Information

  • Site conducted

  • Site Location.

  • Completed On.

  • Inspector.

Back Of Site

Power Generation.

  • Power Generation Method.

  • Kwh from power meter in Switch Gear.

  • Photo's of total Kwh and Max Kwh from city Electric Meter (Next to Main Transformer)

Power Plant.

  • All Plastic Crosses are installed in required locations

  • Plower lock connected to Generators are Supported and there is no weight on the connectors

  • Earth Bonding between Generators is secure and connected correctly.

  • Communications Cables are supported and show no signs of damage.

  • Load Share Cables are supported and show no signs of damage.

  • Any Visible Signs of damage to cables passing through Truck Bed.

  • If Installed, Grounding on Shore Power Enclosure is Connected and Tight.

Switch Gear.

  • Total Kwh from electric meter at Main Site transformer.

  • Have Any Generator Input Circuit Breakers Tripped.

  • Have any outgoing, Circuit Breakers Tripped.

  • Have any DC Circuit breakers or fuses Tripped in the Control Panels.

  • DC Battery Charger is online and Operational.

  • Have any Circuit Breakers Tripped in the 120/240 Switch Board.

  • Shunt Trip UPS is Online and Operational.

  • High Resistance Grounding System is Clear of Alarms.

  • External indication Beacon Is operational. (Green light on)

  • All Lights are operational (Interior and Exterior)

  • Power lock connected to switch Gear are Supported and there is no weight on the connectors

  • Any Visible Signs of damage to cables on the ground.

  • Main Ground bonding Connections On switch Gear are Tight and Main ground link is connected and locked.

  • Grounding connections on main Grounding Triangle are tight and secure.

  • Bonding between generators, Fuel Tank and switch Gear are all connected and tight.

Show and Service Transformers.

  • ADA Cable ramp is in good condition and cables are installed correctly

  • Any Visible Signs of damage to cables.

  • Any Visible signs of Damage to the transformers

  • Power Lock Connectors are in good condition and locking pins are correct position on transformer (Primary and Secondary Side)

  • Have any Circuit breakers tripped (Primary Side)

  • Have Any Circuit Breakers Tripped (secondary Side and Artistic Tour Pack)

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display.

  • All Circuit Breaker Covers are closed and latched. (Transformers and Tour Pack)

  • Pin and Sleeve Lock rings are locked and sealed. (Transformer and Tour Pack)

  • All Grounding connections are connected and secure.

Staff Sanitary (22)

  • Plastic Cross are installed at all power lock connections along Cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position along cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position on Truck Input

  • Slings Installed to remove weight from power lock connectors

  • Any Visible Signs of damage to cables.

  • Pin and Sleeve Lock rings are locked and sealed.

  • All Grounding Lugs are connected and secure.

  • Heater Thermostats are set correctly and covers locked.

  • Restroom Exhaust fans operational.

  • Exhaust fan in Service room is operational.

  • Have any Circuit Breakers Tripped on the Electrical Panels.( including the outside laundry)

  • All Lights are operational.( inside and outside)

Kitchen.

  • Plastic Cross are installed at all power lock connections along Cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position along cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position on transformer and tour pack and Kitchen Switch Board.

  • Any Visible Signs of damage to cables.

  • Have Any Breakers Tripped on the Transformer Primary side.

  • Have any Breakers tripped on the transformer Secondary side.

  • Have any breakers tripped on the 60A or 30A distribution.

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display or a green light on the outlet.

  • All Circuit Breaker Covers are closed and latched.

  • Pin and Sleeve Lock rings are locked and sealed.

  • All Grounding connections are connected and secure.

  • Have any Circuit Breakers Tripped on the Internal Electrical Panels. (Reefer Truck , Kitchen Truck, Breakfast Table and Desert fridge/under counter fridge freezer)

  • All emergency Lights and signs are operational and have been tested with loss of power or test magnet.

Offices.

  • Plastic Cross are installed at all power lock connections along Cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position on transformer.

  • Power Lock Connectors are in good condition and locking pins are correct position along cable run.

  • Power lock between Transformer and Tour Pack are in good condition and all locking pins are in the correct position.

  • Any Visible Signs of damage to cables.

  • Have Any Breakers Tripped on the Transformer primary side.

  • Have any breakers tripped on the Transformer secondary side.

  • Have any breakers tripped on the Tour Pack

  • All GFCI, RCD and Bender Modules are clear of faults and showing a green light on the outlet or zero on the display.

  • All Circuit Breaker Covers are closed and latched.

  • Have any Circuit Breakers Tripped on the Internal Electrical Panels.

Site Shop.

  • Plastic Cross are installed at all power lock connections and pin and sleeve along Cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position along cable run. (if 480v Tour Pack is Used)

  • Any Visible Signs of damage to cables.

  • Have Any Breakers Tripped on the Tour Pack (if 480v Tour pack is used)

  • Have any breakers tripped on the transformer primary side.

  • Have any breakers tripped on the Transformer secondary side.

  • All RCD and Bender Modules are clear of faults and showing Zero on the Display or a green light on the outlet

  • Pin and Sleeve Connectors are in good condition and locking rings are locked and sealed on transformer.

  • Pin and Sleeve Lock rings are locked and sealed.

  • Have any Circuit Breakers Tripped on the Internal Electrical Panels. (75 and 80)

  • All Circuit Breaker Covers are closed and latched on External Distribution.

  • All Grounding Connections are connected and secure.

Water Station

  • Is a transformer being used.

  • Pin and sleeve connections on transformer are tight and sealed

  • Have any breakers on the transformer tripped

  • Have any GFCI on the transformer tripped

  • All Covers are locked and secure

  • Transformer is in good condition

  • Cables for the transformer are in good condition

  • Earthing Connections are tight and secure

  • Pin and sleeve for 60A distro is in good condition and connected correctly

  • Have any GFCI or Breakers Tripped on the 60A Distro.

  • All pin and sleeve are connected correctly and locking rings are tight and secure.

  • All pin and sleeve connected to the pumps are connected correctly and locking ring is tight and secure.

  • Light and electrical equipment is operational in the water station.

Technical. (54)

  • Plastic Cross are installed at all pin and sleeve connections along Cable run.

  • Pin and Sleeve Connectors are in good condition and locking rings are locked and sealed.

  • Any Visible Signs of damage to cables.

  • Have any Circuit Breakers Tripped on the Internal / External Electrical Panel or distribution.

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display.

  • All Circuit Breaker Covers are closed and latched on External Distribution.

  • All Grounding Lugs are connected and secure.

Temps Tent / Cardboard Compactor

  • Temps Tent Distro In good condition.

  • Have any Circuit Breakers tripped on the 30A distort Temps Tent.

  • 30A pin and sleeve is connected correctly and locking ring is locked and secure.

  • All GFCI Modules are clear of faults and showing a green light on the outlet

  • Circuit Breaker cover is locked and secure

  • Temps tent work light is on and working.

  • Any Visible Signs of damage to cables in the temps tent

  • Compactor Pin and Sleeve is connected, Lock ring is locked and secure.

  • Any Visible Signs of damage to cables in the compactor area.

  • Compactor tent work light is on and working.

Stage Left.

  • ADA Cable ramp at Door 8 is in good condition and cables are installed correctly

  • All pin and sleeve connectors are on plastic cross and lock rings are tight and sealed.

  • All weatherproof Cables (Yellow Plugs) are sealed correctly.

  • Bathroom non weather proof plugs are covered and not exposed to the weather.

  • Have Any Circuit Breakers Tripped on Bathroom 60A Distro.

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display or a green light on the module.

  • All Circuit Breaker Covers are closed and latched.

  • All wall light and tunnel light weatherproof Cables (Yellow Plugs) are sealed correctly.

  • Any Visible Signs of damage to weather proof cables.

  • Power Lock cables and Connectors are in good condition and locking pins are correct position along the Big Top.

  • Plastic Cross are installed under all power Lock Connections around the big top.

  • Any Visible signs of Damage to power lock cables or connectors.

Front Of House

Stage Left.

  • All Plastic Crosses are installed in required locations

  • ADA Cable ramp is in good condition and cables are installed correctly.( Wing Door)

  • Any Visible Signs of damage to cables.

  • Power Lock Connectors are in good condition and locking pins are correct position along cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position on transformer.

  • Have Any Circuit Breakers Tripped on the Transformer.

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display or a green light on the outlet.

  • All Circuit Breaker Covers are closed and latched.

  • Pin and Sleeve Lock rings are locked and sealed.

  • All Grounding connections are connected and secure.

  • ADA Cable ramp is in good condition and cables are installed correctly.( Main Entry)

  • 60A and 30A distribution Behind the Swing Set are in good condition.

  • Have any Circuit breakers tripped on the distribution behind the swing sets?

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display or a green light on the outlet for the distribution behind the swing sets.

  • Any visible damage to cable or plugs/ connectors behind the swing sets.

Mast 6

  • Cable mat is in good condition and cables are installed correctly

  • Any Visible Signs of damage to cables.

  • All Grounding connections are connected and secure.

Mast 6

  • Cable mat is in good condition and cables are installed correctly.

  • Any Visible Signs of damage to cables.

  • All Grounding connections are connected and secure.

SMB Transformer (No Mans Land) ,Video Wall and Wings SR and SL

  • 30 Amp Distro in each wing is in good condition.

  • Have any breakers tripped on the wing distros.

  • All GFCI Modules on wing distros are clear of faults.(green light on outlet is on)

  • Plastic Cross are installed at all power lock connections along Cable run in no mans land.

  • Power Lock Connectors are in good condition and locking pins are correct position along cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position on transformer.

  • All Grounding connections are connected and secure.

  • Any Visible Signs of damage to cables.

  • Have Any Breakers Tripped on the Transformer.

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display or a green light on the outlet.

  • All Circuit Breaker Covers are closed and latched on the transformer.

  • Pin and Sleeve Lock rings are locked and sealed on the transformer.

  • Have Any Breakers Tripped on the external Distribution ( 60A distro under SMB)

  • All GFCI and Modules are clear of faults on the external Distribution.

  • 30A distro on top of battery pack is in good condition.

  • Have any Breakers tripped on 30A distro on top of Battery Pack.

  • All GFCI and Modules are clear of faults on the 30A distro on the battery pack.

  • All connections on Battery Pack are connected correctly (emergency lights, mast lights, Work Lights)

  • Socapex breakouts are connected correctly to battery pack and general power is connected to the 30A disto on top of battery pack

  • 60A pin and sleeve to the battery Pack is connected and secure

  • Emergency Exit signs are operational and LED lights come on when test button is pressed.

  • Exterior mast light timer is showing correct time and set for the correct hours of operation.

  • All Work Lights Are operational

  • 60A pin and sleeve is connected to the AV Rack correctly.

  • Any Visible Signs of damage to cables in this area.

Merchandise.

  • Cable ramp is in good condition and cables are installed correctly

  • Any Visible Signs of damage to cables.

  • 30A and 60A distros are in good condition.

  • Have Any Circuit Breakers Tripped.

  • All GFCI Modules are clear of faults.(green light on outlet is on)

  • All Circuit Breaker Covers are closed and latched.

  • Pin and Sleeve Lock rings are locked and sealed.

  • Exterior light timer is showing correct time and set for the correct hours of operation.

Front of Site (Public Area)

  • All Plastic Crosses are installed in required locations

  • All Wall Lights are installed correctly and are upright.

  • Any Visible Signs of damage to cables.

  • All weatherproof Cables (Yellow Plugs) are sealed correctly.

  • Any Visible Signs of damage to weather proof cables.

  • Arch Battery Condition.

  • Does the Mains power charger need to be plugged in to charge Arch Batteries.

  • Arch Solar Panels are charging battery's. Check indicator lights in control panel. (2 green leds on left side of controller)

  • Arch Timer is set to correct time and hours of operation are set correctly.

Box Office.

  • All Plastic Crosses are installed in required locations along the cable run.

  • Pin and Sleeve cables are connected correctly and in good condition and lock rings are tight and sealed.

  • Pin and Sleeve cables are connected to the box office correctly and lock rings are tight and sealed.

  • Any visible damage to pin and sleeve cables.

  • All external LED lights on box office are operational.

  • All window lights are operational.

  • All Inside window lights are operational.

  • Have any Circuit Breakers Tripped.(internal Switch Boards)

  • Have any 24Vdc Fuses blown.(all window lights)

  • General lighting in box office is operational.

Stage Right Swing Set Distribution.

  • ADA Cable ramp is in good condition and cables are installed correctly.( Main Entry)

  • 60A and 30A distribution Behind the Swing Set are in good condition.

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display or a green light on the outlet for the distribution behind the swing sets.

  • Have any Circuit breakers tripped on the distribution behind the swing sets?

  • Any visible damage to cable or plugs/ connectors behind the swing sets.

  • All Plastic Crosses are installed in required locations.

  • Power Lock Connectors are in good condition and locking pins are correct position along cable run.

  • Power Lock Connectors are in good condition and locking pins are correct position on transformer.

  • Have Any Circuit Breakers Tripped on the Transformer.

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display or a green light on the outlet.

  • All Circuit Breaker Covers are closed and latched.

  • Pin and Sleeve Lock rings are locked and sealed.

  • All Grounding connections are connected and secure.

  • ADA Cable ramp is in good condition and cables are installed correctly.( Wing Door)

  • Any Visible Signs of damage to cables.

Stage Right

  • ADA Cable ramp at Door 7 is in good condition and cables are installed correctly

  • All pin and sleeve connectors are on plastic cross and lock rings are tight and sealed.

  • All weatherproof Cables (Yellow Plugs) are sealed correctly.

  • Bathroom non weather proof plugs are covered and not exposed to the weather.

  • Have Any Circuit Breakers Tripped on Bathroom 60A Distro.

  • All GFCI and Bender Modules are clear of faults and showing Zero on the Display or a green light on the module.

  • All Circuit Breaker Covers are closed and latched.

  • All wall light and tunnel light weatherproof Cables (Yellow Plugs) are sealed correctly.

  • Any Visible Signs of damage to weather proof cables.

  • Power Lock cables and Connectors are in good condition and locking pins are correct position along the Big Top.

  • Plastic Cross are installed under all power Lock Connections around the big top.

  • Any Visible signs of Damage to power lock cables or connectors.

Artistic

  • All pin and sleeve cables locked and sealed correctly.(on tour pack and on distro's)

  • All pin and sleeve connections on plastic cross where required

  • Have any breakers tripped on the external 60A distros.

  • GFCI and Bender modules are clear of faults and showing zero on the display or a green light on the module

  • All cables pluged in to the 60A distros are weather proof cables or pin and sleeve.

  • Have any GFCI or breakers tripped on the 30A distros in Artistic (Red Carpet, 2 In male Lodge Area, Wardrobe, Shoe Tent, Drying Area and P-Med)

  • All fluorescent tube's working ( wardrobe area and shoe tent)

  • Chicken Warmer (Artist Heater) Operational, timer set to correct time and Operation time is correct for on and off.

  • 60A pin and sleeve is connected correctly to battery pack.

  • All cables are connected to the battery pack correctly.

  • Exterior mast lights timer is showing correct time and set for the correct hours of operation.

  • Emergency Exit signs are operational and LED lights come on when test button is pressed.

Big Top- Back Stage

  • Pin and sleeve connected to 30A distro correctly.

  • Have any GFCI or breakers tripped.

  • Is Distro in good condition.

  • Any Signs of cable damage to any cables in this area.

  • Back Stage Work lights are operational.

Big Top

  • Ada Cable ramp Under bleacher at door 7 is in good condition.<br>

  • Power Lock are connected to the fridge correctly and locking pins are in correct position.

  • Socapex are connected correctly to the fridge all locking rings are tight.

  • Pin and sleeve are connected correctly to the fridge and locking rings are tight

  • Harting Connector is Connected correctly and locking handle is secure.(Cupola Fan Control Case on the rear)

  • Cupola Fan Control System Is powered and operational No RCD, Breakers or TOL have tripped.

  • Both Twist Lock for the emergency Light Trigger are connected correctly.

  • All 6 red indicators are lit on the Emergency Light Trigger.

  • Link Cable From The Emergency Light Trigger to The fridge is installed and connected

  • Green operation light is Lit indicating Emergency Light Trigger is connected.(on Fridge)

  • Emergency Light ByPass Plug is not connected and hanging in Fridge.

  • External Mast Light and wall Light timer are set to the correct time and hours of operation is correct.

  • Door 7 Distro is connected correctly All connections are tight and plugs are not loose.

  • Door 7 tunnel lights GFCI has not tripped and is operational

  • Mast 1 Battery Pack Operational Power light is on and Indicator for charge is on.

  • Door 5 Distro is connected correctly All connections are tight and plugs are not loose.

  • Door 5 tunnel lights GFCI has not tripped and is operational

  • Has the Exterior wall Lights GFCI at Door 5 Tripped.

  • Door 3 Distro is connected correctly All connections are tight and plugs are not loose.

  • Door 3 tunnel lights GFCI has not tripped and is operational

  • Mast 2 Battery Pack Operational Power light is on and Indicator for charge is on.

  • Door 1 Distro is connected correctly All connections are tight and plugs are not loose.

  • Door 1 tunnel lights GFCI has not tripped and is operational

  • Door 2 Distro is connected correctly All connections are tight and plugs are not loose.

  • Door 2 tunnel lights GFCI has not tripped and is operational

  • Door 4 Distro is connected correctly All connections are tight and plugs are not loose.

  • Door 4 tunnel lights GFCI has not tripped and is operational

  • Mast 4 Battery Pack Operational Power light is on and Indicator for charge is on.

  • Door 6 Distro is connected correctly All connections are tight and plugs are not loose.

  • Door 6 tunnel lights GFCI has not tripped and is operational

  • Has the Exterior wall Lights GFCI at Door 6 Tripped.

  • Door 8 Distro is connected correctly All connections are tight and plugs are not loose.

  • Door 8 tunnel lights GFCI has not tripped and is operational

  • Mast 3 Battery Pack Operational Power light is on and Indicator for charge is on.

  • Door 8 Handicap Tunnel Lights and Exit Sign Operational

  • Door 8 Tunnel Lights and Exit Sign Operational

  • Door 6 Tunnel Lights and Exit Sign Operational

  • Door 4 Tunnel Lights and Exit Sign Operational

  • Door 2 Tunnel Lights and Exit Sign Operational

  • Door 1 Tunnel Lights and Exit Sign Operational

  • Door 3 Tunnel Lights and Exit Sign Operational

  • Door 5 Tunnel Lights and Exit Sign Operational

  • Door 7 Tunnel Lights and Exit Sign Operational

  • Door 7 Handicap Tunnel Lights and Exit Sign Operational

  • All Section Signs Operational

  • All Sponsor Banners Operational

  • When Emergency Lights Triggered Cupola Emergency Light LED Strips Operational

  • When Emergency Lights Triggered All exit signs stay on and all LED flood lights come on and are operational

  • All Mast work Lights Are operational

  • All Cupola Lights Are operational

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.