Deviation

  • When condenser TD is raised, do the fans react by slowing down?

  • Piping Deviation

  • When condenser TD is lowered, do the fans ramp up to compensate?

  • Piping Deviation

Split condenser

  • Is it an Emerson or Danfoss VFD?

  • Is the split condenser cut in/out 138/214?

  • Piping Deviation

  • Which transducer is on the drop leg?

  • Is comparator value 0 (split condenser cut in) 24?

  • Piping Deviation

  • Is comparator value 1 (split condenser cut in) 30.5?

  • Piping Deviation

  • Is comparator value 0 (split condenser cut in) 21.2?

  • Piping Deviation

  • Is comparator value 1 (split condenser cut in) 26.4?

  • Piping Deviation

  • Is comparator value 0 (split condenser cut in) 16.2?

  • Piping Deviation

  • Is comparator value 1 (split condenser cut in) 21.4?

  • Piping Deviation

  • Verify that the VFD on delay is set to 300 seconds or 5 minutes?

  • Piping Deviation

  • Temporarily override the VFD delay to 5 seconds

  • If in full condensing mode, override the cut in comparator value (Danfoss) or cut in pressure (Emerson),above the current saturated condensing temperature.
    If in split condensing mode, override the cut out comparator value (Danfoss) or cut out pressure (Emerson), below the current saturated condensing temperature.

  • By adjusting the given condenser parameters is it possible to force the condenser into split mode?

  • Does pump out valve energize/open?

  • Piping Deviation

  • Does 50% split valve energize/open?

  • Piping Deviation

  • Do fans on seasonal side shut off?

  • Piping Deviation

  • Is the holdback valve solenoid de-energized during 50% split condensing mode?

  • Piping Deviation

  • When rack is in split condenser mode and all compressors are turned off, does the pump out valve de-energize, and do both sub cooler supply solenoid valves de-energize/close?

  • Piping Deviation

  • Is the holdback valve solenoid energized during full condensing mode?

  • Piping Deviation

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.