Title Page

  • Site conducted
  • Conducted on

  • Prepared by

Lift Information

  • Lift Type and Description

  • Lift ID Number

  • Manufacturers Serial Number

  • Lift Location

  • Signed

  • Name

  • Position

Testing Methods

  • It should be established that adequate earthing of all metal work, such as
    the car, landing doorframes, machine, controller and guides is provided. Pay attention to the landing locks, all electrical components in the shaft and car top should have secure and clean earth connections. Check landing pushes for earthing!

  • The fuse protection of the safety circuit should be tested by either a purpose
    made device or by measuring the resistance of the circuit and calculating
    the short circuit current. The safety circuit should not be checked by
    grounding its furthest point. It is recommended that to be consistent with
    BS7671 Requirements for Electrical Installations: IET Wiring Regulations
    and IET Guidance Note 3, this supplementary test should be called for at 5
    yearly intervals unless it can be demonstrated that more frequent tests are
    required or that less frequent tests will be adequate to ensure safety .
    The earth continuity should not exceed 0.5Ω but check the OEM manual for
    any relevant information regarding earth testing methods and acceptable
    values. Lower values may be actually needed to ensure adequate protective
    device disconnection time and higher values might be acceptable.

  • Using calibrated multimeter, on OHMS check for resistance between all metal components, including distribution boards, isolators and controllers. Check terminations of trailing flexes within the controller and car top.

  • To blow the safety circuit fuse, using a shorting kit connect the top landing lock to the metal frame and ensure the fuse blows immediately.

A.1 Earth Continuity

  • State Method Of Test

  • Is the maximum continuity resistance to the earth 0.5Ω or less?

  • Has the fuses protection of the safety circuit been satisfactorily tested by either a purpose made device or by measuring the resistance of the circuit and calculating the short circuit current or test according to the OEM manual?

  • Please Explain

  • Does the result of the supplementary test(s) indicate further remedial work is necessary?

  • state your recommendation(s) for further action required

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.