Information

  • Site conducted

  • Site Location:

  • Conducted on:

  • Inspector.

Front End

Jace Program. (HVAC Control software)

  • Software is open and operational.

Alarms.

  • Active Alarms.

Outside Temperature.

  • Current Outside Temperature.( use weather underground online)

Sensor Box Current Temperatures / Humidity/ C02

Sensor Box 1.

  • Device Status.

  • Reason Device is Offline.

Sensor Box 2.

  • Device Status.

  • Reason Device is Offline.

Sensor Box 3.

  • Device Status.

  • Reason Device is Offline.

Sensor Box 4.

  • Device Status.

  • Reason Device is Offline.

Sensor Box 5.

  • Device Status.

  • Reason Device is Offline.

Sensor Box 6.

  • Device Status.

  • Reason Device is Offline

Sensor Box 7.

  • Device Status.

  • Reason Device is Offline.

Sensor Box 8.

  • Device Status.

  • Reason Device is Offline.

Group Setponts

Group 1.

  • Group Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Group 2.

  • Group Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Group 3.

  • Group Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Group 4.

  • Group Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Group 5.

  • Group Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Group 6.

  • Group Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Group 7.

  • Group Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Group 8.

  • Group Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Kitchen

  • Unit Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

VIP

  • Unit Status.

  • Set point. (*F)

  • Fan Speed. (%)

  • Damper Position. (%)

  • Mode of Operation.

Wireless Network.

  • Sensor Boxes online.

  • Installed HVAC Units Online.

  • Connected to External Network. (can connect to the internet)

Position 17, Kitchen

undefined

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point.(*F)

  • Supply Fan Speed. (%)

  • Max Number of Heating Stages. (1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 11, Artistic SR

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 12, Artistic SL

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 1

Unit Number.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (F)

  • Max Number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 2

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 3

Unit.

  • Unit Number.

HMI

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 4

Unit.

  • Unit Number.

HMI.

  • Active Alarms

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 5

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 10, Cupola

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-4)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 6

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 7

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 8

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 9

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

HMI

  • Active Alarms.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-6)

Unit Inspection.

  • HMI Canvas cover and magnets are in good condition.

  • Condition of Return Air Filters / Protective Grill.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 13 SR VIP

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 15

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 14 SL VIP

Unit.

  • Unit Number.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-4)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 16

Unit.

  • Unit Numbers.

HMI.

  • Active Alarms.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-8)

Unit Inspection.

  • HMI Canvas cover and magnets are in good condition.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Position 18 Site Shop

Unit Number

  • Unit Number.

HMI.

  • Active Alarm.

  • Mode.

  • Operation.

  • Set Point. (*F)

  • Supply Fan Speed. (%)

  • Max number of heating Stages.(1-6)

Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • Condenser Coil Inlet is clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block support load.

Rental Unit Inspection.

  • Supply Air Ducting Connected and secure.

  • Return Air Ducting Connected and secure.

  • Side wall duct entry's are Correctly installed and straps are tight.

  • Damper is Clear of any objects.

  • All Doors are locked and secured correctly.

  • Unit is making full contact with the ground or all block's support load

Soft Ducting.

Front Of House. (Concession Tent)

Position 16.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Position 15.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

VIP

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Big Top.

Position 8.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Position 6.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Position 5.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Position 10.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Position 4.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Position 3.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Position 1.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

  • Nozzles are facing correct direction.

Technical. (54)

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

Artistic.

Position 11.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

Kitchen.

  • Soft Ducting is inflated and not flapping.

  • Straps connecting soft duct to black duct are tight and secure.

External Connected Devices

Remote Displays

SMB Display.

  • Device Status.

  • Display is showing correct information.

  • Reason Device is Offline.

Shop Display

  • Device Status.

  • Display is showing correct infomation.

  • Reason Device is Offline.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.