Title Page
-
Conducted on
-
Prepared by
-
Bedford House
16 - 22 Bedford Street
Belfast
BT2 7FD
Tel: 02890 324701
Ref: Weekly Fire Alarm System.
* Every Thursday at 09.30
* The system is put on "TEST" Mode by phoning the Motioning Station automated Step by Step Service prior to activation.
* An announcement is made over the PA system before and after testing.
Testing of Fire Roller Shutter (ground floor car park) - as from Thursday 15-04-2021
* Every Thursday after Fire Alarm bell test
* Includes checking the operation of shutter and condition of key switch
Fire Panel, Sounders, Strobes
-
Fire Panel - Bedford House Reception
-
Reception Strobe
-
Did the Reception Sounders initiate on activation?
-
Did the activation register on the Fire Panel?
-
Did the correct address register on the Fire Panel?
-
Did the Reception Strobe activate?
-
Did the Security Base Strobe activate?
- YES
- NO
- Not part of Weekly rotational schedule
Automated Doors, Mag locks and Access Control
-
Tiger Trap Doors: Reception
-
Double Doors: Reception to Ground Lift Lobby
-
Double Doors: Ground Floor Lift Lobby to Carpark
-
Access Control Door (Mag Lock) on Mezz
-
Gareth's Office: Access Control - Mag Lock
-
Gym Door: 9th Floor
-
Did the Tiger Trap Doors open on activation of Fire Alarm System?
-
Did the Double Doors - Reception to Ground floor lift lobby, close over on activation of Fire Alarm System?
-
Did the Double Doors: Ground Floor Lift Lobby to Car park, close over on activation of Fire Alarm System?
-
Did the Mag Lock on Access Control Door (Mezz) release on activation of Fire Alarm System?
- YES
- NO
- Not part of Weekly rotational schedule
-
Did the Mag Lock on Gareth's Office Door release on activation of Fire Alarm System?
- YES
- NO
- Not part of Weekly rotational schedule
-
Did the Mag lock on the Gym Door release on activation of Fire Alarm System?
- YES
- NO
- Not part of Weekly rotational schedule
Bedford House Elevators
-
OTIS: Elevators return to Ground / Mezz, depending on location of activation
-
Did all 3 Elevators return to correct floor?
Tenants Doors and Retail Units (Rotational)
-
Tenants floors will be on a rotational basis.
* Call point triggered within Tenants domain
* Door release to be checked during activation
* Retail Units - Repeater Panels -
Name of Tenant and floor; Front / Rear (if applicable)
-
Did the nominated Floor / Tenant Sounders initiate on activation?
- YES
- NO
- Not part of Weekly rotational schedule
-
Did the Tenants doors release on activation of the Fire Alarm System?
- YES
- NO
- Not part of Weekly rotational schedule
-
Could the PA System be heard on the nominated / tenant floor?
- YES
- NO
- Not part of Weekly rotational schedule
-
Retail Units: Did Repeater Panel display activation?
- YES
- NO
- Not part of Weekly rotational schedule
Checklist
-
Location / Address of device activated.
-
Call point in good order
-
Fire Panel Reset
-
Elevators: Returned to normal service
-
Reception PA System operational
-
Fire System on "LIVE" Status
-
Retail Units: Repeater Panels reset
-
Monitoring Station: Telephone Step by Step Automated "TEST" mode operational
-
Monitoring Station: Signal Received
-
Was there any other issue that needs to be reported?
Fire Roller Shutter (car park) - weekly test
-
Is the roller shutter operating and in good order?
-
Is the key switch in good order?
-
Is there any other issues that need to be reported?
-
Report generated on:
-
Name / Signature