Management Historical Information and Front End Alarm history
-
Check Systems Alarm History and note repeats/ concerns.
-
Note Any Issues Store Manager has had in recent past with Site Refrigeration Systems
Packs and Condensing Units.
-
Is the plant room/ Pack enclosure secure?
-
Is the plant room/ pack enclosure / CU surrounds clean and tidy? Safe access and egress?
-
Is there safe access and egress to plant room/ enclosure?
-
Does the plant room have good air flow/ maintaining a reasonable temperature?
PRVs
-
Are all PRVs Tagged?
-
Check stamped dates on PRVs, do they match Tag dates?
-
Are all PRVs within date?
-
Are the PRVs free of oil leaks or stains?
-
Are PRV vent lines in place, secure and clear?
Oil
-
Is the level in oil reservoir sufficient?
-
Do all Compressors have sufficient oil levels?
-
Are Compressors running at correct temperatures?
-
Are Compressor oil controls in working order?
-
Are Compressors free of oil leaks/ stains?
-
Are HP and LP flexible lines in good order and routed to prevent rubbing through?
-
Are HP LP Oil LP switches, gauges, and transducers mounted securely?
-
Is the Temprite/ Oil separator tagged/ noted as changed within last 24 months?
Electrical
-
Are electrical panel doors closed and properly secured?
-
Are pack display panels free of illuminated alarm lights?
-
Are panel/ pack isolators are working.
-
Do all Compressors isolator switches work?
Compressors
-
Do all Compressors stage correctly?
-
Do all Compressors run when called for?
Inverters
-
Are all inverters in operation/ working correctly?
-
Are heat sinks clean and fans working?
-
Are cables to and from inverters secure and insulated from rubbing against frame work?
Other
-
Are packs running at pressures that are within range for the type of refrigerant?
-
Is all pipework and lagging in good order and free of ice/ frost and oil stains?
-
Conduct a leak check. Are packs free of leaks?
-
Are all probes located correctly and secure?
-
Is the liquid level in receiver sufficient?
-
Are low level sensors in the correct position and working?
-
Is the liquid filter/drier tagged/ date of last change noted?
-
Is the liquid filter dryer bypass closed and liquid routed through filter basket?
Gas Coolers
-
Are all fans operational?
-
Are fins and passes clean and clear of debris?
-
If external condensers, is the area clear of trees/ leaves other sources of contamination?
-
Are Probes correctly positioned and secure?
-
Is pipework and lagging free of damage and or oil stains?
-
Are all shut off valve covers present?
Distribution Boards
-
Are distribution boards clear of obstruction and easily accessible?
-
Are door latches sound and doors closed fully?
-
Are the DBs labelled?
SHOP FLOOR
-
Are cases and Isles free of water leaks?
-
Are all cabinets free of damage? ( Broken shelving, bent facias)
-
Are all Dividers present, in good order and correct position?
-
Are all Honey combs present, clean and clear of obstructions?
-
Are all case lights working?
-
Are all bumpers and bump rails present and in good condition?
-
Look on top of Cabinets. Are they clean?
-
Is pipework and lagging free of oil stains?
-
Is pipework and lagging free of damage?
-
If Schrader access valves present, do they have Hex / Real Zero Caps fitted?
-
Check operation and condition of night blinds/ Acrylic Doors. Are they in good order?
-
Are all kick plates present and secure?
COLD STORES
-
Check operation of doors. Do they close and seal correctly?
-
-
-
-
-
-
-
Check all Door and frame heaters. Are they free from frost/ ice build up?
-
Are flap doors present, in working order and free of damage?
-
If present, inspect and press CO2 leak alarm test buttons. Are they free of damage and working?
-
Do the internal and external strobe lights illuminate and are they free of damage?
-
Are all cold store lights working
-
If fitted, inspect and test the Entrapment Alarm. Are they secure and working?
-
Are cold stores free of water leaks/ Damage to drain lines?
-
Are the floor heaters working?
-
Are evaporators clear of stock/ boxes underneath and on all sides?
-
Are evaporators, fins and passes clean?
-
Are cold Stores free of frost/ ice build up?
-
Are all evaporator side covers and drip trays present and secure?
-
Are all evaporator fans working, rotating in correct direction and clean?
-
Are drain pans clean and free of ice?
-
Are drain heater tapes secure and working?
-
Are all Probes correctly positioned and secure?
-
Look on top of Cold Stores ( Without climbing on top unless crawl boards and acros are in place). Are they clean and free of debris?
-
Are tops of cold Stores free of oil and oil stains?
-
Is all pipework and lagging free of damage and frosting/ ice ?
SUMMARY AND OBERVATIONS
-