Information
-
Site conducted
-
Site Location:
- Tyson
- New York
- Miami
- Dallas
- Houston
- Winnipeg
- Portland
- Vancouver
-
Conducted on:
-
Inspector.
- Sam Nicholas
- Mark Gribble
- David Constantineau
- Chas Oldjohn
- Robert Lundy
- Katy Eakin
Front End
Jace Program. (HVAC Control software)
-
Software is open and operational.
Alarms.
-
Active Alarms.
Outside Temperature.
-
Current Outside Temperature.( use weather underground online)
Sensor Box Current Temperatures / Humidity/ C02
Sensor Box 1.
-
Device Status.
-
Reason Device is Offline.
Sensor Box 2.
-
Device Status.
-
Reason Device is Offline.
Sensor Box 3.
-
Device Status.
-
Reason Device is Offline.
Sensor Box 4.
-
Device Status.
-
Reason Device is Offline.
Sensor Box 5.
-
Device Status.
-
Reason Device is Offline.
Sensor Box 6.
-
Device Status.
-
Reason Device is Offline
Sensor Box 7.
-
Device Status.
-
Reason Device is Offline.
Sensor Box 8.
-
Device Status.
-
Reason Device is Offline.
Group Setponts
Group 1.
-
Group Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Group 2.
-
Group Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Group 3.
-
Group Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Group 4.
-
Group Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Group 5.
-
Group Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Group 6.
-
Group Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Group 7.
-
Group Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Group 8.
-
Group Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Kitchen
-
Unit Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
VIP
-
Unit Status.
-
Set point. (*F)
-
Fan Speed. (%)
-
Damper Position. (%)
-
Mode of Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
Wireless Network.
-
Sensor Boxes online.
-
Installed HVAC Units Online.
-
Connected to External Network. (can connect to the internet)
Position 17, Kitchen
undefined
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point.(*F)
-
Supply Fan Speed. (%)
-
Max Number of Heating Stages. (1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 11, Artistic SR
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 12, Artistic SL
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 1
Unit Number.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (F)
-
Max Number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 2
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 3
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 4
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 5
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 10, Cupola
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-4)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 6
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 7
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 8
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 9
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
HMI
-
Active Alarms.
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-6)
Unit Inspection.
-
HMI Canvas cover and magnets are in good condition.
-
Condition of Return Air Filters / Protective Grill.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 13 SR VIP
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 15
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 14 SL VIP
Unit.
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-4)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 16
Unit.
-
Unit Numbers.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarms.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-8)
Unit Inspection.
-
HMI Canvas cover and magnets are in good condition.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Position 18 Site Shop
Unit Number
-
Unit Number.
- N/A
- Rental Unit
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
- 24
- 25
- 26
- 27
- 28
- HV-1
- HV-2
HMI.
-
Active Alarm.
-
Mode.
-
Operation.
- Ventilation
- Cool
- Heat
- Heat / Cool
- Dehumidify
- Standby
-
Set Point. (*F)
-
Supply Fan Speed. (%)
-
Max number of heating Stages.(1-6)
Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
Condenser Coil Inlet is clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block support load.
Rental Unit Inspection.
-
Supply Air Ducting Connected and secure.
-
Return Air Ducting Connected and secure.
-
Side wall duct entry's are Correctly installed and straps are tight.
-
Damper is Clear of any objects.
-
All Doors are locked and secured correctly.
-
Unit is making full contact with the ground or all block's support load
Soft Ducting.
Front Of House. (Concession Tent)
Position 16.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Position 15.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
VIP
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Big Top.
Position 8.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Position 6.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Position 5.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Position 10.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Position 4.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Position 3.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Position 1.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
-
Nozzles are facing correct direction.
Technical. (54)
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
Artistic.
Position 11.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
Kitchen.
-
Soft Ducting is inflated and not flapping.
-
Straps connecting soft duct to black duct are tight and secure.
External Connected Devices
Remote Displays
SMB Display.
-
Device Status.
-
Display is showing correct information.
-
Reason Device is Offline.
Shop Display
-
Device Status.
-
Display is showing correct infomation.
-
Reason Device is Offline.