Information

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Weather Condition

  • Enter Expected High and Expected Low Temperature

  • Nasatka Personnel

  • AHJ, GC or End-user Personnel

Commissioning - Performance Verification Testing

  • Barrier Information

  • AVB Barrier
  • Barrier Serial Number

  • Nasatka Barrier Product Line

  • Barrier Model

  • Enter Barrier Size

  • Ensure Barrier plate is no more than 5/8 inches from road surface (barrier plate should flat or almost flat when down)

  • Describe Failure and Corrective Action

  • Heat Trace Installed

  • Verify Breaker is GFPE

  • Verify Breaker is sized correctly (per AVB for Heat trace)

  • Thermostat Installed

  • Thermostat Sensor Probe attached to Cabinet

  • Splice and Power Connection Installed

  • Heat Trace END cap Installed

  • Was Heat Trace tested prior to Start-up

  • Tested By

  • Paint Scheme

  • Enter Sheme and Paint Color

  • Enter Custom Color Paint Finish

  • Take Picture of Paint Finish

  • Describe Non-Compliant and Corrective Action

  • Select Barrier Power Unit

  • Batteries Installed for MOOG

  • UPS battery Installed

  • Enter Main power feed (120/208/480/other)

  • Main Breaker Size to AVB

  • Grounding installed for Barrier Frame

  • Grounding installed for Cabinet

  • Verify COAST button (barrier goes down when pressed)

  • Barrier STOPS moving when Coast button is released.

  • Verify JOG toggle switch - Toggle UP - Barrier moves UP

  • Verify JOG toggle switch - Toggle DOWN - Barrier moves DOWN

  • Verify Drains (8 connected)

  • Actuator Power and Encoder cables secured as required

  • Surge Protection Device (SPD) Installed

  • HVAC installed

  • Enter Main power feed (120/208/480/other)

  • Enter Main Breaker Size to AVB

  • Ensure Hydraulic Fluid is installed in unit.

  • Describe Failure and Corrective Action

  • Ensure all hoses are installed and connected.

  • Describe Failure and Corrective Action

  • Ensure No leaks

  • Describe Failure and Corrective Action

  • Verify Operating Pressure Settings (min. pressure 1300 PSI - max pressure 2200 PSI)

  • Record pressure setting

  • Describe Failure and Corrective Action

1. Sequence of Operations - Normal Mode

  • SECURED/CLOSED/UP position initiated via the push button on Master Control Panel (MCP)?

  • Describe Failure and Corrective Action

  • UNSECURED/OPEN/DOWN Position initiated via push button on Master Control Panel (MCP)?

  • Describe Failure and Corrective Action

  • Barrier goes to the SECURED/CLOSED/UP position in standard operating time?

  • Describe Failure and Corrective Action

  • Barrier goes to the UNSECURED/OPEN/DOWN position in standard operating time?<br>

  • Describe Failure and Corrective Action

  • SECURED/CLOSED/UP position initiated via the push button on Remote panel(s)?

  • Describe Failure and Corrective Action

  • UNSECURED/OPEN/DOWN position initiated via the push button on Remote panel(s)?

  • Describe Failure and Corrective Action

  • Verified Indicating lights for status of barrier positions on Master Control Panel (MCP)?

  • MCP Barrier Position Light is ON "RED" when Barrier is UP/CLOSE/SECURED

  • Describe Failure and Corrective Action

  • MCP Barrier Position Light is ON "GREEN" when Barrier is DOWN/OPEN/UNSECURED

  • Describe Failure and Corrective Action

  • Describe Failure and Corrective Action

  • Verified Indicating lights for status of barrier position on Remote Control Panel (RCP)

  • RCP Barrier Position Light is ON "RED" when Barrier is UP/CLOSE/SECURED

  • Describe Failure and Corrective Action

  • RCP Barrier Position Light is ON "GREEN" when Barrier is DOWN/OPEN/UNSECURED

  • Describe Failure and Corrective Action

  • Verified all ILLUMINATED SWITCHES or LIGHTS are functional on Master control panel when LAMP TESTED

  • Describe Failure and Corrective Action

  • Verified AUDIBLE HORN and/or HORN STROBE ALARM to indicate barrier MOVING from the SECURED/UP position to UNSECURED/DOWN position and from the UNSECURED/DOWN position to the SECURED/UP position.

  • Describe Failure and Corrective Action

  • Verified all TRAFFIC SIGNAL LIGHTS

  • VERIFY LIGHT CHANGES FROM FLASHING YELLOW TO RED (BARRIER STARTS IN DOWN/UNSECURED/OPEN POSITION MOVING TOWARDS UP/SECURE/CLOSED POSITION)

  • Describe Failure and Corrective Action

  • VERIFY LIGHT STAYS SOLID RED AND CHANGES TO FLASHING YELLOW ONCE BARRIER IS COMPLETELY DOWN (BARRIER STARTS IN UP/SECURED/CLOSED POSITION MOVING TOWARDS DOWN/UN-SECURE/OPEN POSITION)

  • Verified all TRAFFIC SIGNAL LIGHTS - FLASHING YELLOW - BARRIER UNSECURED/OPEN/DOWN Position are functional.

  • Verified all TRAFFIC SIGNAL LIGHTS - RED ON - BARRIER SECURED/CLOSED/UP Position are functional.

  • Verified all TRAFFIC ARMS - ARM in the DOWN POSITION when Barrier is in the SECURED/CLOSED/UP Position are functional.

  • Verified all TRAFFIC ARMS - ARM in the UP POSITION when Barrier is in the UNSECURED/OPEN/DOWN Position are functional.

  • VERIFY LIGHT CHANGES FROM FLASHING YELLOW TO RED (BARRIER STARTS IN DOWN/UNSECURED/OPEN POSITION MOVING TOWARDS UP/SECURE/CLOSED POSITION)

  • Describe Failure and Corrective Action

  • VERIFY LIGHT CHANGES FROM SOLID RED TO FLASHING YELLOW (BARRIER STARTS IN UP/SECURED/CLOSED POSITION MOVING TOWARDS DOWN/UN-SECURE/OPEN POSITION)

  • Verified all TRAFFIC SIGNAL LIGHTS - FLASHING YELLOW - BARRIER UNSECURED/OPEN/DOWN Position are functional.

  • Verified all TRAFFIC SIGNAL LIGHTS - RED ON - BARRIER SECURED/CLOSED/UP Position are functional.

  • Verified all TRAFFIC ARMS - ARM in the DOWN POSITION when Barrier is in the SECURED/CLOSED/UP Position are functional.

  • Verified all TRAFFIC ARMS - ARM in the UP POSITION when Barrier is in the UNSECURED/OPEN/DOWN Position are functional.

  • Verify On-Barrier LED Lights are functional.

  • Comments

  • Enter any corrective actions that WILL NEED to be undertaken.

  • Perform a Visual Inspection of Barrier for any damages.

2. SoO - EMERGENCY FAST OPERATION (EFO) OR EMERGENCY SECURE OPERATION (ESO)

  • ALL Barrier(s) are in UNSECURED/OPEN/DOWN Position. Initiate EFO/E-UP Push Button on Master Panel and Barrier(s) move to SECURE/CLOSE/UP position. (Safety loops and Photo Eye are bypassed by EFO/ESO command)

  • ALL Barriers are in UNSECURED/OPEN/DOWN Position. Initiate EFO/ESO Push Button on Remote Panel and Barriers move to SECURE/CLOSE/UP position. (Safety loops and Photo Eyes are bypassed by EFO/ESO command)

  • EFO/ESO ALARM sounds continuously , until Key RESET of the system at Master Control Panel.

  • Barrier goes to SECURED/CLOSED/UP position in Approx. two seconds or less for EFO/ESO.

  • Verified all ILLUMINATED SWITCHES or LIGHTS are functional on both Master control panel(s) and Remote panel(s) during EFO/ESO.

  • EFO/ESO Initiated. Verified all TRAFFIC LIGHTS are RED and ON - Barrier is in SECURED/CLOSED/UP position are functional during EFO/ESO.

  • Verified all TRAFFIC ARMS - ARM is in the DOWN POSITION when Barrier is moving to the SECURED/CLOSED/UP Position are functional during Normal Operation.

  • Verified all TRAFFIC ARMS - ARM in the DOWN POSITION when Barrier completes to the SECURED/CLOSED/UP Position are functional during EFO/ESO.

  • Verified all TRAFFIC ARMS - ARM in the UP POSITION when Barrier is in the UNSECURED/OPEN/DOWN Position are functional during Normal Operation.

  • Verified Safety Loops for Traffic Arms. (Test while arm is moving DOWN from the UP POSITION.)

  • Verify Barrier Safety Loops. (Test while Barrier is moving from UNSECURE to SECURE position)

  • Enter any corrective actions that WILL NEED to be undertaken

3. Sequence of Operations - SPECIAL MODE/MANUAL MODE.

  • Manual Operation of Barrier.

  • Fill in any Special Sequence of Operations requirements (Card Reader, Roll down doors, ETC.)

4. PLC Settings

  • PLC System Settings

4.1 Barrier Options

  • STOP ON SAFETY

  • EFO RESUME DELAY

  • LOOP 1 PRESENCE ONLY

  • GRAVITY NONSECURE

  • STOP ON SAFETY NONSECURE

  • RESECURE RETRY

  • TRAFF LT RED RESECURE START

  • EFO & SECURE VALVE

  • SAFETY LOOPS

  • ANALOG ON

  • CARD READER

  • STANDARD TANK HPU OR EPU

  • WARNING HORN ALL TRANSITIONS

  • WARNING HORN EXCESSIVE LOOP

  • SYNC MODE

  • NO TRAFFIC AUTOCLOSE

  • PICTURES OF SETTINGS

4.2 BARRIER TIMERS - TIMER VALUES IN TENTHS OF A SECOND (10 = 1 SECOND)

  • SECURE TIME

  • NONSECURE TIME

  • EFO TIME

  • GATE ARM UP TIME

  • GATE ARM DOWN TIME

  • LOOP OCCUPIED TIMER

  • TRAFFIC FIGHT DELAY NONSECURE TIME

  • NONSECURE WARNING TIME

  • PICTURE OF SETTINGS

4.3 ADVANCE BARRIER TIMERS

  • EFO DELAY TIME

  • EFO RESUME DELAY TIME

  • RESECURE DELAY TIME

  • CARD READER CLOSE DELAY TIME

  • NO ENTRY AUTOCLOSE TIME

  • INPUT SCAN TIME

  • Nsec MAX when Nsec TIME

  • Sec MAX when Sec TIME

  • Nsec VALVE HOLD OPEN TIME

  • PRE WARN TIME

  • PICTURE OF SETTINGS

  • 5. Loop Detector Module
  • LOOP Detector Module DIP Settings

  • LOOP Detector LED Status

  • PICTURE OF LOOP DETECTOR MODULE WITH FINAL SETTINGS

6. User Interface Panel - MASTER (MCP)

  • Master Panel Installed

  • Power On and OFF - Keyed switch Installed

  • Verify Operation and Blue Light ON

  • Remote 1 - Keyed switch Installed

  • Verify Operation and Blue Light ON

  • EFO/ESO RESET - Keyed switch Installed

  • Verify Operation

  • EFO/ESO Button with Lockable Cover Installed

  • Verify Operation

  • EFO/ESO RESET - Keyed switch Installed

  • Verify Operation

  • LAMP TEST - Push Button Installed

  • Verify Operation

  • FAULT LIGHT - Installed

  • Verify Operation

  • BARRIER SECURE - PUSH BUTTON (RED) - Installed

  • Verify Operation

  • BARRIER NONSECURE - PUSH BUTTON (GREEN) - Installed

  • Verify Operation

7. User Interface Panel - REMOTE (RCP)

  • REMOTE Panel Installed

  • Power On and OFF - Keyed switch and Blue LED installed

  • EFO/ESO Button with Lockable Cover Installed

  • Verify Operation

  • BARRIER SECURE - PUSH BUTTON (RED) - Installed

  • Verify Operation

  • BARRIER NONSECURE - PUSH BUTTON (GREEN) - Installed

  • Verify Operation

  • LAMP TEST - Push Button Installed

  • Verify Operation

  • FAULT LIGHT - Installed

  • Verify Operation

8. User Interface Panel - LOCAL (LCP)

  • LOCAL Control Panel - LCP (TETHER connection at EPU)

  • Power On and OFF - Keyed switch and Blue LED installed

  • EFO/ESO Button with Lockable Cover Installed

  • Verify Operation

  • FAULT LIGHT - Installed

  • Verify Operation

  • LAMP TEST - Push Button Installed

  • Verify Operation

  • BARRIER SECURE - PUSH BUTTON (RED) - Installed

  • Verify Operation

  • BARRIER NONSECURE - PUSH BUTTON (GREEN) - Installed

  • Verify Operation

APPROVAL AND ACCEPTANCE

9.0 APPROVAL and ACCEPTANCE AUTHORIZED SIGNATURES

  • ELECTRONIC SIGNATURE ACKNOWLEDGE, I AGREE THAT MY ELECTRONIC SIGNATURE
    IS A LEGALLY BINDING EQUIVALENT TO MY HANDWRITTEN SIGNATURE. WHENEVER I
    EXECUTE AN ELECTRONIC SIGNATURE, IT HAS THE SAME VALIDITY AND MEANING AS
    MY HANDWRITTEN SIGNATURE. I WILL NOT AT ANY TIME IN THE FUTURE, REPUDIATE
    THE MEANING OF MY ELECTRONIC SIGNATURE OR CLAIM THAT MY ELECTRONIC SIGNATURE IS NOT LEGALLY BINDING.

  • On Site Representative (GC/Customer)

  • End-User Representative

  • Installer Representative

  • Nasatka Representative

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.