Information
-
Store Number and Name
-
Date
-
Prepared by:
-
Refrigeration Engineer
-
M&E Engineer
Refrigeration
-
Spot check any completed WO that has been carried out by a sub contractor and ensure this has been done to a safe and satisfactory standard
-
Check 6 random Refrigeration/M&E asset tags and verify correct on Verisae.
-
Is plant area clean and tidy
-
Are there any signs of oil on equipment or floor area.
-
Are refrigerant liquid levels marked.
-
Are there any visible alarm lights on electrical panels
-
Are all electrical panels securely closed
-
Have real zero caps been fitted to all plant access points
-
Are the PRV,s in date and tagged. Must not be more than 5 years old
-
Are all condensers clean and fans fully operational
-
Are there any empty refrigerant cylinders onsite. If so please note serial numbers and email fgas@arcus-engineering.com
-
Are all coldstore evaporators free from ice build up
-
Are cold store doors fully operational
-
Check all frozen food doors close correctly
-
Are all trim heaters working
-
Are all product dividers fitted (where required and without damage)?
-
Are the sales floor cabinets water leak free
-
Remove 1 x random honeycombe and photograph.
-
Night blinds fitted and working correctly?
-
Are all kick plates fitted
-
Are all cabinets correctly loaded, please raise with store manager if not
M&E
-
Are all maintenance stickers fitted to Plant/equipment up to date and visible
-
Are all sockets, switches and other equipment free from damage
-
Are there any operated trips or circuit breakers etc
-
Is all cable management or pipe work that is visibly damage
-
Is all redundant Plant/Equipment clearly identified
-
Is there a water hygiene book on site and is it up to date
-
Are all hot water cylinders storing at 60c
-
Is the HWS system functioning correctly ( flow & return are hot )
-
Are all belts free from damage and filters fitted and clean
-
Are the store air curtains working correctly
-
Is the store pressurised with all HVAC equipment functioning correctly
-
Are all VSD's functioning and at SSL set points ( 40Hz or 50Hz unless designed for a different setting )
-
Is the store average temperature at set point (19c )
-
Are all A/C filters fitted and clean
-
Are all A/C units working without any faults showing
-
Are all disabled call alarms working correctly
-
Is all plant/ equipment asset tagged
-
Do all the hand dryers operate correctly
-
Is the site free from any blocked toilets, urinals or sinks
-
Is the site free from dripping taps or overfilling toilet syphons
-
Is the site free of any litter/ waste materials etc in plant room/s and roof
Sign Off
-
Inspected and signed on behalf of Arcus Solutions
-
Store Manager